
POWER WIRING INSTALLATION NOTES
032406
E
164201554---5
12 of 15
DESCRIPTION:
DATE:
DRAWING NO:
SHEET:
REVISION:
Installation Information
A-23
EATON
Powerware
®
9390 UPS (100–160 kVA) Installation and Operation Manual
S
164201554 Rev E
powerware.com
Table O. INPUT/OUTPUT Ratings for Powerware 9390---120/100 and 9390---160/100 Parallel Systems
Configuration
Units
Rating 50/60 Hz
Basic Unit Rating at 0.9 lagging pF load
kVA
kW
100
90
100
90
Input and Bypass Input
Output
VOLTS
VOLTS
208/220
208/220
480
480
All
AC Input from UPM
Full Load Current for each Module
(3) Phases, (1) Neutral---if required, (1) Ground
D
Amps
278/262
120
Minimum Conductor Size for each Module
Number per Phase for each Module
AWG or kcmil
(each)
See Table E through
Table G for wire size.
1+1
AC Input to Tie Cabinet Bypass (optional)
Full Load Current
(3) Phases, (1) Neutral---if required, (1) Ground
F
Amps
278/262
120
AC Output to Critical Load
Full Load Current
(3) Phases, (1) Neutral---if required, (1) Ground
G
Amps
278/262
120
System Neutral Bonding Jumper
Minimum Conductor Size
Number (See Note 27)
---
AWG or kcmil
(each)
1/0
(1)
4
(1)
2+0
and
2+1
AC Input to Tie Cabinet Bypass (optional)
Full Load Current
(3) Phases, (1) Neutral---if required, (1) Ground
F
Amps
556/524
240
AC Output to Critical Load
Full Load Current
(3) Phases, (1) Neutral---if required, (1) Ground
G
Amps
556/524
240
System Neutral Bonding Jumper
Minimum Conductor Size
Number (See Note 27)
---
AWG or kcmil
(each)
3/0
(1)
1/0
(1)
3+0
and
3+1
AC Input to Tie Cabinet Bypass (optional)
Full Load Current
(3) Phases, (1) Neutral---if required, (1) Ground
F
Amps
834/786
360
AC Output to Critical Load
Full Load Current
(3) Phases, (1) Neutral---if required, (1) Ground
G
Amps
834/786
360
System Neutral Bonding Jumper
Minimum Conductor Size
Number (See Note 27)
---
AWG or kcmil
(each)
1/0
(2)
2/0
(1)
4+0
AC Input to Tie Cabinet Bypass (optional)
Full Load Current
(3) Phases, (1) Neutral---if required, (1) Ground
F
Amps
1112/1048
480
AC Output to Critical Load
Full Load Current
(3) Phases, (1) Neutral---if required, (1) Ground
G
Amps
1112/1048
480
System Neutral Bonding Jumper
Minimum Conductor Size
Number (See Note 27)
---
AWG or kcmil
(each)
2/0
(2)
2/0
(1)
NOTE:
Callout letters
D
,
F
, and
G
map to Drawing 164201554---4, sheets 4 of 6, 5 of 6,
and 6 of 6.
Summary of Contents for Powerware 9390-160/100
Page 1: ...Powerware 9390 UPS 100 160 kVA Installation and Operation Manual...
Page 225: ......
Page 226: ...164201554E 164201554 E...