64
Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P-164001106—Rev 01
Table 6. Replacing a Failed Panelboard CT – Procedure (Continued)
5.
Select the
CT FIX
button to bring up
CT Fix
screen.
6.
Select the CT strip with the failing CT from the
drop-down list.
7.
The
CT Fix
screen shows available and assigned
CT Fix positions. Three (3) substitute CT positions
are available for each panelboard strip.
8.
Select a CT Fix position. (CT Fix 1=Top, 2=Middle,
3=Bottom on the panelboard strip.) The scrollable
CT list is shown truncated here.
In this example, a split-core CT will be connected to
CT Fix 1
position to substitute for
CT2
.
9.
CT Fix
screen shows
CT Fix 1
position in use for
CT2.