MBM INSTALLATION
Eaton 9395 Maintenance Bypass Module Installation and Operation Manual
S
164201719 Rev 3
www.eaton.com/powerquality
4-24
4.3.7
MBP, MIS, BIB, and RIB Current Settings
The MBP, MIS, BIB, and RIB are adjustable trip breakers set at the factory. These
breakers are designed to control the input and output to the UPS.
Verify the settings of the installed MBP, MIS, BIB, and RIB match the values listed in
Table 4‐2 and Table 4‐3. Use the continuous current (Ir) dial on each breaker to adjust
the trip current as necessary.
Table 4‐2. Recommended Maximum MBM MBP, MIS, and BIB Circuit Breaker Ratings
MBM Model
UPS Rating
Continuous Current (Ir)
Breaker Setting
Eaton 9395 275 kVA MBM
225 kVA
300A
B
275 kVA
350A
D
300 kVA
400A
E
Eaton 9395 550 kVA MBM
450 kVA
600A
A
500 kVA
700A
Set dial half-way
between A and B
550 kVA
700A
Set dial half-way
between A and B
Table 4‐3. Recommended Maximum MBM RIB Circuit Breaker Ratings
MBM Model
UPS Rating
Continuous Current (Ir)
Breaker Setting
Eaton 9395 275 kVA MBM
225 kVA
350A
D
275 kVA
400A
E
300 kVA
400A
E
Eaton 9395 550 kVA MBM
450 kVA
700A
Set dial half-way
between A and B
500 kVA
700A
Set dial half-way
between A and B
550 kVA
800A
B
4.4
Initial Startup
Startup and operational checks must be performed by an authorized Eaton Customer
Service Engineer, or the warranty terms specified on page NO TAG become void. This
service is offered as part of the sales contract for the MBM. Contact an Eaton service
representative in advance (usually a two-week notice is required) to reserve a
preferred startup date.