Eaton PDI WaveStar Color Monitor Setup and Operation Manual P-164001109—Rev 01
7
C
Chhaapptteerr 33 C
Coolloorr M
Moonniittoorr N
Neettw
woorrkkiinngg
33..11
S
Suuppppoorrtteedd P
Prroottooccoollss
All protocols supported by the Color Monitor can be used simultaneously.
Downstream Protocol
The downstream device network has fixed parameters of Modbus RTU, 9600 baud,
EVEN parity.
Upstream Protocols
There are separate upstream ports for Modbus RTU and Ethernet, supporting these
protocols:
•
Modbus RTU
•
Ethernet port
–
TCP/IP, used by the web page server (see
)
–
Modbus TCP/IP
–
SNMP Version 1
33..22
M
Moonniittoorr N
Neettw
woorrkk C
Coonnnneeccttiioonnss
The Color Monitor’s backpanel has Modbus RTU and Ethernet ports (see
For Color Monitors embedded in Eaton products (PDUs, RPPs, or JCOMMs), Modbus RTU backpanel
connections are typically made in manufacturing and extended to a terminal block or external panel for
convenient customer access. See paragraph
Customer Modbus RTU Connections
The customer’s Ethernet cable is connected directly to the Monitor’s Ethernet port.
Figure 4. Color Monitor Network Connections
Summary of Contents for PDI WaveStar
Page 1: ...p n P 164001109 Revision 01 Setup and Operation Manual Eaton PDI WaveStar Color Monitor...
Page 4: ......
Page 12: ...2 Eaton PDI WaveStar Color Monitor Setup and Operation Manual P 164001109 Rev 01 Safety...
Page 60: ...50 Eaton PDI WaveStar Color Monitor Setup and Operation Manual P 164001109 Rev 01 Web Pages...
Page 62: ...52 Eaton PDI WaveStar Color Monitor Setup and Operation Manual P 164001109 Rev 01 Glossary...
Page 64: ...54 Eaton PDI WaveStar Color Monitor Setup and Operation Manual P 164001109 Rev 01 Bibliography...
Page 68: ...P 16400110901 P 164001109 01...