Using the Control Panel
9-45
EATON
Powerware
®
9390 UPS (100–160 kVA) Installation and Operation Manual
S
164201554 Rev E
powerware.com
9.3
System Controls Screen
Press the
CONTROLS
pushbutton on the main menu bar to display the System Controls
screen. LOAD OFF, normal operation, transfer to bypass, charger control, and power
module startup and shutdown functions are controlled from this screen. In addition, the
screen displays the current status of the UPS and indicates whether the UPS is in
Maintenance Bypass or Bypass, and the state of the power module (PM) and battery
charger. Figure 9-51 and Figure 9-52 show the System Controls screens.
Use the
or
pushbutton on the menu bar to toggle the menu bar functions between
the two System Controls screens.
MAINTENANCE BYPASS
BYPASS
POWER MODULE (PM)
OFF
:
OFF
:
ONLINE
:
SYSTEM CONTROLS
LOAD OFF
BYPASS
NORMAL
CHARGER
OFF
:
Figure 9-51. System Controls Screen 1