Quick Start Guide

1

IQ 35M Meter Series

  IB02601008E    September 2011  www.eaton.com

ZL0073-0C

IQ 35M Meter Series

RoHS

Compliant

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

•  Follow safe electrical work practices. See NFPA 70E in the USA, or applicable local codes.
•  This equipment must only be installed and serviced by qualified electrical personnel.
•  Read, understand and follow the instructions before installing this product.
•  Turn off all power supplying equipment before working on or inside the equipment.
•  Any covers that may be displaced during the installation must be reinstalled 
  before powering the unit.
•  Use a properly rated voltage sensing device to confirm power is off.
  DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION

Failure to follow these instructions will result in death or serious injury.

DANGER

NOTICE

•  This product is not intended for life or safety applications.

•  Do not install this product in hazardous or classified locations.

•  The installer is responsible for conformance to all applicable codes.

•  Mount this product inside a suitable fire and electrical enclosure.

This symbol indicates an electrical 

shock hazard exists.

Documentation must be consulted where 

this symbol is used on the product.

FCC PART 15 INFORMATION

NOTE:  This equipment has been tested by the manufacturer and found 

to comply with the limits for a class B digital device, pursuant to part 

15 of the FCC Rules. These limits are designed to provide reasonable 

protection against harmful interference when the equipment is 

operated in a residential environment. This equipment generates, uses, 

and can radiate radio frequency energy and, if not installed and used 

in accordance with the instruction manual, may cause harmful 

interference to radio communications. Operation of this equipment in 

a residential area may cause harmful interference in which case the 

user will be required to correct the interference at his own expense. 

Modifications to this product without the express authorization of the 

manufacturer nullify this statement. 

For use in a Pollution Degree 2 or better environment only. A Pollution Degree 2 

environment must control conductive pollution and the possibility of condensation 

or high humidity. Consider the enclosure, the correct use of ventilation, thermal 

properties of the equipment, and the relationship with the environment. Installation 

category:  CAT II or CAT III

Provide a disconnect device to disconnect the meter from the supply source. Place 

this device in close proximity to the equipment and within easy reach of the opera-

tor, and mark it as the disconnecting device. The disconnecting device shall meet 

the relevant requirements of IEC 60947-1 and IEC 60947-3 and shall be suitable 

for the application. In the US and Canada, disconnecting fuse holders can be used. 

Provide overcurrent protection and disconecting device for supply conductors with 

approved current limiting devices suitable for protecting the wiring. If the equipment 

is used in a manner not specified by the manufacturer, the protection provided by 

the device may be impaired.

Specifications

Measurement Accuracy:

 

   Real Power and Energy 

IEC 62053-22 Class 0.5S, ANSI C12.20  

 0.5%

Input Voltage Characteristics:

 

   Measured AC Voltage 

Min. 90 V

L-N

 (156 V

L-L

) for stated accuracy

 

UL Maximums:  600 V

L-L

 (347 V

L-N

)

 

CE Maximums:  300 V

L-N

 (520 V

L-L

)

   Impedance 

2.5 M

Ω

 (L-N)/5 M

Ω

 (L-L)

   Frequency Range 

45 to 65 Hz

Input Current Characteristics:

 

   Measurement Input Range 

0 to 0.333 VAC or 0 to 1.0 VAC 

 

(+20% over-range)

   Impedance 

10.6 k

Ω

 (1/3 V mode) or 32.1 k

Ω

 (1 V mode)

Control Power:

 

   AC 

5 VA max.; 90 V min.

 

UL Maximums:  600 V

L-L

 (347 V

L-N

)

 

CE Maximums:  300 V

L-N

 (520 V

L-L

)

   DC * 

3 W max.; UL and CE: 125 to 300 VDC

   Ride Through Time 

100 msec at 120VAC

Mechanical Characteristics:

 

   IP Degree of Protection (IEC 60529) 

IP40 front display; IP20 Meter

   Terminal Block Screw Torque 

3.5 in-lb (0.4 N·m) nominal/

 

4.4 in-lb (0.5 N·m) max.

   Terminal Block Wire Size 

14 to 24 AWG

   Rail 

T35 (35mm) DIN Rail per EN50022

Environmental Conditions:

 

   Operating Temperature  

-30° to 70°C

   Storage Temperature 

-40° to 85°C

   Humidity Range 

<95% RH (non-condensing)

   Altitude of Operation 

3 km max.

Metering Category:

 

   North America 

CAT III; for distribution systems 

 

up to 347 V

L-N

/600 VAC

L-L

   CE 

CAT III; for distribution systems 

 

up to 300 V

L-N

   Dielectric Withstand 

Per UL 508, EN61010

   Conducted and Radiated Emissions 

FCC part 15 Class B, EN55011/EN61000

 

Class B (residential and light industrial)

   Conducted and Radiated Immunity 

EN61000 Class A (heavy industrial)

Safety:

 

   North America (cULus) 

UL508 (open type device)/

 

CSA 22.2 No. 14-05

   Europe (CE) 

EN61010-1:2001

* External DC current limiting is required. See Fuse Recommendations

CAUTION

RISK OF EQUIPMENT DAMAGE

• This product is designed only for use with 1V or 0.33V current 

transducers (CTs).

• DO NOT USE CURRENT OUTPUT (e.g. 5A) CTs ON THIS PRODUCT.

• Failure to follow these instructions can result in overheating and 

permanent equipment damage.

Additional Resources:

For a copy of the full installation guide 

for this product, visit www.eaton.com