54
Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P-164001106—Rev 01
66..22..22
A
Annaalloogg S
Seennssoorrss:: P
Paanneellbbooaarrdd C
CTT S
Sttrriippss
Panelboards have side mounted CT strips with (42) CTs each. To view panelboard sensor data, select the
panelboard symbol. Panelboards have multiple menus that can be viewed using the slide-out side menu.
Figure 41. Panelboard Screens (Part One)
Select the Menu Icon
to view options.
Select
Panel 1
Panelboard circuits can have limits
speci
�
ied individually by circuit.
Bars are colored by status:
Green = Under limit (OK).
Orange = Above warning limit
Red = Above alarm limit
Current/Power
Screen
by circuit (CKT):
Current(A)
Load (% of Breaker Rating)
Power(KW)
Power(KVA)
Power(KVAR)
Power Factor(PF)
Circuit Status:
–Good (Green)
– Warning (Orange)
–Alarm (Red)
Summary of Contents for PDI WaveStar Infinity 2
Page 4: ......
Page 78: ...P 16400110601 P 164001106 01...