FLA DIAL ADJUSTMENT - For motors having a 1.15
service factor, rotate the FLA adjustment dial to corre-
spond to the motor’s FLA rating. Estimate the dial posi-
tion when the motor FLA falls between two letter values
as shown in the example.
For motors having 1.0 service factor, rotate the FLA dial
one-half position counter-clockwise (CCW).
.254
.306
.359
.411
H2001B
.375
.452
.530
.607
H2002B
.560
.676
.791
.907
H2003B
.814
.983
1.15
1.32
H2004B
1.20
1.45
1.71
1.96
H2005B
1.79
2.16
2.53
2.90
H2006B
2.15
2.60
3.04
3.49
H2007B
3.23
3.90
4.56
5.23
H2008B
4.55
5.50
6.45
7.40
H2009B
6.75
8.17
9.58
11.0
H2010B
9.14
10.8
12.4
14.0
H2011B
14.0
16.9
19.9
22.8
H2012B
18.7
22.7
26.7
30.7
H2013B
23.5
28.5
33.5
—
H2014B
Reset
Adjustment
Dial
Example of setting for
manual reset.
TEST FOR TRIP INDICATION - To test overload relay
for trip indication when in manual reset, pull out the blue
reset button. An orange flag will appear indicating that
the device has tripped. Push reset button into reset.
NEMA SIZE 0 AND 1
HEATER PACK SELECTION TABLE
MOTOR FLA RATING
FLA DIAL POSITIONS
STD
TRIP
CLASS 20
SIZE F
NEMA SIZE 2
HEATER PACK SELECTION TABLE
MOTOR FLA RATING
FLA DIAL POSITIONS
STD
TRIP
CLASS 20
SIZE J AND K
NEMA SIZE 3 and 4
HEATER PACK SELECTION TABLE
MOTOR FLA RATING
FLA DIAL POSITIONS
STD
TRIP
CLASS 20
SIZE N
A
B
C
D
3.23
3.90
4.56
5.23
H2008B
4.55
5.50
6.45
7.40
H2009B
6.75
8.17
9.58
11.0
H2010B
9.14
10.8
12.4
14.0
H2011B
14.0
16.9
19.9
22.8
H2012B
18.7
22.7
26.7
30.7
H2013B
23.5
28.5
33.5
38.5
H2014B
29.0
34.0
39.1
44.1
H2015B
39.6
45.5
51.5
57.4
H2016B
53.9
60.9
67.9
74.9
H2017B
A
B
C
D
18.0
20.2
22.3
24.5
H2018
24.6
27.6
30.5
33.4
H2019
33.5
37.5
41.5
45.6
H2020
45.7
51.2
56.7
62.1
H2021
62.2
69.7
77.1
84.6
H2022
84.7
94.9
105
115
H2023
106
118
131
144
H2024
A
B
C
D
MAXIMUM RATINGS
NEMA SIZE
AMPERES
SIZE
AMPERS
0
18
1
27
F
32
Use 75
°
C copper conductors only
Max. Wire Size - 8 AWG
WARNING - To provide continued protection against fire
or shock hazard, the complete overload relay must be
replaced if burnout of the heater element occurs.
MAXIMUM RATINGS
NEMA SIZE
AMPERES
SIZE
AMPERS
2
45
J
60
K
73
NOTE: After the above referenced settings have been
made, rotate the FLA dial one position clockwise for
these heaters (see table). If less than one position is
available, rotate dial to maximum. This note does not
apply when these heaters are used with adapter base.
Catalog No. C306TB1.
NOTE: After the above referenced settings have been
made, rotate the FLA dial one position clockwise for these
heaters (see table). If less than one position is available,
rotate dial maximum. This note does not apply when these
heaters are used with adapter base. Catalog No. C306TB1.
Exception: does not apply to AN16DN0.
Example of a 12.0 FLA setting for a heater pack number H2011B
showing position for 1.0 or 1.15 service factor motor.
MANUAL/AUTOMATIC RESET - The overload relay is
factory set at “M” for manula reset operation as shown
in the illustration. For automatic reset operation, turn
the reset adjustment dial to the “A” position. Automatic
reset is not intended for two-wire control devices.
FLA
Adjustment
Dial
1.0
Service
Factor
1.0
Service
Factor
Use 75
°
C copper conductors only
Max. Wire Size - 3 AWG
MAXIMUM RATINGS
NEMA SIZE
AMPERES
SIZE
AMPERS
3
90
N*
14
4*
135
NOTES: Part Winding Starters - Select heater packs
for 50% of the motor FLA
Wye Delta Starters - Select heater packs for 58%
motor FLA
For motor FLA values not listed, turn the dial clockwise
for higher or counterclockwise for lower ratings.
Minimum Wire Size - 6 AWG
■
■
◆
●
●
◆
◆
●
◆
A
M
➞ ➞
B
A
C
D
➞➞