33
PT UNIT USER MANUAL
APRIL 2023 www.eaton.com.cn
Table A5. Setpoints Group 1: Protection Group.
Register
Bit Field
Mask
Field
Setpoint Name
R/W
Format
Value Definition
403000
15-0
0xFFFF
Password
W
Factory default = 0000
403001
15-0
0xFFFF
Group 1 = Protection
R/W
0x01FF
403002
15-0
0xFFFF
Rating Information
R
IZM61: 200A,400A,630A,800A,1000A,1250A,1600A
IZM65: 400 A, 630 A, 800 A, 1000 A,1250 A, 1600 A, 2000 A, 2500 A
IZM67: 2000 A, 2500 A,3200 A, 4000 A
403003
2-0
0x007
Breaker Frame
R
Encoded
06 = IZM61
07 = IZM 65
08 = IZM 67
403004
3-0
0xFFFF
Style
R
Encoded
PT10 = 16
PT10G = 17
PT20 = 18
PT20G = 19
PT20C = 20
PT20GC = 21
PT25 = 22
PT25G = 23
403005
Style 2
R
Invalid
403006
0
0x001
Thermal Memory
R/W
Encoded
0 = Disabled
1 = Enabled
403007
0
0x001
ZSI
R/W
Encoded
0 = Disabled
1 = Enabled
403008
1-0
0x003
Curve Slope
R/W
Encoded
0 = I
0.5
t
1 = It
2 = I
2
t
3 = I
4
t
403009
6-0
0x007F
Long Delay Pickup (I
r
)
R/W
Unsigned
40 ~100, step is 1 (indicating 0.40 I
n
~1.00 I
n
)
403010
7-0
0x00FF
Long Delay Time (t
r
)
R/W
Unsigned
5~240, step is 1 (indicating 0.5s to 24s)
403011
6-0
0x007F
High Load Alarm 1
R/W
Unsigned
0: OFF
50<=High load alarm 1< High load alarm 2<=120 (%)
403012
0
0x0001
Short Delay Slope
R/W
Encoded
0 = Flat 1 = I
2
t
403013
7-0
0x00FF
Short Delay Pickup (I
sd
)
R/W
Unsigned
15 ~100, step is 1 (indicating 1.5 I
r
~ 10.0 I
r
)
403014
7-0
0x00FF
Short Delay Time (t
sd
)
R/W
Unsigned
Flat 5~50, step is 1 (indicating 0.05s to 0.50s)
I
2
t 10~50, step is 1 (indicating 0.10s to 0.50s)
403014
LCD Rotation
R
Invalid
403015
7-0
0x00FF
Instantaneous Pickup (L
i
)
R/W
Unsigned
0 = OFF
20~150, step is 1 (indicating 2.0I
n
~15.0I
n
)
403016
0
0x0001
Ground Type
R/W
Encoded
0 = Residual
1 = Source/Zero
403017
0-1
0x0003
Ground Feature
R/W
Encoded
0 = Trip
1 = Alarm
2 = OFF
403018
0
0x0001
Ground Slope
R/W
Encoded
0 = Flat
1 = I
2
t
Appendix A - Modbus Communication Port Setting