IQ 35M Meter Series

   IB02601008E    September 2011  www.eaton.com

ZL0073-0C

Dimensional Drawings 

4.2” 

(107mm)

3.6” 

(91mm)

1.5” 

(39mm)

2.3” 

(59mm)

1.9” 

(48mm)

1.8” 

(45mm)

3.6 “

(91 mm)

4.2 “

(107 mm)

0.2 “

(4 mm)

3.9“

(99 mm)

2.4 “

(61 mm)

+

+

+

4.3 “

(109 mm)

1.2 “

(31 mm)

0.3 “

(8 mm)

0.4 “

(10 mm)

Bottom View 

(DIN Mount Configuration)

Bottom View 

(Screw Mount Configuration)

Housing

Product Diagram

Installation

Disconnect power prior to installation.

Any covers that may be displaced during the installation must be reinstalled 

before powering the unit.

Mount the meter in an appropriate electrical enclosure near equipment to be moni-

tored.

Do not install on the load side of a Variable Frequency Drive (VFD).

For Bidirectional models, observe correct CT orientation.

The meter can be mounted in two ways:  on standard 35 mm DIN rail or screw-mounted to the back 

of the enclosure.

A.  DIN Rail Mounting

1.  Attach mounting clips to the underside of the housing by sliding them into the slots 

from the inside. The stop-

ping pegs must face the 

housing, and the outside 

edge of the clip must be 

flush with the outside edge 

of the housing.

2.  Snap the clips onto the DIN 

rail. See diagram of the 

underside of the meter.

3.  To prevent horizontal shift-

ing across the DIN rail, use 

two Eaton IQ35M-DRSC end stop clips or equivalent.

 

B.  Screw Mounting

1.  Attach the mounting clips to the 

underside of the housing by slid-

ing them into the slots from the 

outside. The stopping pegs must 

face the housing, and the screw 

hole must be exposed on the 

outside of the housing.

2.  Use three #8 screws (not sup-

plied) to mount the meter to 

the back of the enclosure. See 

diagram of the underside of the 

meter.

Clip flush with 
outside edge

Snap onto 
DIN rail

Insert clips from inside

Screw holes 
exposed for 
mounting

Insert clips from outside

Alarm

Energy





Two 5-character rows 
of display text. 
Top row alphanumeric; 
Bottom row numeric only

The red Alarm LED lights when 
any of the 3 phase voltages drop 
below the selected threshold: 

 On models with pulse outputs 

(all except IQ 35MA15), the 
green Energy LED lights when 
the Energy pulse output contacts 
are closed. 

 On models with pulse inputs 

(IQ 35MA15), the green Energy 
LED lights when the pulse 1 
input contacts are active or 
closed.

CONTROL POWER

0.1A  50/60 Hz

A

B

C

N

1

2

A

B

C

Alarm

Energy

NC

NO

+    -     S

OUTPUT

Common - 1 or 1/3 VAC Input

-

+

-

+

-

+

IA

IB

IC

VA

VB

VC

Neutr

al

Ear

th

Con

trol

Po

we

r

Func

tions 

var

y b

model

UL: 90V 

L-N

 - 600V 

L-L

        CE: 90V 

L-N

 - 300V 

L-N

VOLTAGE INPUTS
CAT III  50/60 Hz

+

Alarm

NC

Pulse L

oss

Alarm O

utput

Energy

NO

Pulse O

utput

Pulse Inputs

1

Pulse Input 1

2

Pulse Input 2

IQ35MA11/IQ35MAx2/

IQ35MAx3

IQ 35MA15

+    -     S

VARh

VAR

h O

utput

No C

onnec

t

+    -     S

RS-485

Modbus

Shield

+    -     S

RS-485

BA

Cnet

Shield

IQ 35MA11 - Pulse

IQ 35MAx2 and IQ 

35MAx3 - Modbus

IQ 35MA15 - BACnet

Product Identification

Model

Description

Output

Pulse

Alarm

Modbus BACnet

IQ 35MA11

Pulse output only

IQ 35MA12

Modbus output

IQ 35MA13

Modbus output, data logging

IQ 35MA15

BACnet MS/TP, data logging, 

Pulse contact inputs

IQ 35MA22

Modbus output, bidirectional

IQ 35MA23

Modbus output, bidirectional, 

data logging