MBM INSTALLATION PLAN AND UNPACKING
Eaton 9395 Maintenance Bypass Module Installation and Operation Manual
S
164201719 Rev 3
www.eaton.com/powerquality
3-11
Table 3‐9. Power Cable Terminations for the Eaton 9395 550 kVA MBM
Terminal Function
Terminal
Function
Size of Pressure
Termination
Tightening
Torque
Nm (lb in)
Hex Size
AC Input to Maintenance
Bypass
E1
Phase A
4 - #2-600 kcmil
56.5 (500)
1/2
”
Hex
E2
Phase B
4 - #2-600 kcmil
56.5 (500)
1/2
”
Hex
E3
Phase C
4 - #2-600 kcmil
56.5 (500)
1/2
”
Hex
AC Output from Optional
RIB to UPS
RIB-1
Phase A
4 - 3/0-400 kcmil
31.1 (275)
5/16
”
Hex
RIB-3
Phase B
4 - 3/0-400 kcmil
31.1 (275)
5/16
”
Hex
RIB-5
Phase C
4 - 3/0-400 kcmil
31.1 (275)
5/16
”
Hex
AC Output from Optional
BIB to UPS
BIB-1
Phase A
4 - 3/0-400 kcmil
31.1 (275)
5/16
”
Hex
BIB-3
Phase B
4 - 3/0-400 kcmil
31.1 (275)
5/16
”
Hex
BIB-5
Phase C
4 - 3/0-400 kcmil
31.1 (275)
5/16
”
Hex
AC Input from UPS to MIS
MIS-1
Phase A
4 - 3/0-400 kcmil
31.1 (275)
5/16
”
Hex
MIS-3
Phase B
4 - 3/0-400 kcmil
31.1 (275)
5/16
”
Hex
MIS-5
Phase C
4 - 3/0-400 kcmil
31.1 (275)
5/16
”
Hex
AC Output to Critical Load
E13
Phase A
4 - #2-600 kcmil
56.5 (500)
1/2
”
Hex
E14
Phase B
4 - #2-600 kcmil
56.5 (500)
1/2
”
Hex
E15
Phase C
4 - #2-600 kcmil
56.5 (500)
1/2
”
Hex
Input and Output Neutral
E12
Neutral
12 - #2-600 kcmil
56.5 (500)
1/2
”
Hex
Customer Ground
GND
Ground
6 - #6-350 kcmil
31.1 (275)
5/16
”
Hex
NOTE
Customer ground sized in accordance with NEC Table 250.122.