3.6.2.7 Analog output signal
When the device is used with its default settings, there will be an analog
voltage signal (0 - 10 V) available at control signal terminal 8. This value will
correspond to 0 to 100% of P-01 (maximum frequency / speed). The output
can handle a maximum load of 20 mA.
Parameter P-25 is used to configure whether this output signal will be
provided at the terminal:
Table 16: Control signal terminal 8 (AO)
3.6.2.8 Relay contact
Control signal terminals 10 and 11 are connected to the DC1 variable
frequency drive’s internal relay contact (N/O) in a potential-free manner.
The relay function can be configured with parameter P-18:
P-25
Signal
(0 - +10 V)
Description
8
f-Out
Output frequency (f-Out) / speed
0 - 100 % of P-01
Resolution: 0.1 Hz
9
I-Out
Output current (I-Out) / motor current
0 - 100 % of P-08
Resolution: 0.1 A
12
P-Out
Output power (P-Out)
0 - 200% relative to the DC1’s rated motor output
Analog output AO: Accuracy
≧
1% relative to maximum value; resolution: 10-bit
Figure 57:
Analog output (AO)
(connecting example)
→
Control terminals 7 and 9 are the common 0 V reference
potential for all analog and digital input signals.
9
0...+10 V
AO
8
OV
<
20 mA
f-Out
-
+