OPERATION
EATON
BladeUPS
®
(12 kVA) User's Guide
S
164201649 Rev 4
www.eaton.com/powerquality
67
Table 4. User Settings (continued)
Default Setting
Available Settings
Description
Battery Setup
Number of EBMs: [0 through 4]
(See “Configuring the UPS for EBMs” on page 74.)
0
(means internal batteries only)
Battery Low Alarm Level: [1.750 through 1.950 volts per cell]
(See “Setting the Battery Low Alarm Level” on page 75.)
1.880 V/cell
(provides approximately 2.5 min warning
for the UPS)
Automatic Battery Tests: [Enabled] [Disabled]
(See “Running Automatic Battery Tests” on page 75.)
Enabled
(automatically runs the battery test once
a month)
External Battery Capacity: Set Watts per cell
Use this setting only in conjunction with customer-supplied
external batteries and the External Battery Interconnect.
None
Power Strategy
[High Efficiency] [Standard]
For more information, see the following section, “Operating
Modes.”
High Efficiency
Start Screen
Eaton logo
Mimic screen (see Figure 45 on page 63)
Eaton logo
User Password
[Enabled] [Disabled]
If Enabled is selected, the password is USER.
Disabled
Audible Alarms
[Normal Sound] [Disabled]
Normal Sound
Unsynchronized Transfer to Bypass
[Allowed] [Not Allowed]
Not Allowed
Transfer to Bypass When Overload
[After a delay] [Immediately]
After a delay
Automatic Start Delay
-1 through 32767 seconds
(-1 means disabled)
0s
Control Commands from X-Slot1
Control Commands from X-Slot2/Serv
[Allowed] [Disabled]
Selecting Disabled prevents load commands such as Load Off
through the X-Slot, including remotely.
Allowed
X-Slot Signal Input Activation Delay
0 through 65 seconds
5s
Site Wiring Fault Notice
[Enabled] [Disabled]
Enabled
Reset Custom Event Settings
0 through 32
Total: 0/32
REPO Configuration
[Enabled][Disabled]
Enabled
Operating Modes
The BladeUPS module front panel indicates the UPS status through the UPS
indicators. Figure 44 on page 63 shows the UPS front panel indicators and controls.
Normal Mode
During Normal mode, the
indicator illuminates solid and the utility powers the
UPS. The UPS monitors and charges the batteries as needed and provides filtered
power protection to your equipment.
By default, the BladeUPS module operates on a High Efficiency setting that minimizes
heat contribution to the rack environment. The system bypass input directly supplies
the system output with three-phase AC power, and the UPS stands ready to
automatically transfer to double-conversion (Standard) operation as needed. The
battery recharges when necessary.
Summary of Contents for Powerware Series
Page 1: ...Powerware Series Eaton BladeUPS 12 kVA User s Guide ...
Page 2: ......
Page 3: ...Powerware Series Eaton BladeUPS 12 kVA User s Guide ...
Page 84: ...OPERATION EATON BladeUPS 12 kVA User s Guide S 164201649 Rev 4www eaton com powerquality 76 ...
Page 119: ......
Page 120: ... 1642016494 164201649 4 ...