41
PT UNIT USER MANUAL
APRIL 2023 www.eaton.com.cn
A.3.10 Primary Status/Secondary Status/Cause
Code Definitions
Table A14. Primary Status Code Definitions
Code
Definition
0x01
Open
0x02
Closed
0x03
Tripped
0x04
Alarmed
0x0D
Picked-up
Table A15. Secondary Status Code Definitions
Code
Definition
0x01
Not applicable
0x03
Test mode
0x07
Powered-up since last trip/alarm reset
0x08
Alarm
Table A16. Cause Code Definitions
Code
Definition
Code
Definition
0x0000
Unknown
0x0001
Normal
0x0003
Instantaneous
0x0005
Instantaneous neutral
over- current
0x000B
Over-voltage
0x000C
Under-voltage
0x000E
Aux-power under voltage
0x000F
Over-frequency
0x0010
Under-frequency
0x0011
Current unbalance
0x0012
Voltage unbalance
0x0013
Apparent power factor
0x001A
Power demand
0x001B
VA demand
0x001E
THD
0x001F
Operations count
0x0021
Control via communication
0x0025
Coil supervision
0x0028
Current demand
0x0029
Low battery
0x003D
Long delay
0x003E
Short delay
0x0041
Reverse power
0x0044
Phase sequence
0x004B
Making current release
0x004C
Fixed hardware
instantaneous
0x004D
Setpoints error
0x004E
Over-temperature
0x0050
Long delay neutral
over- current
0x0054
Ground fault
0x0055
Earth fault
0x0071
Calibration
0x0088
Real time clock
0x009A
Breaker mechanism fault
0x009E
Short delay neutral
over-current
0x009F
Thermal memory alarm
0x00A0
Local test from LCD
0x00A1
High load alarm 2
0x00A2
Ground alarm early warning
0x00A2
Over-temperature alarm
0x07FD
Non-volatile memory error
0x07FE
Watchdog fault
A.3.11 Exception Codes
When there's error in request or response, trip unit would
respond an exception code.
•
If the function code in the query is not supported by trip
unit, exception code 01 is returned in the response, also
used for the unsupported sub-function code in Modbus
diagnostics.
•
If the requested data register/ bit address is illegal,
excep-tion code 02 is returned.
•
If the data in the query is illegal, exception code 03 is
returned.
•
If the trip unit doesn't support the query function,
exception code 04 is returned.
•
In certain circumstances, exception code 05(ACK) is
returned.
•
If the trip unit can't perform the current request at this
time, a BUSY exception code 06 is returned.
•
If the trip unit can't perform the requested action, a NAK
exception code 07 is returned.
•
If only a partial register is used in the query, exception
code 132 is returned.
•
If the requested event entry doesn't exist, exception
code 135 is returned.
Appendix A - Modbus Communication Port Setting