background image

11

PT UNIT USER MANUAL   

APRIL 2023   www.eaton.com.cn

4. PT Protection Settings

4. PT Protection Settings

The PT unit protection settings are designed to be 

customized to any application. Settings for long delay 

pickup, long delay time, short delay pickup, short delay time, 

instantaneous pickup, ground fault pickup, and ground fault 

time are all independently configurable. These functions 

are set using the Navigation buttons below the display (for 

PT20/25 style) or using rotary switches on the front of the trip 

unit (for PT10 style). 

Please refer to Table 2 for a detailed list of the configurable 

setting values.

Before placing any circuit breaker in operation, set each trip 

unit protection setting to the values specified by the engineer 

responsible for the installation.

4.1 Long Delay Pickup and Time Setting

The PT unit offers a wide range of settings for Long Delay 

Pickup (LDPU or I

r

). This setting ranges from 0.4 to 1.0 and 

is expressed as a multiple of the frame’s current rating (In). 

The pickup value for Long Delay is 105% to 115% of the 

calculated value to ensure that the circuit breaker can carry 

the full rating of (I

r

), without tripping.

The long delay time settings range from 0.5 to 24 seconds. 

They represent the total clearing times when the current 

value equals six times I

r

. All times are referenced from the 

top of the tolerance band, ensuring that the time never 

exceeds that maximum setting. When an I

4

t slope is selected, 

an overload creates a very long-time delay which could 

exceed breaker ratings. Therefore, when a time delay above 

seven seconds is selected, seven seconds will be used 

instead.

If a long delay causes the circuit breaker to trip,

• 

For PT10, the “LONG” indicator will blink.

• 

For PT20/25, the “LONG” indicator will blink. The “LONG 

DELAY” message will be displayed if auxiliary power is 

present.

4.1.1 Long Delay Slope Selection

The I

2

t settings is the factory default curve for long delay. 

The curve can be changed using the display and navigation 

buttons to several alternative curves to better match the 

requirements for protection and coordination. The PT 10 only 

support I

2

t. 

• 

I

0.5

t  - Slightly inverse time curve

• 

It 

- Moderately inverse time curve

• 

I

2

t  - Inverse time current curve, used in standard 

distribution protection (factory default)

• 

I

4

t  - Extremely inverse time current curve, a steep 

protective slope for coordination with fuses or for special 

type of loads.

4.1.2 Long Delay Thermal Memory

In addition to the standard Long Delay protection, a Long 

Time Memory (LTM) function is supported by the trip unit. 

This protects load circuits from the effects of repeated 

overload conditions. LTM is configured using the display 

and Navigation buttons or using the Power TRIP Protection 

Manager software.

As an example, if a circuit breaker is closed soon after a Long 

Delay trip, and the current again exceeds the Long Delay 

setting (Ir), the LTM automatically reduces the time to trip 

to allow for the fact that the load conductor temperature is 

already higher than normal because of the prior overload 

condition. Each time the overload condition is repeated, 

the LTM causes the circuit breaker to trip in a progressively 

shorter time. When the load current returns to normal, the 

LTM begins to reset (after about ten minutes it will have reset 

fully) so the next long delay trip time will again correspond 

to the setting value. It is recommended to disable the LTM in 

certain applications and field tests.

4.2 Short Delay Pickup and Time Settings

Settings for Short Delay Pickup (SDPU or I

sd

) are expressed 

as multiples ranging from 1.5 to 10 for the long delay pickup 

current setting (I

r

 ). 

The short delay time (t

sd

) is selected in conjunction with 

one of two short delay slopes, flat, or I2 t. There are six 

settings for the flat curve of PT10, ranging from 0.05 seconds 

(minimum time) to 0.5 seconds, and four settings for the I

2

inverse time curve, ranging from 0.1 seconds (minimum time) 

to 0.5 seconds.

The I

2

t inverse time curve will provide a longer time delay 

for currents below eight times I

r

 as compared with a flat 

response curve. For currents greater than eight times I

r

, the 

I

2

t response flattens out to the flat response.

If a short delay causes the circuit breaker to trip, 

• 

For PT10, the “SHORT” indicator will blink.

• 

For PT20/25, the “SHORT” indicator will blink.  

The “SHORT DELAY” message will be displayed if auxiliary 

power is present.

The Zone Selective Interlocking (ZSI) feature may affect the 

tripping times for the short delay protective function. Please 

refer to the section on ZSI.

4.3 Instantaneous Pickup Settin

The instantaneous (Ii) setting is expressed as multiples 

ranging from 2 to 15 of the In value or can be set to “OFF”. 

The instantaneous protection trips the breaker with no 

intentional time delay.

Summary of Contents for PT 10

Page 1: ...al Power Trip PT Units Instruction Manual MN013018SC Instructions apply to CCC new generation IZM61 series air circuit breaker CCC new generation IZM65 series air circuit breaker CCC new generation IZ...

Page 2: ...Functionality 9 3 4 Pickup Cause of Trip Indicator 9 3 5 Rotary Switches PT10 only 10 3 6 Reset Button 10 3 7 Door 10 3 8 USB 10 3 9 Battery 10 3 10 In Ratings 10 3 11 Side Labels 10 4 PT PROTECTION S...

Page 3: ...NDARYWIRINGTERMINALSASSOCIATEDWITHTHEPTTRIPUNIT 22 9 TESTING THE TRIP UNIT AND CIRCUIT BREAKER 22 9 1 Functional Opening Test Local via Display 22 9 2 Simulated Current Test Remote via USB PTM Configu...

Page 4: ...ct the circuit breaker before performing maintenance or tests Any tripping operation will cause disruption of service and possible personal injury resulting in the unnecessary switching of connected e...

Page 5: ...ed by the current rating and user selected protection settings There is no mechanical or direct magnetic action between the primary current side and the mechanical tripping parts of the circuit breake...

Page 6: ...etermine the current through the circuit breaker The mechanical action required to initiate tripping of the circuit breaker is provided by a special low energy trip actuator This trip actuator is an i...

Page 7: ...nit Type Catalog Number Protection style LCD Rotary switch Ground fault Modbus RTU Zone inter lock Relay output Digital input PT 10 PT10 LSI PT10G LSIG PT 20 PT20 LSI PT20G LSIG PT20C LSI PT20GC LSIG...

Page 8: ...ds 0 05 0 1 0 2 0 3 0 4 0 5 0 05 0 5 Adjustable step is 0 01 Zone Interlock Enable Disable Instantaneous Protection Instantenous x In Off 2 4 5 6 7 8 10 12 15 Off 2 15 Adjustable step is 0 1 Neutral P...

Page 9: ...1 65500 adjustable Interval of 1 Reverse Power Delay s 1 300 adjustable Interval of 1 Frequency Protection Over frequency Pickup Hz 40 70 adjustable Interval of 1 When Phase A phase voltage exceeds 1...

Page 10: ...it Accuracy Notes VAB VBC VCA Volts 0 5 of Reading Line to Line Voltage Minimum VAB VBC VCA Volts 0 5 of Reading Group values held until reset Maximum VAB VBC VCA Volts 0 5 of Reading Group values hel...

Page 11: ...y Total kWh 2 5 of Reading Forward reverse Real Energy Net kWh 2 5 of Reading Forward reverse Real Energy Forward kWh 2 5 of Reading Delivered by source to load Real Energy Reverse kWh 2 5 of Reading...

Page 12: ...rm Over temperature alarm Clock error See Appendix B Troubleshooting for details When the status indicator remains off there is no auxiliary power applied or insufficient primary current to power the...

Page 13: ...ions from the main menu Each submenu can be accessed by highlighting the appropriate submenu by pressing the Down or Up Arrow buttons then the Enter button 3 3 Password Protection Functionality The cy...

Page 14: ...monitor the trip unit A USB connection will also typically provide power from the host side of the USB cable to power up the trip unit when another source of auxiliary power is not available This con...

Page 15: ...t Extremely inverse time current curve a steep protective slope for coordination with fuses or for special type of loads 4 1 2 Long Delay Thermal Memory In addition to the standard Long Delay protecti...

Page 16: ...ections are indicated with an asterisk while the fixed time flat response time selections are indicated without an asterisk Both have a range from 0 1 seconds to 0 5 seconds PT20 25 For PT20 25 units...

Page 17: ...flowing through the ground conductor When the current measured by the trip exceeds the ground fault setting the circuit breaker will trip or alarm The ground circuit sensing method is usually applied...

Page 18: ...lay setting is reached the trip unit will act Power demand protection When the detected active power is greater than the defined power demand setting and the corresponding time delay setting is reache...

Page 19: ...Zout of that breaker should wired to the Zin of the same breaker to provide a self interlocking feature Refer to Eaton Application Note AP02602002SC for detailed description and examples 4 6 8 Phase L...

Page 20: ...breaker The index starts from zero and increases to 10 000 points depending on the conditions under which the circuit breaker operates The index remains in the frame module of the circuit breaker Chan...

Page 21: ...ed by communications With CAM supported module closing release and shunt release Event Closed by communications Event Time change if 60 seconds Previous time is recorded Alarm Calibration Alarm Setpoi...

Page 22: ...C VCA VAN VBN VCN PT25 only Power Watts Vars VA PT25 only Demand Watts Vars VA PT25 only Temperature Frequency PT25 only Power factor PT25 only Operations count User Waveform or Alarm Waveform Wavefor...

Page 23: ...t point High Load 2 current flow is greater than set point adjustable from 50 to 120 of Ir current flow falls 5 below the set point Over Temperature Alarm temperature exceeds 5 below the level of the...

Page 24: ...ESET button is pressed or communications reset command received Under frequency Alarm under frequency alarm is active and under frequency alarm has occurred RESET button is pressed or communications r...

Page 25: ...d to supply power to the trip unit change and save relevant settings 7 Important System Components 7 1 Auxiliary Power Providing auxiliary power to the PT unit will provide full functionality even whe...

Page 26: ...on and protection schemes the protection settings if altered during any test sequence should be reset to their as found values WARNING Do not attempt to install test or perform maintenance on equipmen...

Page 27: ...y a test current of 125 of the ground pickup setting through one phase of the circuit breaker This should cause the circuit breaker to trip in less than one second and operate the alarm indicator if s...

Page 28: ...for removal Figure 16 Location of the Top and Bottom Trip Unit Screws To install a new trip unit First connect the wiring harness at the top of the trip unit s control module such harness is not avail...

Page 29: ...No Location Circuit Breaker Order Reference Amperes Rating In Continuous Ampere Rating Ir Protection Settings Circle the Selected Value Long Delay Pickup 0 4 0 5 0 6 0 7 75 0 8 0 9 95 98 1 0 Ir A Tim...

Page 30: ...tes in a single Modbus transaction The trip unit responds to a limited number of Modbus function codes These are function codes 02 03 04 06 08 and 16 Function codes 03 and 04 are used interchangeably...

Page 31: ...404623 406159 120E 180E VAB V 10 404625 406161 1210 1810 VBC V 10 404627 406163 1212 1812 VCA V 10 404631 406167 1216 1816 VAN V 10 404633 406169 1218 1818 VBN V 10 404635 406171 121A 181A VCN V 10 4...

Page 32: ...m VCA V 10 404883 406419 1312 1912 Minimum VAN V 10 404885 406421 1314 1914 Maximum VAN V 10 404887 406423 1316 1916 Minimum VBN V 10 404889 406425 1318 1918 Maximum VBN V 10 404891 406427 131A 191A M...

Page 33: ...der register and Register 0 is the low order register Register 3 high byte contains value corresponding to engineering units power of 10 signed exponent Register 3 low byte contains a mantissa multipl...

Page 34: ...67 403004 4 0 0x000F Style R Encoded PT10 16 PT10G 17 PT20 18 PT20G 19 PT20C 20 PT20GC 21 PT25 22 PT25G 23 403005 Style 2 R Invalid 403006 0 0 Invalid R Invalid 403007 0 0 Invalid R Invalid 403008 Fre...

Page 35: ...8 Remote control 29 Mechanical fault trip 30 Mechanical fault alarm 31 Electrical fault alarm 32 Over voltage trip 33 Over voltage alarm 34 Under voltage trip 35 Under voltage alarm 36 Over frequency...

Page 36: ...ixed 1 Sliding 403020 7 0 0x00FF Demand Interval R W Unit Minute 5 to 60 minutes 403021 7 0 0x00FF Breaker Health Alarm Threshold R W Unit Percentage 50 to 100 403022 11 0 0x0FFF System Voltage R W Un...

Page 37: ...pe R W Encoded 0 I0 5t 1 It 2 I2t 3 I4t 403009 6 0 0x007F Long Delay Pickup Ir R W Unsigned 40 100 step is 1 indicating 0 40 In 1 00 In 403010 7 0 0x00FF Long Delay Time tr R W Unsigned 5 240 step is...

Page 38: ...ndicating 0 10 0 50 second 403021 0 0x0001 Ground Fault Thermal memory R W Encoded 0 Disabled 1 Enabled 403022 6 0 0x007F Neutral Protection Ratio R W Unsigned 0 0 60 60 100 100 403023 6 0 0x007F High...

Page 39: ...00FF Voltage Unbalance Protection Threshold Setting R W Unsigned 5 25 step is 1 Unit 403010 11 0 0x0FFF Voltage Unbalance Protection Time Setting R W Unsigned 1 300 step is 1 Unit Seconds 403011 2 0 0...

Page 40: ...Current Demand Protection Setting R W Encoded 0 Trip 1 Alarm 2 OFF 403030 11 0 0x0FFF Current Demand Protection Threshold Setting Phase A R W Unsigned 20 100 step is 1 indicating 0 2In 1 00In 403031 1...

Page 41: ...s in the trip unit registers 408200 and 408202 provide the Previous Event ID and Next Event ID respectively If the requested event does not exist in the trip unit exception code 0x87 is returned The d...

Page 42: ...Event ID 408198 Unsigned32 R W Requested Event ID 408200 Unsigned32 R Previous Event ID 408202 Unsigned32 R Next Event ID 408204 Date Time R Date Time 408212 Encoded R Format of Data Minor Alarm 00061...

Page 43: ...register to provide compatibility and at a new register assignment below 9999 The format is given as low high register numbers followed by low16 high16 Modbus register addresses An example is 4xxxx 4y...

Page 44: ...lock Definition Modbus Register Number Modbus Register Address Data Range Month 402921 0x0B68 1 12 Day 402922 0x0B69 1 31 Year 402923 0x0B6A Day of week 402924 0x0B6B 1 Sunday 7 Saturday Hour 402925 0...

Page 45: ...er current 0x0054 Ground fault 0x0055 Earth fault 0x0071 Calibration 0x0088 Real time clock 0x009A Breaker mechanism fault 0x009E Short delay neutral over current 0x009F Thermal memory alarm 0x00A0 Lo...

Page 46: ...The trip unit is malfunctioning Replace the trip unit The breaker trips too rapidly and reports long delay fault Long Time Thermal Memory Function is selected Disable the Long Time Thermal Memory for...

Page 47: ...not indicating proper state Check the auxiliary switch See the Instructions for Auxiliary Switch The circuit breaker mechanism is not properly closed Contact your Eaton representative for factory assi...

Page 48: ...the purchaser THERE ARE NO UNDERSTANDINGS AGREEMENTS WARRANTIES EXPRESSED OR IMPLIED INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY OTHER THAN THOSE SPECIFICALLY SET OUT I...

Reviews: