Indication
Log*
Relay
Phone
Horn
Message
Output AC Under Voltage
1
No
No
HA Information Only
Output AC Under Voltage OK
Off
No
No
HA Condition Cleared
Output Under or Over Frequency
1
No
No
HA Information Only
Output Under or Over Frequency OK
Off
No
No
HA Condition Cleared
Rectifier Current Over 125%
1
No
No
A
Information Only
Rectifier Input Over Current
1
No
No
A
Information Only
UPS Module Off
1
No
No
A
Information Only
UPS Module Off OK
Off
No
No
A
Condition Cleared
UPS on Battery
1
No
No
A
Investigate UPS
UPS on Battery OK
Off
No
No
A
Condition Cleared
UPS on Bypass
1
No
No
A
Investigate UPS
UPS on Bypass OK
Off
No
No
A
Condition Cleared
UPS on Generator
1
No
No
A
Information Only
UPS on Generator OK
Off
No
No
A
Condition Cleared
*Log codes indicate where the UPS records the event: H = History log; HA = History and Active logs; and