Output Personalization

 

ON/OFF Personalization

Battery Personalization

4.4  Personalization Using External Software

 

 

Insert the Solution-Pac CD-ROM in the drive.

 

On the first navigation screen, select “Point to Point solution” and follow the instructions on how to install the 
Personal Solution-Pac software.

 

Then select “Settings”, “Advanced settings” and “UPS settings”.

Note that the Linux/Unix/MacOS versions of the Personal Solution-Pac software do not offer this possibility.

 

(1). These Parameters may be modified only when the UPS is OFF.

 

(2). Bypass is disabled when frequency converter is enabled.

Function

Factory Setting

Options

Comments

Output voltage

 

(1)

100 VAC

100/104/110/120/125 VAC

Frequency converter

 

(1)

Disabled

Enabled 

(2)

The connected devices are never 
transferred to the bypass.

Output frequency

 

(1)

Automatic selection

50 or 60 Hz

User selectable only if the 
frequency-converter function is 
enabled.

Transfer to the bypass 

AC input

 

(1)

Bypass AC power must be 

within tolances

Bypass AC power may be 

outside tolerances

Overload level

 

(1)

102%

50 / 70%

Alarm if threshold is overrun.

Function

Factory Setting

Options

Comments

Battery test

Weekly test

No test / daily test / monthly 

test

Selection of the 

backup time

Automatic detection of 
number of battery modules

0 to 200 Ah

UPS restarts automatically when 
Normal AC source is restored.

Battery protection 
against excessive 

discharges

Enabled

Disabled

When function disabled, EATON 
warranty no longer applies.

Function

Factory Setting

Options

Comments

Start on battery power Enabled 

Disabled

Automatic restart

Enabled

Disabled

The UPS restarts automatically 
when AC power returns.

Energy savings

Disabled

Enabled

When function enabled, battery 
shuts down when power drops  

to <5%.

Detection of phase/ 
neutral inversion 

(SWF)

Enabled

Disabled

When function enabled, the UPS 
remains OFF if the system detects 

phase/neutral inversion.

86-86710-00EN A02 - Page 22

4. Access to Maintenance and Personalization Data

86-86710-00 A02 UM.indd   22

14/01/2009   10:56:28

5. Maintenance

5.1  Troubleshooting 

 

If LED 

(21)

 or 

(22) 

is ON, a fault or an alarm has occurred. Use the escape button 

(24)

 to stop the audio alarm.

Indication

Diagnostic

Correction

1

The UPS does not start, the LCD 

indicates: COLD START NOK 

CHECK AC WIRING

The AC input power is not 

connected or is connected to the 

UPS output.

Check AC power availability.

Check the UPS is correctly 

connected to the AC input power.

2

LED 

(22) 

is ON, the SWF LED 

(11)

 at the rear of the UPS is ON. 

The LCD indicates: SITE WIR. 

FAULT CHECK AC WIRING

Phase inversion on AC input 

power. The UPS does not start.

Check polarity and grounding system.

3

LED 

(22)

 is ON, the LCD 

indicates: NO BATTERY CHECK 

CONNECTION

The battery is incorrectly 

connected.

Check battery connections (see 

Section 5.2, Battery-module 

replacement).

4

LED 

(22)

 is ON, the LCD 

indicates: BATTERY FAULT 

SERV REQUIRED

A fault is detected on the battery. Replace the battery (see  Section 5.2, 

Battery-module replacement). Call the 

after-sales support department.

5

LED 

(21)

 is ON, the LCD 

indicates: OVERLOAD ALARM 

REDUCE LOAD

The load level exceeds the 

programmed overload level or 

UPS capacity.

Reduce the load.

6

LED

 (22)

 is ON, the LCD 

indicates: LOAD UNPROTECTED 

OUTPUT OVERLOAD

The UPS is overloaded. Devices 

connected to the UPS are fed 

directly by the electrical network 

via the By-pass.

Check the power drawn by the 

connected devices and disconnect any 

non-priority devices.

7

LED 

(22)

 is ON, the LCD 

indicates: REDUCE LOAD 

RESTART UPS

After repetitive overloads, the UPS 

is locked in the By-pass position. 

Devices connected to the UPS 

are fed directly by the electrical 

network.

Check the power drawn by the 

connected devices and disconnect any 

non-priority devices. Shut down and 

restart the UPS to return to normal 

operation.

8

LED 

(22) 

is ON, the LCD 

indicates: OVERLOAD FAULT 

REDUCE LOAD

The UPS shut down automatically 

because of overload at the UPS 

output.

Check the power drawn by the 

connected devices and disconnect any 

non-priority devices.

9

LED 

(22)

 is ON, the LCD 

indicates: LOAD SHORT-CIRCU 

CHECK WIRING

The UPS shut down automatically 

because of a short-circuit at the 

UPS output.

Remove the load, and then restart the 

UPS.

10

LED 

(22)

 is ON, the LCD 

indicates: INTERNAL FAULT 

SERV REQUIRED

A UPS internal fault has occurred. 

There are two possible situations:  

w

 the load is still supplied, but 

directly with AC power via the 

bypass,  

w

 the load is no longer supplied.

Call the after-sales support

department.

11

The LCD indicates: REMOTE 

POWER OFF RPO

Switching of the Remote Power 

Off (RPO) has led to the shut 

down of the UPS.

Return the contact in the normal 

position, and press the ON/OFF button 

to restart.

86-86710-00EN A02 - Page 23

86-86710-00 A02 UM.indd   23

14/01/2009   10:56:29

Summary of Contents for EX Pulsar Series

Page 1: ...ion and User Manual English EX 2200 RT 2U 3000 RT 2U EXB RT 3U Pulsar Series 86 86710 00 A02 UM indd 1 14 01 2009 10 56 17 Installation and User Manual EX 2200 RT 2U 3000 RT 2U EXB RT 3U Pulsar Series...

Page 2: ...w P 86 86710 00...

Page 3: ...nglish EX 2200 RT 2U 3000 RT 2U EXB RT 3U Pulsar Series 86 86710 00 A02 UM indd 1 14 01 2009 10 56 17 EX 2200 RT 2U 3000 RT 2U EXB RT 3U Pulsar Series www eaton com 2010 EATON Email JapanSales Eaton c...

Page 4: ......

Page 5: ...2 6 1 3 6 2 2 1 7 2 2 8 2 3 8 2 4 9 2 5 FlexPDU 10 2 6 MBP 10 2 7 FlexPDU MBP UPS 11 3 3 1 13 3 2 14 3 3 AC 14 3 4 UPS 14 3 5 UPS 15 4 4 1 17 4 2 17 4 3 17 4 4 18 5 5 1 19 5 2 20 5 3 MBP UPS 22 6 6 1...

Page 6: ......

Page 7: ...1 EATON EX VCCI A III IV UPS EATON EX www eaton com EATON UPS EATON CFC HCFC 50 PS PET 01 HDPE 02 PVC 03 LDPE 04 PP 05 PS 06 www eaton com 01 PET 01 PET...

Page 8: ...A VCCI 2008 04 Class A EN 62040 2 IEC 62040 2 IEC 61000 4 2 ESD IEC 61000 4 3 Radiated eld IEC 61000 4 4 EFT IEC 61000 4 5 Surge IEEE C6241 Category B Ring wave IEC 61000 4 6 Electromagnetic eld IEC...

Page 9: ...3 LED LED LED CFC HCFC UPS EATON EATON UPS EATON UPS...

Page 10: ...4...

Page 11: ...56 20 1 Presentation 1 1 Standard Positions Tower Position Rack Position Dimensions H x W x D in inches EX 2200 RT 2U 17 3 x 3 38 x 25 2 EX 3000 RT 2U 17 3 x 3 38 x 25 2 EX EXB RT 3U 17 3 x 5 16 x 19...

Page 12: ...onnection of equipment 10 10 foot input power cord w L5 30P for EX 3000 w 5 20P for EX 2200 11 LED SWF indicating distribution system phase neutral reversal 12 Connectors for battery modules to the UP...

Page 13: ...ions cable 34 USB communications cable 36 Solution Pac CD ROM 37 Documentations supplied depending on the UPS model 38 Mounting kit for 19 inch bays 39 2 supports for the upright position 40 FlexPDU m...

Page 14: ...y EATON 86 86710 00EN A02 Page 12 2 Installation 86 86710 00 A02 UM indd 12 14 01 2009 10 56 22 2 2 Installation in Tower Position 2 3 Installation in Rack Position It is advised to first install the...

Page 15: ...ot restricted access 86 86710 00EN A02 Page 13 2 Installation 86 86710 00 A02 UM indd 13 14 01 2009 10 56 23 2 4 Communication Ports Connection of RS232 or USB communication port optional The RS232 an...

Page 16: ...PDU 2 6 MBP MBP UPS 2 5 Connections with a FlexPDU Power Distribution Unit Module optional 2 6 Connections with a HotSwap MBP Module optional The HotSwap MBP module makes it possible to service or eve...

Page 17: ...UPS start up with the HotSwap MBP module 1 Check that the UPS is correctly connected to the HotSwap MBP module 2 Set switch 53 to the Normal position 3 Start the UPS by pressing the ON OFF button 27 o...

Page 18: ...12 86 86710...

Page 19: ...ncluded on the Solution Pac CD ROM provided by EATON Press button 27 for approximately 1 second w The buzzer beeps once and all the LEDs go ON simultaneously w The buzzer then beeps twice during the s...

Page 20: ...The devices connected to the UPS are no longer supplied w The connected devices continue to be supplied by the UPS when AC power is no longer available The necessary energy is provided by the battery...

Page 21: ...009 10 56 28 3 5 UPS EX 2 RPO Remote Power Off UPS UPS 27 ROO Remote On Off AC 27 UPS UPS 5 3 5 Using the UPS Remote Control Functions EX has the choice of two remote control options w RPO Remote Powe...

Page 22: ...16...

Page 23: ...m Enabled Disabled w Press the Scroll button 25 several times until the personalization menu is reached w Press the Enter button 26 to access the different possibilities w Finally confirm the selectio...

Page 24: ...C 1 2 1 1 50 60 Hz AC 1 AC AC 1 102 50 70 AC UPS 5 SWF UPS 0 200A AC UPS EATON 4 4 Solution PacCD ROM PC Point to Point solution Personal Solution Pac Settings Advanced Settings UPS Settings Personal...

Page 25: ...LCD BATTERY FAULT SERV REQUIRED 5 2 5 LED 21 LCD OVERLOAD ALARM REDUCE LOAD UPS 6 LED 22 LCD LOAD UNPROTECTED OUTPUT OVERLOAD UPS UPS AC UPS 7 LED 22 LCD REDUCE LOAD RESTART UPS UPS UPS Bypass UPS AC...

Page 26: ...20 MBP UPS 12 MBP 53 Bypass MBP UPS AC MBP UPS UPS MBP 2 6 13 MBP 53 Normal UPS UPS MBP UPS UPS MBP 2 6 14 AC MBP 53 Bypass UPS MBP MBP 53 Normal UPS MBP 2 6 UPS UPS 27 5 2 a b c d e f 5 86 86710...

Page 27: ...s together the two parts of the connector during remounting A Unscrew the left hand side of the front panel two screws then remove the part B Disconnect the battery block by separating the two connect...

Page 28: ...d replaced Return to normal operation 1 Check that the UPS is correctly connected to the HotSwap MBP module 2 Start the UPS by pressing the ON OFF button 27 on the UPS control panel LED 51 UPS ON OK t...

Page 29: ...V 4 50 60 Hz autoselection 0 95 2 mA Load output w Voltage w Frequency w Harmonic distortion w Overload capacity w Current 100V 50 60 Hz 0 5 6 4 for linear load 6 for nonlinear load 102 continuous 105...

Page 30: ...r to 0 to have powershare outlet provide power at the same time the as main outlets 86 86710 00EN A02 Page 28 6 Appendices 86 86710 00 A02 UM indd 28 14 01 2009 10 56 32 6 2 Programming the Programmab...

Page 31: ...pply button The section entitled Shutdown timer allows the user to define how long the powershare outlet should provide power after a power loss To configure the powershare to power off at the same ti...

Page 32: ...6 6 3 AC AC UPS UPS UPS UPS UPS FlexPDU Power Distribution Unit UPS AC 50 Hz 60 Hz 60 Hz 50 Hz MBP UPS LCD AC UPS AC UPS UPS Personal Solution Pac UPS Personal Solution Pac UPS AC UPS UPS UPS UPS UPS...

Page 33: ...www eaton com 86 86710 00 A02 86 86710 00 A02 UM indd 34 14 01 2009 10 56 53 www eaton com...

Page 34: ...w P 86 86710 00...

Page 35: ...A02 UM indd 1 14 01 2009 10 56 17 Installation and User Manual EX 2200 RT 2U 3000 RT 2U EXB RT 3U Pulsar Series www eaton com Copyright 2010 EATON All rights reserved For Technical Support Customer Ca...

Page 36: ......

Page 37: ...on 3 1 Start Up and Normal Operation 13 3 2 Operation on Battery Power 14 3 3 Return of AC Power 14 3 4 UPS Shutdown 14 3 5 Using the UPS Remote Control Functions 15 4 Access to Maintenance and Person...

Page 38: ......

Page 39: ...asbestos Packing To improve waste treatment and facilitate recycling separate the various packing components The cardboard we use comprises over 50 of recycled cardboard Sacks and bags are made of pol...

Page 40: ...ield IEC 61000 4 4 EFT IEC 61000 4 5 Surge IEEE C6241 Category B Ring wave IEC 61000 4 6 Electromagnetic field IEC 61000 4 8 Conducted magnetic field This is a Class A product based on the standard of...

Page 41: ...Important instructions that must always be followed Information advice help Visual indication Action Audible signal LED off LED on LED flashing 86 86710 00EN A02 Page 7 86 86710 00 A02 UM indd 7 14 01...

Page 42: ...4 86 86710 00...

Page 43: ...ht in pounds EX 2200 RT 2U 70 EX 3000 RT 2U 72 EX EXB RT 3U 93 Part Numbers EX 2200 RT 2U 86722 EX 3000 RT 2U 86732 EX EXB RT 3U 68405 86 86710 00EN A02 Page 9 86 86710 00 A02 UM indd 9 14 01 2009 10...

Page 44: ...outlets for connection of equipment 9 Groups of 4 outlets for connection of equipment 10 10 foot input power cord w L5 30P for EX 3000 w 5 20P for EX 2200 11 LED SWF indicating distribution system ph...

Page 45: ...o facilitate sorting 30 EX 2200 or 3000 UPS 33 RS232 communications cable 34 USB communications cable 36 Solution Pac CD ROM 37 Documentations supplied depending on the UPS model 38 Mounting kit for 1...

Page 46: ...dvised to first install the battery module then the power module above Follow steps 1 to 4 for module mounting on the rails The rails and necessary hardware are supplied by EATON 86 86710 00EN A02 Pag...

Page 47: ...ment 2 Connect the other end of the communica tion cable 33 or 34 to the USB 1 or RS232 2 communication port on the UPS The UPS can now communicate with EATON power management software It is not neces...

Page 48: ...f the FlexPDU module EX 3000 EX 3000 1 Connect the input cord 56 of the HotSwap MBP module to the AC power source 2 Connect the UPS input cord 10 to the UPS Input 55 of the HotSwap MBP module This cor...

Page 49: ...ed to the AC power source even if button 27 is not pressed Once the UPS is connected to the AC power source eight hours of charging are required before the battery can supply the rated backup time i T...

Page 50: ...12 86 86710 00 This page left blank intentionally...

Page 51: ...Solution Pac CD ROM provided by EATON Press button 27 for approximately 1 second w The buzzer beeps once and all the LEDs go ON simultaneously w The buzzer then beeps twice during the self test then b...

Page 52: ...ately 2 seconds The devices connected to the UPS are no longer supplied w The connected devices continue to be supplied by the UPS when AC power is no longer available The necessary energy is provided...

Page 53: ...a normally closed volt free contact 60 Vdc 30 Vac max 20 mA max 0 75 mm2 cable cross section between the two pins of connector 5 see diagram i RPO ROO 4 Plug connector 5 into the back of the UPS 5 Con...

Page 54: ...16 4 4 4 86 86710 00 This page left blank intentionally...

Page 55: ...o alarm Enabled Disabled w Press the Scroll button 25 several times until the personalization menu is reached w Press the Enter button 26 to access the different possibilities w Finally confirm the se...

Page 56: ...ed Transfer to the bypass AC input 1 Bypass AC power must be within tolances Bypass AC power may be outside tolerances Overload level 1 102 50 70 Alarm if threshold is overrun Function Factory Setting...

Page 57: ...UPS are fed directly by the electrical network via the By pass Check the power drawn by the connected devices and disconnect any non priority devices 7 LED 22 is ON the LCD indicates REDUCE LOAD REST...

Page 58: ...y part of a grounded battery can result in electrical shock The likelihood of such shock can be reduced if such grounds are removed during installation and maintenance applicable to equipment and remo...

Page 59: ...to firmly press together the two parts of the connector during remounting A Unscrew the left hand side of the front panel two screws then remove the part B Disconnect the battery block by separating...

Page 60: ...e UPS control panel LED 51 UPS ON OK to switch goes OFF the UPS can now be disconnected and replaced Return to normal operation 1 Check that the UPS is correctly connected to the HotSwap MBP module 2...

Page 61: ...without condensation 20 40 C 4 104 F 1000 m w Noise level 47 dBA 86 86710 00EN A02 Page 27 86 86710 00 A02 UM indd 27 14 01 2009 10 56 31 EX 2200 EX 3000 EXB 9 Output power 1890 VA 1 1480 W 2500 VA 2...

Page 62: ...power plug located in the SYS Tray 2 Click on the symbol next to UPS Settings to expand the UPS Settings section 3 Click on Startup Timer and change the The group of outlets restarts after to 0 to ha...

Page 63: ...Shutdown timer allows the user to define how long the powershare outlet should provide power after a power loss To configure the powershare to power off at the same time as the main outlets 6 Set the...

Page 64: ...ely drawn by the load to the maximum output of the UPS Personalization It is possible to modify certain UPS parameters set in the factory Certain UPS functions can also be modified by the Personal Sol...

Page 65: ...es 31 2009 10 56 32 2009 10 56 32...

Page 66: ...www eaton com 86 86710 00 A02 86 86710 00 A02 UM indd 34 14 01 2009 10 56 53 www eaton com 614 03760 01...

Reviews: