Eaton PDI WaveStar Color Monitor Setup and Operation Manual P-164001109—Rev 01
39
Figure 33. Find the Circuits in an Alarm Condition
Touch
DEVICES
button to display the device list.
Find the
Device Name
noted in the alarm in the device list.
Touch the
Device Name
to display its screen chain.
Step through the device’s screen chain
(using
NEXT
) to find the screen with the
ALARM
column.
Scroll through the device’s circuits to
find the component in alarm. (Alarm
shows as
ACTIVE
under
ZERO
,
WARNING
, or
ALARM
.)
Review information for that circuit on
all of the device’s screens.
77..33
A
Allaarrm
mss bbyy D
Deevviiccee TTyyppee
Each device has its own alarm set based on its points list. Warnings and alarms that can be viewed on the
Monitor are listed below. The Monitor does not display setpoints from the points lists, such as alarm
thresholds.
77..33..11
C
Coolloorr M
Moonniittoorr A
Allaarrm
mss
Table 2. Monitor Alarms
Alarm
Alarm Description
DISPLAY Comm. N Error (N is device
number from 1-20):
Communication error with one of the devices in the Monitor’s downstream device
chain
Summary of Contents for PDI WaveStar
Page 1: ...p n P 164001109 Revision 01 Setup and Operation Manual Eaton PDI WaveStar Color Monitor...
Page 4: ......
Page 12: ...2 Eaton PDI WaveStar Color Monitor Setup and Operation Manual P 164001109 Rev 01 Safety...
Page 60: ...50 Eaton PDI WaveStar Color Monitor Setup and Operation Manual P 164001109 Rev 01 Web Pages...
Page 62: ...52 Eaton PDI WaveStar Color Monitor Setup and Operation Manual P 164001109 Rev 01 Glossary...
Page 64: ...54 Eaton PDI WaveStar Color Monitor Setup and Operation Manual P 164001109 Rev 01 Bibliography...
Page 68: ...P 16400110901 P 164001109 01...