The Color Monitor backpanel has these connections:
•
Power connections: 120V AC, 230V AC, and 24VDC (230V is optional and requires a different transformer.)
•
Modbus connections:
–
Downstream (to Monitor device chain) is always 4-wire Modbus
–
Upstream is 4-wire or 2-wire, jumper selected
•
Summary Alarm: Dry contact (NO) signals when the Monitor has an alarm condition. Dry contact
specification: 0.5A at 120VAC or 30VDC.
The backpanel also has a RESET button: If the Monitor hangs, you can reset it by pressing this button.
Figure 39. Color Monitor Backpanel