6 Technical Data
6.1 General rating data
DC1…20… and DC1…OE1 Variable Frequency Drives
02/20 MN040059EN
www.eaton.com
145
6 Technical Data
6.1 General rating data
Technical data
Symbol
Unit
Value
General
Standards
EMC: EN 61800-3:2004+A1-2012
Radio interference: EN 55011: 2010
Security: EN 61800-5: 2007
Degree of protection: EN 60529: 1992
Soiling: IEC 721-3-3
Certifications and manufacturer’s declarations on conformity
CE, UL, cUL, c-Tick, UkrSEPRO, Gost-R
Production quality
RoHS, ISO 9001
Climatic proofing
ρ
w
%
< 95 %, average relative humidity (RH),
non-condensing (EN 50178)
Ambient air temperature
Operational
IP20 (NEMA 0)
ϑ
°C
-10 - +50 without derating
-10 - +45 for DC1-12011… and DC1-32011…,
for UL compliance over a period of 24 hours
IP66 (NEMA 4X)
ϑ
°C
-20 - +40 without derating
Storage
ϑ
°C
-40 - +60 (frost-free and condensation-free)
pollution degree
Non-conductive dust permissible
Transport
IP20: Class 1C2 (chemical gases), Class 1S2 (solid particles)
IP66: Class 1C3 (chemical gases), Class 1S3 (solid particles)
Storage
IP20: Class 2C2 (chemical gases), Class 2S2 (solid particles)
IP66: Class 2C3 (chemical gases), Class 2S3 (solid particles)
Operational
IP20: Class 3C2 (chemical gases), Class 3S2 (solid particles)
IP66: Class 3C3 (chemical gases), Class 3S3 (solid particles)
Vibration level (not evaluated during operation)
Shock test
Pulse shape
Half sinus
Top acceleration
15 g
Time Window
11 ms
Vibration test
Frequency range
f
Hz
10 - 150
10 - 57.55: 0.15 mm peak-peak
57.55 - 150: 1 g Top acceleration
Vibration evaluation
1 octave/minute
MTBF (mean time between failures)
Years
157
Electrostatic discharge (ESD, EN 61000-4-2:2009
U
kV
±4, contact discharge
±8, air discharge
Fast transient burst (EFT/B, EN 61000-4-4: 2004)
U
kV
±1, at 5 kHz, control signal terminal
±2, at 5 kHz, motor connection terminals,
single-phase mains connection terminals
±4, at 5 kHz, three-phase mains connection terminals
Summary of Contents for PowerXL DC1-122D3NN-A20CE1
Page 4: ...II...