5 Error Messages
5.4 Messages after a data transfer with a DX-COM-STICK3
142
DC1…20… and DC1…OE1 Variable Frequency Drives
02/20 MN040059EN
www.eaton.com
5.4 Messages after a data transfer with a DX-COM-STICK3
Table 32: Possible messages after a data transfer
5.5 Operating status indicators
The six flashing dots on the seven-segment display are used to indicate
various operating statuses.
View
Description
P
A
SS-r
Parameter transfer to DX-COM-STICK3 was successful
OS-Loc
DX-COM-STICK3 locked.
In order to transfer data, check the switch position on the side.
F
A
iL-r
Error while attempting to read the parameters from the variable frequency drive.
P
A
SS-t
Parameter transfer to variable frequency drive successful.
F
A
iL-P
The parameter set stored in the DX-COM-STICK3 is for a different rating (different motor
current, motor output, etc.) than that of the connected variable frequency drive.
Fail-t
Error when attempting to copy parameter set to variable frequency drive
no-d
A
t
No data found in DX-COM-STICK3.
dr-Loc
Parameter set in variable frequency drive locked. Unlock variable frequency drive first.
dr-rVn
The variable frequency drive has an enable signal and cannot take new parameters.
Stop the variable frequency drive.
tyPE-E
The parameter set stored in the DX-COM-STICK3 does not match the variable frequency drive.
Only transfers from the variable frequency drive to the DX-COM-STICK3 are possible.
tyPE-F
The DX-COM-STICK3 is not compatible with the variable frequency drive.
8
.
8
.
8
.
8
.
8
.
8
.
↓
↓
↓
↓
↓
↓
1
2
3
4
5
6
Number(s)
Behavior
Significance
1, 2, 3, 4, 5, 6
Flash synchronously
Overload
The current current exceeds the value set with P-08.
1, 6
Flash in an alternating
pattern
Power outage or power supply switched off
1
Flashes
Fire Mode enabled