1 DC1 device series
1.8 Output reduction (derating)
DC1…20… and DC1…OE1 Variable Frequency Drives
02/20 MN040059EN
www.eaton.com
29
1.8 Output reduction (derating)
Derating the DC1 variable frequency drive / limiting the maximum continuous
output current (I
2
) will generally be necessary if, during operation:
•
The ambient air temperature is higher than 40 °C
•
An installation altitude of 1,000 m is exceeded
•
The effective switching frequency is higher than the minimum value
The following tables specify the factors that need to be applied when
selecting a DC1 variable frequency drive if the drive will be run outside these
conditions:
Derating for ambient temperature
Derating for installation altitude
Derating for switching frequency
Enclosure degree
of protection
Maximum permissible ambient air temperature
Derate
without
derating
with
derating
IP20
50 °C
50 °C
1)
none
IP66
40 °C
50 °C
2.5 % per K
1) 45 °C for continuous operation for 24 hours, as per UL, for DC1-12011…B-A20CE1 and DC1-32011…B-A20CE1
Enclosure degree
of protection
permissible altitude
Derate
without
derating
with
derating
IP20, IP66
1000 m
2000 m – with UL Certification
4000 m maximum – without UL
Certification
1 % per 100 m
Enclosure degree
of protection
Switching frequency (P-17), setting (audible)
1)
4 kHz
8 kHz
12 kHz
16 kHz
24 kHz
32 kHz
IP20
none
none
20 %
30 %
40 %
50 %
IP66
none
10 %
25 %
35 %
50 %
50 %
1) The switching frequency’s effective rms value will be approximately half the value set with parameter P-17
(double modulation).