20
Troubleshooting a UPS equipped with the HotSwap MBP module
If a fault leads to UPS shutdown, press the ON/OFF button
(27)
to clear the fault.
5.2 Battery Module Replacement
Safety recommendations
Servicing of batteries should be performed or supervised by personnel knowledgeable about batteries and the
required precautions. Risk of explosion if battery is replaced by an incorrect type. When replacing batteries, replace
with the same type and number of batteries or battery packs.
CAUTION:
Do not dispose of batteries in a fire. The batteries may explode. Dispose of used batteries according
to the instructions.
CAUTION:
Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes. It may be
toxic.
CAUTION:
A battery can present a risk of electrical shock and high short circuit current. The following precau-
tions should be observed when working on batteries:
a. Remove watches, rings, or other metal objects.
b. Use tools with insulated handles.
c. Wear rubber gloves and boots.
d. Do not lay tools or metal parts on top of batteries.
e. Disconnect charging source prior to connecting or disconnecting battery terminals.
f. Determine if battery is inadvertently grounded. If inadvertently grounded, remove source from ground.
Contact with any part of a grounded battery can result in electrical shock. The likelihood of such shock can
be reduced if such grounds are removed during installation and maintenance (applicable to equipment and
remote battery supplies not having a grounded supply circuit).
Indication
Diagnostic
Correction
12
The load is no longer supplied
when the rotary switch
(53)
on
the HotSwap MBP module is set
to the Bypass position.
w
The protected devices are con-
nected to the UPS output instead
of to the HotSwap MBP module.
w
The AC power cord is connected
to the UPS input instead of to the
HotSwap MBP module.
Check the wiring between the UPS
and the HotSwap MBP module (see
Section 2.6).
13
The load is no longer supplied
when the rotary switch
(53)
on
the HotSwap MBP module is set
to the Normal position.
w
The UPS is shut down.
w
The wiring between the UPS
and the HotSwap MBP module
is not correct.
w
Start the UPS.
w
Check the wiring between the UPS
and the HotSwap MBP module (see
Section 2.6).
14
The load is no longer supplied
if AC power fails.
w
The rotary switch
(53)
on the
HotSwap MBP module is set to
the Bypass position.
w
The wiring between the UPS
and the HotSwap MBP module
is not correct.
w
Set the rotary switch
(53)
on
the HotSwap MBP module to the
Normal position.
w
Check the wiring between the UPS
and the HotSwap MBP module (see
Section 2.6).
w
Ups is shutdown
86-86710-00EN A02 - Page 24
5. Troubleshooting
86-86710-00 A02 UM.indd 24
14/01/2009 10:56:29
Battery-module removal
Mounting the new battery module
Carry out the above instructions in reverse order.
w
To ensure safety and high performance, use only batteries supplied by EATON.
w
Take care to firmly press together the two parts of the connector during remounting.
A
. Unscrew the left-hand side of the front
panel (two screws), then remove the part.
B
. Disconnect the battery block by separating
the two connectors (never pull on the
wires).
C
. Unscrew the metal bracket and remove the
part.
D.
Pull out the battery pack.
86-86710-00EN A02 - Page 25
5. Troubleshooting
86-86710-00 A02 UM.indd 25
14/01/2009 10:56:30
Summary of Contents for EX Pulsar Series
Page 2: ...w P 86 86710 00...
Page 4: ......
Page 6: ......
Page 9: ...3 LED LED LED CFC HCFC UPS EATON EATON UPS EATON UPS...
Page 10: ...4...
Page 18: ...12 86 86710...
Page 22: ...16...
Page 33: ...www eaton com 86 86710 00 A02 86 86710 00 A02 UM indd 34 14 01 2009 10 56 53 www eaton com...
Page 34: ...w P 86 86710 00...
Page 36: ......
Page 38: ......
Page 42: ...4 86 86710 00...
Page 50: ...12 86 86710 00 This page left blank intentionally...
Page 54: ...16 4 4 4 86 86710 00 This page left blank intentionally...