IQ 35M Meter Series

   IB02601008E    September 2011  www.eaton.com

ZL0073-0C

L1

N

L2 L3

X2

X1

A

B

C

N

A

B

C

X2

X1

X2

X1

+

-

+

-

+

-

White

Black

White

Black

White

Black

Diagram 5:  3-Phase 4-Wire Wye Direct 

Voltage Input Connection 3 CT

USE SYSTEM TYPE 40 (3L + 1n)

White

Black

White

Black

White

Black

L1

N

L2 L3

X2

X1

A

B

C

N

A

B

C

X2

X1

X2

X1

+

-

+

-

+

-

Diagram 6:   3-Phase 4-Wire Wye 

Connection 3 CT 3 PT

USE SYSTEM TYPE 40 (3L + 1n)

Direct Connect Control Power (DC)

L1

N

L2 L3

1 2

G

L1

N

L2 L3

1 2

G

L1

1 2

G

L2 L3

Direct Connect Control Power (Line to 

Neutral)

Line to Neutral from 90VAC to 347VAC (UL) or 300VAC (CE)

1 2

G

Control Power Transformer (CPT) 

Connection

Direct Connect Control Power (Line to 

Line)

Line to Line from 90VAC to 600VAC (UL) (520 VAC CE). In UL 

installations, the lines may be floating (i.e. a delta). If any 

lines are tied to an earth (i.e. a corner grounded delta), see 

the Line to Neutral installation limits. In CE installations, 

the lines must be neutral (earth) referenced at less than 

300VAC

L-N

.

The Control Power Transformer may be wired L-N or L-L.  

Output to meet meter input requirements

DC Control Powerfrom 125VDC to 300VDC (UL and CE max.). 

Fuse Recommendations:  

Keep the fuses close to the power source (obey local and 

national code requirements).

For selecting fuses and circuit breakers, use the fol-

lowing criteria:

 

z

Current interrupt capacity should be selected based 

on the installation category and fault current capa-

bility.

 

z

Over-current protection should be selected with a 

time delay.

 

z

The voltage rating should be sufficient for the input 

voltage applied.

 

z

Provide overcurrent protection and disconnecting 

means to protect the Wiring. For DC installations, 

the installer must provide external circuit protection 

(suggested:  0.5A, time delay fuses).

 

z

The earth connection is required for electromagnetic 

compatibility (EMC) and is not a protective earth 

ground.

Wiring Notes:

 

z

Use 14-24 gauge wire for all connections.

 

z

When tightening terminals, ensure that the correct 

torque is applied:  3.5 - 4.4 in·lb (0.4-0.5 N·m).

Wiring Diagrams

N L1

 

X2

X1

White

Black

A

B

C

N

+

-

+

-

+

-

A

B

C

Diagram 1:  1-Phase Line-to-Neutral 

2- Wire System 1 CT 

Diagram 2:  1-Phase Line-to-Line 2-Wire 

System 1 CT

L1 L2

X2

X1

X2

X1

A

B

C

N

+

-

+

-

+

-

A

B

C

N

White

Black

White

Black

L1 L2

X2

X1

A

B

C

N

+

-

+

-

+

-

A

B

C

White

Black

 Diagram 3:  1-Phase Direct Voltage 

Connection 2 CT

L1 L2 L3

X2

X1

A

B

C

N

A

B

C

X2

X1

X2

X1

+

-

+

-

+

-

White

Black

White

Black

White

Black

 Diagram 4:  3-Phase 3-Wire 3 CT no PT

USE SYSTEM TYPE 11 (2L)

USE SYSTEM TYPE 12 (2L + 1n)

USE SYSTEM TYPE 31 (3L)

USE SYSTEM TYPE 10 (1L + 1n)

Warning:  CT negative terminals are refer-

enced to the meter’s neutral (N) and may be 

elevated from ground.

For IQ 35MA1x models, CTs are not polarity sensitive. No need to observe orientation.

For IQ 35MA2x models, CTs are polarity sensitive. Observe correct orientation as shown below.

Control Power