IQ 35M Meter Series

   IB02601008E    September 2011  www.eaton.com

ZL0073-0C

Solid-State Pulse Output (IQ 35MA11, IQ 35MA12, IQ 

35MA13, and IQ 35MA2x Only

These models have one normally open (N.O.) KZ Form A output and one normally 

closed (N.C.) KY output. One is dedicated to energy (Wh), and the other to Alarm. 

The IQ 35MA11 also provides an additional N.O. reactive energy (VARh) contact. 

See the Setup section for configuration information.

The solid state pulse outputs are rated for 30VAC/DC nom.

Maximum load current is 100mA at 25°C. Derate 0.56mA per °C above 25°C (e.g. 

86mA@50°C).

* The over-current protective device must be rated for the short circuit current at the 

connection point.

** All pulse outputs and communication circuits are only intended to be connected 

to non-hazardous voltage circuits (SELV or Class 2). Do not connect to hazardous 

voltages.

~

=

~

=

≤ 100 mA

≤ 100 mA

~

=

≤ 100 mA

Alarm

Energy

Output

+         –         S

Power Source**

3-30VDC

6-30VAC

Power Source**

3-30VDC

6-30VAC

Over-Current Protective

Device* (not supplied)

Power Source**

3-30VDC

6-30VAC

(IQ 35MA11 only)

Daisy-chaining Devices to the Power Meter 

The RS-485 slave port allows the power meter to be connected in a daisy chain with 

up to 63 2-wire devices. In this bulletin, communications link refers to a chain of 

devices that are connected by a communications cable.

NOTES:

RS-485 Communications (Modbus and BACnet models only)

+

S

Red

Black

 

Gray

 

3.5

–4.4 in•lb

(0.4–0.5 

N•

m)

Use 14-24 gauge wire

• 

The terminal’s voltage and current ratings are compliant with the require-
ments of the EIA RS-485 communications standard.

• 

The RS-485 transceivers are ¼ unit load or less.

• 

RS-485+ has a 47 k

Ω

 pull up to +5V, and RS-485- has a 47 k

Ω

 pull down 

to Shield (RS-485 signal ground).

• 

Wire the RS-485 bus as a daisy chain from device to device, without 
any stubs. Use 120 

Ω

 termination resistors at each end of the bus (not 

included). 

• 

Shield is not internally connected to Earth Ground.

• 

Connect Shield to Earth Ground somewhere on the RS-485 bus.

• 

Use 14 to 24 gauge wire for all connections.

• 

When tightening terminals, ensure that the correct torque is applied:  
3.4-4.4 in·lb (0.4-0.5 N·m).

+

S

120

Ω

 terminator on 

the first and last de-

vice of the daisy chain

Belden 1120A or 

equivalent

Shield wire

Pulse Contact Inputs (IQ 35MA15 Only)

The IQ 35MA15 has two inputs with pulse accumulators for solid state or mechanical contacts 

in other sensors, such as water or gas flow meters. These inputs are isolated from the measured 

circuits and referenced to the communication signal ground. Use with contacts that do not require 

current to remove oxidation.

+         –            S

+

~10 kΩ

Comm

Ground

4-10 VDC

nominal

Pulse Input 

Contacts

Equivalent 

Circuit