40
Eaton PDI WaveStar Color Monitor Setup and Operation Manual P-164001109—Rev 01
77..33..22
P
PD
DU
U A
Allaarrm
mss
Table 3. General PDU Alarms
Warning or Alarm
Alarm Description
EPO
Emergency Power Off on PDU has been engaged. When EPO button is pushed, the
alarm is activated and the unit’s main input circuit breaker will then be shunt-tripped
off line.
Remote EPO
Remote EPO on PDU can be activated in by closing the contacts on the contractor
board. When Remote EPO button is activated, the alarm is activated and the unit’s
main input circuit breaker will then be shunt-tripped off line.
Thermal Overtemp
Stage 1 transformer temperature alarm: 180
⁰
F or higher temperature registered in the
transformer windings.
Thermal Hightemp
Stage 2, PDU shutdown on transformer temperature alarm by tripping main PDU input
circuit breaker when 195
⁰
F or higher temperature is registered in the transformer
windings. (Temperature threshold can vary by transformer and PDU.)
Phase Rotation
Input phase rotation is incorrect.
S1-S2 Phase Angle
Dual input sources are not synchronized; cannot shutdown one source and transfer
load to the alternate source.
Ground Curr Trip
Ground current above preset level (10A) causes breaker trip (normally disabled, enable
as option).
Phase Rotation Trip
Incorrect phase rotation causes breaker trip (normally disabled, enable as option).
Over Voltage Trip
Over voltage causes breaker trip (normally disabled, enable as option).
Table 4. PDU Transformer Input
Alarm
Alarm Description
NOTE
: If the PDU is configured for dual inputs, "Input 1" or "Input 2" will prefix the alarm instead of "Input."
Input Voltage AB High
Input voltage AB measures above threshold level in points list.
Input Voltage AB Low
Input voltage AB measures below threshold level in points list.
Input Voltage BC High
Input voltage BC measures above threshold level in points list.
Input Voltage BC Low
Input voltage BC measures below threshold level in points list.
Input Voltage CA High
Input voltage CA measures above threshold level in points list.
Input Voltage CA Low
Input voltage CA measures below threshold level in points list.
Input Frequency High
Input frequency measures above threshold level.
Input Frequency Low
Input frequency measures below threshold level.
Input Current A High
Input current phase A measures above threshold level (optional).
Input Current A Low
Input current phase A measures below threshold level (optional).
Input Current B High
Input current phase B measures above threshold level (optional).
Summary of Contents for PDI WaveStar
Page 1: ...p n P 164001109 Revision 01 Setup and Operation Manual Eaton PDI WaveStar Color Monitor...
Page 4: ......
Page 12: ...2 Eaton PDI WaveStar Color Monitor Setup and Operation Manual P 164001109 Rev 01 Safety...
Page 60: ...50 Eaton PDI WaveStar Color Monitor Setup and Operation Manual P 164001109 Rev 01 Web Pages...
Page 62: ...52 Eaton PDI WaveStar Color Monitor Setup and Operation Manual P 164001109 Rev 01 Glossary...
Page 64: ...54 Eaton PDI WaveStar Color Monitor Setup and Operation Manual P 164001109 Rev 01 Bibliography...
Page 68: ...P 16400110901 P 164001109 01...