Supported system types

The meter has a number of different possible system wiring configurations (see Wiring Diagrams, page 9-10). To configure the meter, set the System Type via the User 

Interface, Modbus register 130 (IQ35MAx2 and IQ35MAx3), or BACnet Analog Value Object AV2 (IQ 35MA15). The System Type tells the meter which of its current and volt-

age inputs are valid, which are to be ignored, and if neutral is connected. Setting the correct System Type prevents unwanted energy accumulation on unused inputs, selects 

the formula to calculate the Theoretical Maximum System Power, and determines which phase loss algorithm is to be used. The phase loss algorithm is configured as a 

percent of the Line-to-Line System Voltage (except when in System Type 10) and also calculates the expected Line to Neutral voltages for system types that  have Neutral 

(12 & 40).

Values that are not valid in a particular System Type will display as “----” on the User Interface or as QNAN in the Modbus registers or BACnet Analog Input objects

CTs

Voltage Connections

System Type

Phase Loss Measurements

Wiring 

Diagram

Number of 

wires

Qty

ID

Qty

ID

Type

Modbus Register  130 or

BACnet Analog Value object AV2

User Interface: 

SETUP> S SYS

VLL

VLN

Balance

Diagram 

number

Single-Phase Wiring

2

1

A

2

A, N

L-N

10

1L + 1n

AN

1

2

1

A

2

A, B

L-L

11

2L

AB

2

3

2

A, B

3

A, B, N

L-L with N

12

2L + 1n

AB

AN, BN

AN-BN

3

Three-Phase Wiring

3

3

A, B, C

3

A, B, C

Delta

31

3L

AB, BC, CA

AB-BC-CA

4

4

3

A, B, C

4

A, B, C, N Grounded Wye 40

3L + 1n

AB, BC, CA

AN, BN, CN

AN-BN-CN & AB-BC-CA

5, 6

To avoid distortion, use parallel wires for control power and voltage inputs.

The following symbols are used in the wiring diagrams on the following page.

Symbol

Description

Voltage Disconnect Switch

Fuse (installer is responsible for ensuring compliance with local requirements. No fuses are included with 

the meter.)

Earth ground

X2

X1

Current Transducer

Potential Transformer

Protection containing a voltage disconnect switch with a fuse or disconnect circuit breaker. The protection 

device must be rated for the available short-circuit current at the connection point.

Display Diagram




Tx

Rx

ERR

Screen Name or Units

Diagnostic 
Alert

Numeric 
Data

Alive Indicator

RS-485 Equipped Units Only:

          Transmit Data

          Receive Data

          Receive Data Error

LCD Screen:

Buttons:

+

(Up)

Select

(Right)

Next

(Down)

Select

(Left)

Back


Export (IQ 35MA2x models only)
Import (IQ 35MA2x models only)

Reviews: