32
Eaton PDI WaveStar Color Monitor Setup and Operation Manual P-164001109—Rev 01
66..44
B
BC
CM
MS
S K
KW
WH
H R
Reeaaddiinnggss
Compared to BCMS Normal, BCMS KWH panelboard devices have one additional screen showing power
measurements (KWH, etc.) for individual circuits. The first screen in the device’s chain provides KW, KVA,
KVAR, and power factor readings for each panelboard circuit (see and ).
Figure 26. Readings: BCMS KWH (Part 1)
Select
device name. Device name will highlight in blue.
Users can change the device name in
SETTINGS
.
Select
READINGS
to display panelboard power data.
Scroll among
READINGS
pages using
PREVIOUS/NEXT
buttons.
Panelboard Circuits Instantaneous
Readings:
NO
= Circuit Number (scroll through 42
circuits)
AMPS
= Amperes
KW
= Kilowatts
KVA
= Kilovolt-Amperes
KVAR
= Kilovolt-Amperes Reactive
PF
= Power Factor
Panelboard Circuits, Measurements
and Alarms:
NO
= Circuit Number
AMPS
= Amperes
CB
= Circuit breaker rating (Amps)
MIN
= Lowest current read
MAX
= Highest current read
ZERO
: OK = Current has not dropped to 0
since last reset; ACTIVE = Current has
read 0 after having read a minimum
current
WARNING
: OK = No warning
outstanding; ACTIVE = warning
outstanding
ALARM
: OK = No alarm outstanding;
ACTIVE = Alarm is outstanding
Summary of Contents for PDI WaveStar
Page 1: ...p n P 164001109 Revision 01 Setup and Operation Manual Eaton PDI WaveStar Color Monitor...
Page 4: ......
Page 12: ...2 Eaton PDI WaveStar Color Monitor Setup and Operation Manual P 164001109 Rev 01 Safety...
Page 60: ...50 Eaton PDI WaveStar Color Monitor Setup and Operation Manual P 164001109 Rev 01 Web Pages...
Page 62: ...52 Eaton PDI WaveStar Color Monitor Setup and Operation Manual P 164001109 Rev 01 Glossary...
Page 64: ...54 Eaton PDI WaveStar Color Monitor Setup and Operation Manual P 164001109 Rev 01 Bibliography...
Page 68: ...P 16400110901 P 164001109 01...