background image

39

PT UNIT USER MANUAL   

APRIL 2023   www.eaton.com.cn

Appendix A - Modbus Communication Port Setting

A.3.6 Configuration Registers

Non-volatile register 402001/425345 (0x07D0

16

/0x6300

16

) is 

used to configure the trip unit to respond to a group of data 

objects, of which some objects are invalid within that group. 

When non-zero (default value), any attempt to access a group 

of data objects that contain an invalid object will result in an 

illegal data object code 02. When register 402001/425345 
(0x07D0

16

/0x6300

16

) is set to zero, the trip unit will respond 

to a group of objects with data contained in the valid objects 

of the group along with an illegal value (if available), or else 

000016 data contained in the invalid objects.

Non-volatile register 402002/425346 (0x07D1

16

/0x6301

16

is used to configure the data transmission order of 32-bit 

floating point data. If non-zero (default value), the floating-

point low order word is first in the Modbus register space. 

When the register is set to be 0, the floating-point high 

order word is first in the Modbus register space. Non-volatile 
register 402003/425347 (0x07D2

16

/0x6302

16

) is used to 

configure the data transmission order of 32-bit fixed point 

data. If non-zero (default value), the fixed-point low order 

word is first in the Modbus register space. When the register 

is set to be 0, the fixed-point high order word is first in the 

Modbus register space. 

To accommodate Modbus master that can access up to 

register 9999, some Eaton registers initially assigned above 

9999 have been assigned dual access, both at the original 

register (to provide compatibility) and at a new register 

assignment below 9999. The format is given as low/high 

register numbers followed by (low16/high16 Modbus register 
addresses). An example is: 4xxxx/4yyyyy (XXXX+1

16

/YYYY+1

16

).

Table 10. Configuration Registers

Register

Definition

R/W

Modbus Register

Number

Modbus Register 

Address

Number

Mapped block 

of registers 

configuration

R/W

401001/420481

0x03E8/0x5000

100

Mapped block of 

registers data

R

401201/420737

0x04B0/0x5100

100*2

Invalid 

object access 

configuration

R/W

402001/425345

0x07D0/0x6300

1

Floating point

data word order 

R/W

402002/425346

0x07D1/0x6301

1

Fixed point data 

word order 

configuration

R/W

402003/425347

0x07D2/0x6302

1

Remote control

R/W

402901/425089

0x0B54/0x6200

3

Date and time 

register

R/W

402921

0x0B68

8

A.3.7 Remote Control

A set of registers is used for the trip unit remote control, 

starting from 402901/425089 through 402903/425091. 

These three registers should be written together with a “slave 

action number” and its first complement using function code 

16. The data format registers are shown as Figure A2. The 

“slave action number” and its function are listed in Table A11, 

their support being product dependent.

If the “slave action number" and its first complement 

command is valid, the trip unit will execute the action. Once 

the command is successfully acknowledged by the trip unit, 

it returns a normal function code 16 response to Modbus 

master. Since it may take some time for the trip unit to 

act, Modbus master may further determine if the product 

completed the slave action function successfully after the 

normal response. If the “slave action number” and its first 

complement command is invalid, the trip unit returns 

exception code 03.

Figure A2. Remote Control Data Format 

Summary of Contents for PT 10

Page 1: ...al Power Trip PT Units Instruction Manual MN013018SC Instructions apply to CCC new generation IZM61 series air circuit breaker CCC new generation IZM65 series air circuit breaker CCC new generation IZ...

Page 2: ...Functionality 9 3 4 Pickup Cause of Trip Indicator 9 3 5 Rotary Switches PT10 only 10 3 6 Reset Button 10 3 7 Door 10 3 8 USB 10 3 9 Battery 10 3 10 In Ratings 10 3 11 Side Labels 10 4 PT PROTECTION S...

Page 3: ...NDARYWIRINGTERMINALSASSOCIATEDWITHTHEPTTRIPUNIT 22 9 TESTING THE TRIP UNIT AND CIRCUIT BREAKER 22 9 1 Functional Opening Test Local via Display 22 9 2 Simulated Current Test Remote via USB PTM Configu...

Page 4: ...ct the circuit breaker before performing maintenance or tests Any tripping operation will cause disruption of service and possible personal injury resulting in the unnecessary switching of connected e...

Page 5: ...ed by the current rating and user selected protection settings There is no mechanical or direct magnetic action between the primary current side and the mechanical tripping parts of the circuit breake...

Page 6: ...etermine the current through the circuit breaker The mechanical action required to initiate tripping of the circuit breaker is provided by a special low energy trip actuator This trip actuator is an i...

Page 7: ...nit Type Catalog Number Protection style LCD Rotary switch Ground fault Modbus RTU Zone inter lock Relay output Digital input PT 10 PT10 LSI PT10G LSIG PT 20 PT20 LSI PT20G LSIG PT20C LSI PT20GC LSIG...

Page 8: ...ds 0 05 0 1 0 2 0 3 0 4 0 5 0 05 0 5 Adjustable step is 0 01 Zone Interlock Enable Disable Instantaneous Protection Instantenous x In Off 2 4 5 6 7 8 10 12 15 Off 2 15 Adjustable step is 0 1 Neutral P...

Page 9: ...1 65500 adjustable Interval of 1 Reverse Power Delay s 1 300 adjustable Interval of 1 Frequency Protection Over frequency Pickup Hz 40 70 adjustable Interval of 1 When Phase A phase voltage exceeds 1...

Page 10: ...it Accuracy Notes VAB VBC VCA Volts 0 5 of Reading Line to Line Voltage Minimum VAB VBC VCA Volts 0 5 of Reading Group values held until reset Maximum VAB VBC VCA Volts 0 5 of Reading Group values hel...

Page 11: ...y Total kWh 2 5 of Reading Forward reverse Real Energy Net kWh 2 5 of Reading Forward reverse Real Energy Forward kWh 2 5 of Reading Delivered by source to load Real Energy Reverse kWh 2 5 of Reading...

Page 12: ...rm Over temperature alarm Clock error See Appendix B Troubleshooting for details When the status indicator remains off there is no auxiliary power applied or insufficient primary current to power the...

Page 13: ...ions from the main menu Each submenu can be accessed by highlighting the appropriate submenu by pressing the Down or Up Arrow buttons then the Enter button 3 3 Password Protection Functionality The cy...

Page 14: ...monitor the trip unit A USB connection will also typically provide power from the host side of the USB cable to power up the trip unit when another source of auxiliary power is not available This con...

Page 15: ...t Extremely inverse time current curve a steep protective slope for coordination with fuses or for special type of loads 4 1 2 Long Delay Thermal Memory In addition to the standard Long Delay protecti...

Page 16: ...ections are indicated with an asterisk while the fixed time flat response time selections are indicated without an asterisk Both have a range from 0 1 seconds to 0 5 seconds PT20 25 For PT20 25 units...

Page 17: ...flowing through the ground conductor When the current measured by the trip exceeds the ground fault setting the circuit breaker will trip or alarm The ground circuit sensing method is usually applied...

Page 18: ...lay setting is reached the trip unit will act Power demand protection When the detected active power is greater than the defined power demand setting and the corresponding time delay setting is reache...

Page 19: ...Zout of that breaker should wired to the Zin of the same breaker to provide a self interlocking feature Refer to Eaton Application Note AP02602002SC for detailed description and examples 4 6 8 Phase L...

Page 20: ...breaker The index starts from zero and increases to 10 000 points depending on the conditions under which the circuit breaker operates The index remains in the frame module of the circuit breaker Chan...

Page 21: ...ed by communications With CAM supported module closing release and shunt release Event Closed by communications Event Time change if 60 seconds Previous time is recorded Alarm Calibration Alarm Setpoi...

Page 22: ...C VCA VAN VBN VCN PT25 only Power Watts Vars VA PT25 only Demand Watts Vars VA PT25 only Temperature Frequency PT25 only Power factor PT25 only Operations count User Waveform or Alarm Waveform Wavefor...

Page 23: ...t point High Load 2 current flow is greater than set point adjustable from 50 to 120 of Ir current flow falls 5 below the set point Over Temperature Alarm temperature exceeds 5 below the level of the...

Page 24: ...ESET button is pressed or communications reset command received Under frequency Alarm under frequency alarm is active and under frequency alarm has occurred RESET button is pressed or communications r...

Page 25: ...d to supply power to the trip unit change and save relevant settings 7 Important System Components 7 1 Auxiliary Power Providing auxiliary power to the PT unit will provide full functionality even whe...

Page 26: ...on and protection schemes the protection settings if altered during any test sequence should be reset to their as found values WARNING Do not attempt to install test or perform maintenance on equipmen...

Page 27: ...y a test current of 125 of the ground pickup setting through one phase of the circuit breaker This should cause the circuit breaker to trip in less than one second and operate the alarm indicator if s...

Page 28: ...for removal Figure 16 Location of the Top and Bottom Trip Unit Screws To install a new trip unit First connect the wiring harness at the top of the trip unit s control module such harness is not avail...

Page 29: ...No Location Circuit Breaker Order Reference Amperes Rating In Continuous Ampere Rating Ir Protection Settings Circle the Selected Value Long Delay Pickup 0 4 0 5 0 6 0 7 75 0 8 0 9 95 98 1 0 Ir A Tim...

Page 30: ...tes in a single Modbus transaction The trip unit responds to a limited number of Modbus function codes These are function codes 02 03 04 06 08 and 16 Function codes 03 and 04 are used interchangeably...

Page 31: ...404623 406159 120E 180E VAB V 10 404625 406161 1210 1810 VBC V 10 404627 406163 1212 1812 VCA V 10 404631 406167 1216 1816 VAN V 10 404633 406169 1218 1818 VBN V 10 404635 406171 121A 181A VCN V 10 4...

Page 32: ...m VCA V 10 404883 406419 1312 1912 Minimum VAN V 10 404885 406421 1314 1914 Maximum VAN V 10 404887 406423 1316 1916 Minimum VBN V 10 404889 406425 1318 1918 Maximum VBN V 10 404891 406427 131A 191A M...

Page 33: ...der register and Register 0 is the low order register Register 3 high byte contains value corresponding to engineering units power of 10 signed exponent Register 3 low byte contains a mantissa multipl...

Page 34: ...67 403004 4 0 0x000F Style R Encoded PT10 16 PT10G 17 PT20 18 PT20G 19 PT20C 20 PT20GC 21 PT25 22 PT25G 23 403005 Style 2 R Invalid 403006 0 0 Invalid R Invalid 403007 0 0 Invalid R Invalid 403008 Fre...

Page 35: ...8 Remote control 29 Mechanical fault trip 30 Mechanical fault alarm 31 Electrical fault alarm 32 Over voltage trip 33 Over voltage alarm 34 Under voltage trip 35 Under voltage alarm 36 Over frequency...

Page 36: ...ixed 1 Sliding 403020 7 0 0x00FF Demand Interval R W Unit Minute 5 to 60 minutes 403021 7 0 0x00FF Breaker Health Alarm Threshold R W Unit Percentage 50 to 100 403022 11 0 0x0FFF System Voltage R W Un...

Page 37: ...pe R W Encoded 0 I0 5t 1 It 2 I2t 3 I4t 403009 6 0 0x007F Long Delay Pickup Ir R W Unsigned 40 100 step is 1 indicating 0 40 In 1 00 In 403010 7 0 0x00FF Long Delay Time tr R W Unsigned 5 240 step is...

Page 38: ...ndicating 0 10 0 50 second 403021 0 0x0001 Ground Fault Thermal memory R W Encoded 0 Disabled 1 Enabled 403022 6 0 0x007F Neutral Protection Ratio R W Unsigned 0 0 60 60 100 100 403023 6 0 0x007F High...

Page 39: ...00FF Voltage Unbalance Protection Threshold Setting R W Unsigned 5 25 step is 1 Unit 403010 11 0 0x0FFF Voltage Unbalance Protection Time Setting R W Unsigned 1 300 step is 1 Unit Seconds 403011 2 0 0...

Page 40: ...Current Demand Protection Setting R W Encoded 0 Trip 1 Alarm 2 OFF 403030 11 0 0x0FFF Current Demand Protection Threshold Setting Phase A R W Unsigned 20 100 step is 1 indicating 0 2In 1 00In 403031 1...

Page 41: ...s in the trip unit registers 408200 and 408202 provide the Previous Event ID and Next Event ID respectively If the requested event does not exist in the trip unit exception code 0x87 is returned The d...

Page 42: ...Event ID 408198 Unsigned32 R W Requested Event ID 408200 Unsigned32 R Previous Event ID 408202 Unsigned32 R Next Event ID 408204 Date Time R Date Time 408212 Encoded R Format of Data Minor Alarm 00061...

Page 43: ...register to provide compatibility and at a new register assignment below 9999 The format is given as low high register numbers followed by low16 high16 Modbus register addresses An example is 4xxxx 4y...

Page 44: ...lock Definition Modbus Register Number Modbus Register Address Data Range Month 402921 0x0B68 1 12 Day 402922 0x0B69 1 31 Year 402923 0x0B6A Day of week 402924 0x0B6B 1 Sunday 7 Saturday Hour 402925 0...

Page 45: ...er current 0x0054 Ground fault 0x0055 Earth fault 0x0071 Calibration 0x0088 Real time clock 0x009A Breaker mechanism fault 0x009E Short delay neutral over current 0x009F Thermal memory alarm 0x00A0 Lo...

Page 46: ...The trip unit is malfunctioning Replace the trip unit The breaker trips too rapidly and reports long delay fault Long Time Thermal Memory Function is selected Disable the Long Time Thermal Memory for...

Page 47: ...not indicating proper state Check the auxiliary switch See the Instructions for Auxiliary Switch The circuit breaker mechanism is not properly closed Contact your Eaton representative for factory assi...

Page 48: ...the purchaser THERE ARE NO UNDERSTANDINGS AGREEMENTS WARRANTIES EXPRESSED OR IMPLIED INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY OTHER THAN THOSE SPECIFICALLY SET OUT I...

Reviews: