background image

11

HotSwap MBP module operation

  

UPS start-up with the HotSwap MBP module

1.  Check that the UPS is correctly connected to the HotSwap MBP module.

2.  Set switch 

(53) 

to the Normal position.

3.  Start the UPS by pressing the ON/OFF button 

(27) 

on the UPS control panel.

 

The load is supplied by the UPS.

LED 

(51)

 “UPS ON - OK to switch” on the HotSwap MBP module goes ON.

HotSwap MBP module test

1.  Set switch 

(53) 

to the Bypass position and check that the load is still supplied.

2.  Set switch 

(53)

 back to the Normal position.

2.7  UPS Connection Without a FlexPDU or HotSwap MBP Module

  

Check that the indications on the name plate located on the back of the UPS correspond to the AC power source  

  and the true electrical consumption of the total load.

 

  

Note:

 The UPS charges the battery as soon as it is connected to the AC power source, even if button 

(27)

 is not  

  pressed. Once the UPS is connected to the AC power source, eight hours of charging are required before the                                                     

  battery can supply the rated backup time

 

  The HotSwap MBP module has a rotary 

switch (53) with two positions:

 

  Normal – the load is supplied by the UPS,  

 

 

LED 

(51)

 is ON.

 

  Bypass – the load is supplied directly by  

 

 

the AC power source. LED 

(52)

 is  

 

 

ON.

  1.  Connect the input cord 

(31)

 (100V 30A / or 

20A on EX 2200) to the AC power source.

  2.  Connect the loads to the UPS. 

It is preferable to connect the priority loads  

to the four outlets marked 

(9)

 and the 

non-priority loads to the two outlets 

marked 

(8)

 that can be programmed. 

Connect any high-power devices to the 

20A (or 30A on EX 3000) outlet 

(7)

 as 

shown at left for EX 2200.

 

  To program shutdown of outlets 

(8) 

during operation on battery power and 

thus optimise the available backup time, 

the EATON communications software is 

required.

86-86710-00EN A02 - Page 15

2. Installation

86-86710-00 A02 UM.indd   15

14/01/2009   10:56:26

HotSwap MBP module operation

  

UPS start-up with the HotSwap MBP module

1.  Check that the UPS is correctly connected to the HotSwap MBP module.

2.  Set switch 

(53) 

to the Normal position.

3.  Start the UPS by pressing the ON/OFF button 

(27) 

on the UPS control panel.

 

The load is supplied by the UPS.

LED 

(51)

 “UPS ON - OK to switch” on the HotSwap MBP module goes ON.

HotSwap MBP module test

1.  Set switch 

(53) 

to the Bypass position and check that the load is still supplied.

2.  Set switch 

(53)

 back to the Normal position.

2.7  UPS Connection Without a FlexPDU or HotSwap MBP Module

  

Check that the indications on the name plate located on the back of the UPS correspond to the AC power source  

  and the true electrical consumption of the total load.

 

  

Note:

 The UPS charges the battery as soon as it is connected to the AC power source, even if button 

(27)

 is not  

  pressed. Once the UPS is connected to the AC power source, eight hours of charging are required before the                                                     

  battery can supply the rated backup time

 

  The HotSwap MBP module has a rotary 

switch (53) with two positions:

 

  Normal – the load is supplied by the UPS,  

 

 

LED 

(51)

 is ON.

 

  Bypass – the load is supplied directly by  

 

 

the AC power source. LED 

(52)

 is  

 

 

ON.

  1.  Connect the input cord 

(31)

 (100V 30A / or 

20A on EX 2200) to the AC power source.

  2.  Connect the loads to the UPS. 

It is preferable to connect the priority loads  

to the four outlets marked 

(9)

 and the 

non-priority loads to the two outlets 

marked 

(8)

 that can be programmed. 

Connect any high-power devices to the 

20A (or 30A on EX 3000) outlet 

(7)

 as 

shown at left for EX 2200.

 

  To program shutdown of outlets 

(8) 

during operation on battery power and 

thus optimise the available backup time, 

the EATON communications software is 

required.

86-86710-00EN A02 - Page 15

2. Installation

86-86710-00 A02 UM.indd   15

14/01/2009   10:56:26

2. 

インストレーション

ホットスワップ

MBP

モジュールにはスイッチ

(53)

があり、切り替えが出来ます。

Normal 

負荷は

UPS

から給電されます。

LED

ンプ

(51)

が点灯します。

ByPass 

負荷は

AC

電源から直接給電されま

す。

 LED

ランプ

(52)

 

が点灯します。

ホットスワップ

MBP

モジュールによる

UPS

起動

1.  UPS

が正確・確実にホットスワップ

MBP

モジュールに接続されていることを確認してください。

2.  

スイッチ

(53)

を「

Normal

」位置に合わせてください。

3.  UPS

操作パネルの主電源スイッチ

(27)

 

をオンにして

UPS

を起動します。

UPS

から電源が供給されます。

LED

(51)

UPS ON - OK to switch

」が点灯すれば、ホットスワップ

MBP

モジュールが動作しています。

ホットスワップ

MBP

モジュールの試験

1.  

スイッチ

(53)

Bypass

位置に設し、給電されていることを確認してください。

2.  

スイッチ

(53)

Normal

位置に戻してください。

2.7

 

FlexPDU

またはホットスワップ

MBP

モジュールがない時の

UPS

接続

1. 

入力ケーブル

(31)

100

30

A、

EX 2200

20A

)を

AC

電源に接続します。

2. 

負荷を

UPS

に接続します。

出力コンセント

4

(9)

は、優先負荷コンセン

トです。
出力コンセント

2

(8)

(プログラマブル)

は、非優先負荷コンセントです。
プログラムコントロールを使用しない場合
は、優先負荷コンセントのご使用をお勧めい
たします。
左図のように、大容量機器をコンセント

(7) 

EX 3000

30A

EX 2200

20A

)に接続し

ます。

(8)

のプログラマブルコンセントは、プログラ

ムの組み方によっては、バックアップ運転時
に誤動作を起こす場合がありますので、プロ
グラムソフトを最適化してご使用ください。

必ず

UPS

背面表示されている定格値と

AC

電源および全負荷の実際消費量が充分余裕があるかを確認してください。

ホットスワップ

MBP

モジュールの運転

ご注意:主電源スイッチ

(27)

を押さなくても、

UPS

AC

電源に接続すると、バッテリが充電されます。

 

定格のバックアップ

時間を満たすには

 8 

時間の充電が必要とされます。

Summary of Contents for EX Pulsar Series

Page 1: ...ion and User Manual English EX 2200 RT 2U 3000 RT 2U EXB RT 3U Pulsar Series 86 86710 00 A02 UM indd 1 14 01 2009 10 56 17 Installation and User Manual EX 2200 RT 2U 3000 RT 2U EXB RT 3U Pulsar Series...

Page 2: ...w P 86 86710 00...

Page 3: ...nglish EX 2200 RT 2U 3000 RT 2U EXB RT 3U Pulsar Series 86 86710 00 A02 UM indd 1 14 01 2009 10 56 17 EX 2200 RT 2U 3000 RT 2U EXB RT 3U Pulsar Series www eaton com 2010 EATON Email JapanSales Eaton c...

Page 4: ......

Page 5: ...2 6 1 3 6 2 2 1 7 2 2 8 2 3 8 2 4 9 2 5 FlexPDU 10 2 6 MBP 10 2 7 FlexPDU MBP UPS 11 3 3 1 13 3 2 14 3 3 AC 14 3 4 UPS 14 3 5 UPS 15 4 4 1 17 4 2 17 4 3 17 4 4 18 5 5 1 19 5 2 20 5 3 MBP UPS 22 6 6 1...

Page 6: ......

Page 7: ...1 EATON EX VCCI A III IV UPS EATON EX www eaton com EATON UPS EATON CFC HCFC 50 PS PET 01 HDPE 02 PVC 03 LDPE 04 PP 05 PS 06 www eaton com 01 PET 01 PET...

Page 8: ...A VCCI 2008 04 Class A EN 62040 2 IEC 62040 2 IEC 61000 4 2 ESD IEC 61000 4 3 Radiated eld IEC 61000 4 4 EFT IEC 61000 4 5 Surge IEEE C6241 Category B Ring wave IEC 61000 4 6 Electromagnetic eld IEC...

Page 9: ...3 LED LED LED CFC HCFC UPS EATON EATON UPS EATON UPS...

Page 10: ...4...

Page 11: ...56 20 1 Presentation 1 1 Standard Positions Tower Position Rack Position Dimensions H x W x D in inches EX 2200 RT 2U 17 3 x 3 38 x 25 2 EX 3000 RT 2U 17 3 x 3 38 x 25 2 EX EXB RT 3U 17 3 x 5 16 x 19...

Page 12: ...onnection of equipment 10 10 foot input power cord w L5 30P for EX 3000 w 5 20P for EX 2200 11 LED SWF indicating distribution system phase neutral reversal 12 Connectors for battery modules to the UP...

Page 13: ...ions cable 34 USB communications cable 36 Solution Pac CD ROM 37 Documentations supplied depending on the UPS model 38 Mounting kit for 19 inch bays 39 2 supports for the upright position 40 FlexPDU m...

Page 14: ...y EATON 86 86710 00EN A02 Page 12 2 Installation 86 86710 00 A02 UM indd 12 14 01 2009 10 56 22 2 2 Installation in Tower Position 2 3 Installation in Rack Position It is advised to first install the...

Page 15: ...ot restricted access 86 86710 00EN A02 Page 13 2 Installation 86 86710 00 A02 UM indd 13 14 01 2009 10 56 23 2 4 Communication Ports Connection of RS232 or USB communication port optional The RS232 an...

Page 16: ...PDU 2 6 MBP MBP UPS 2 5 Connections with a FlexPDU Power Distribution Unit Module optional 2 6 Connections with a HotSwap MBP Module optional The HotSwap MBP module makes it possible to service or eve...

Page 17: ...UPS start up with the HotSwap MBP module 1 Check that the UPS is correctly connected to the HotSwap MBP module 2 Set switch 53 to the Normal position 3 Start the UPS by pressing the ON OFF button 27 o...

Page 18: ...12 86 86710...

Page 19: ...ncluded on the Solution Pac CD ROM provided by EATON Press button 27 for approximately 1 second w The buzzer beeps once and all the LEDs go ON simultaneously w The buzzer then beeps twice during the s...

Page 20: ...The devices connected to the UPS are no longer supplied w The connected devices continue to be supplied by the UPS when AC power is no longer available The necessary energy is provided by the battery...

Page 21: ...009 10 56 28 3 5 UPS EX 2 RPO Remote Power Off UPS UPS 27 ROO Remote On Off AC 27 UPS UPS 5 3 5 Using the UPS Remote Control Functions EX has the choice of two remote control options w RPO Remote Powe...

Page 22: ...16...

Page 23: ...m Enabled Disabled w Press the Scroll button 25 several times until the personalization menu is reached w Press the Enter button 26 to access the different possibilities w Finally confirm the selectio...

Page 24: ...C 1 2 1 1 50 60 Hz AC 1 AC AC 1 102 50 70 AC UPS 5 SWF UPS 0 200A AC UPS EATON 4 4 Solution PacCD ROM PC Point to Point solution Personal Solution Pac Settings Advanced Settings UPS Settings Personal...

Page 25: ...LCD BATTERY FAULT SERV REQUIRED 5 2 5 LED 21 LCD OVERLOAD ALARM REDUCE LOAD UPS 6 LED 22 LCD LOAD UNPROTECTED OUTPUT OVERLOAD UPS UPS AC UPS 7 LED 22 LCD REDUCE LOAD RESTART UPS UPS UPS Bypass UPS AC...

Page 26: ...20 MBP UPS 12 MBP 53 Bypass MBP UPS AC MBP UPS UPS MBP 2 6 13 MBP 53 Normal UPS UPS MBP UPS UPS MBP 2 6 14 AC MBP 53 Bypass UPS MBP MBP 53 Normal UPS MBP 2 6 UPS UPS 27 5 2 a b c d e f 5 86 86710...

Page 27: ...s together the two parts of the connector during remounting A Unscrew the left hand side of the front panel two screws then remove the part B Disconnect the battery block by separating the two connect...

Page 28: ...d replaced Return to normal operation 1 Check that the UPS is correctly connected to the HotSwap MBP module 2 Start the UPS by pressing the ON OFF button 27 on the UPS control panel LED 51 UPS ON OK t...

Page 29: ...V 4 50 60 Hz autoselection 0 95 2 mA Load output w Voltage w Frequency w Harmonic distortion w Overload capacity w Current 100V 50 60 Hz 0 5 6 4 for linear load 6 for nonlinear load 102 continuous 105...

Page 30: ...r to 0 to have powershare outlet provide power at the same time the as main outlets 86 86710 00EN A02 Page 28 6 Appendices 86 86710 00 A02 UM indd 28 14 01 2009 10 56 32 6 2 Programming the Programmab...

Page 31: ...pply button The section entitled Shutdown timer allows the user to define how long the powershare outlet should provide power after a power loss To configure the powershare to power off at the same ti...

Page 32: ...6 6 3 AC AC UPS UPS UPS UPS UPS FlexPDU Power Distribution Unit UPS AC 50 Hz 60 Hz 60 Hz 50 Hz MBP UPS LCD AC UPS AC UPS UPS Personal Solution Pac UPS Personal Solution Pac UPS AC UPS UPS UPS UPS UPS...

Page 33: ...www eaton com 86 86710 00 A02 86 86710 00 A02 UM indd 34 14 01 2009 10 56 53 www eaton com...

Page 34: ...w P 86 86710 00...

Page 35: ...A02 UM indd 1 14 01 2009 10 56 17 Installation and User Manual EX 2200 RT 2U 3000 RT 2U EXB RT 3U Pulsar Series www eaton com Copyright 2010 EATON All rights reserved For Technical Support Customer Ca...

Page 36: ......

Page 37: ...on 3 1 Start Up and Normal Operation 13 3 2 Operation on Battery Power 14 3 3 Return of AC Power 14 3 4 UPS Shutdown 14 3 5 Using the UPS Remote Control Functions 15 4 Access to Maintenance and Person...

Page 38: ......

Page 39: ...asbestos Packing To improve waste treatment and facilitate recycling separate the various packing components The cardboard we use comprises over 50 of recycled cardboard Sacks and bags are made of pol...

Page 40: ...ield IEC 61000 4 4 EFT IEC 61000 4 5 Surge IEEE C6241 Category B Ring wave IEC 61000 4 6 Electromagnetic field IEC 61000 4 8 Conducted magnetic field This is a Class A product based on the standard of...

Page 41: ...Important instructions that must always be followed Information advice help Visual indication Action Audible signal LED off LED on LED flashing 86 86710 00EN A02 Page 7 86 86710 00 A02 UM indd 7 14 01...

Page 42: ...4 86 86710 00...

Page 43: ...ht in pounds EX 2200 RT 2U 70 EX 3000 RT 2U 72 EX EXB RT 3U 93 Part Numbers EX 2200 RT 2U 86722 EX 3000 RT 2U 86732 EX EXB RT 3U 68405 86 86710 00EN A02 Page 9 86 86710 00 A02 UM indd 9 14 01 2009 10...

Page 44: ...outlets for connection of equipment 9 Groups of 4 outlets for connection of equipment 10 10 foot input power cord w L5 30P for EX 3000 w 5 20P for EX 2200 11 LED SWF indicating distribution system ph...

Page 45: ...o facilitate sorting 30 EX 2200 or 3000 UPS 33 RS232 communications cable 34 USB communications cable 36 Solution Pac CD ROM 37 Documentations supplied depending on the UPS model 38 Mounting kit for 1...

Page 46: ...dvised to first install the battery module then the power module above Follow steps 1 to 4 for module mounting on the rails The rails and necessary hardware are supplied by EATON 86 86710 00EN A02 Pag...

Page 47: ...ment 2 Connect the other end of the communica tion cable 33 or 34 to the USB 1 or RS232 2 communication port on the UPS The UPS can now communicate with EATON power management software It is not neces...

Page 48: ...f the FlexPDU module EX 3000 EX 3000 1 Connect the input cord 56 of the HotSwap MBP module to the AC power source 2 Connect the UPS input cord 10 to the UPS Input 55 of the HotSwap MBP module This cor...

Page 49: ...ed to the AC power source even if button 27 is not pressed Once the UPS is connected to the AC power source eight hours of charging are required before the battery can supply the rated backup time i T...

Page 50: ...12 86 86710 00 This page left blank intentionally...

Page 51: ...Solution Pac CD ROM provided by EATON Press button 27 for approximately 1 second w The buzzer beeps once and all the LEDs go ON simultaneously w The buzzer then beeps twice during the self test then b...

Page 52: ...ately 2 seconds The devices connected to the UPS are no longer supplied w The connected devices continue to be supplied by the UPS when AC power is no longer available The necessary energy is provided...

Page 53: ...a normally closed volt free contact 60 Vdc 30 Vac max 20 mA max 0 75 mm2 cable cross section between the two pins of connector 5 see diagram i RPO ROO 4 Plug connector 5 into the back of the UPS 5 Con...

Page 54: ...16 4 4 4 86 86710 00 This page left blank intentionally...

Page 55: ...o alarm Enabled Disabled w Press the Scroll button 25 several times until the personalization menu is reached w Press the Enter button 26 to access the different possibilities w Finally confirm the se...

Page 56: ...ed Transfer to the bypass AC input 1 Bypass AC power must be within tolances Bypass AC power may be outside tolerances Overload level 1 102 50 70 Alarm if threshold is overrun Function Factory Setting...

Page 57: ...UPS are fed directly by the electrical network via the By pass Check the power drawn by the connected devices and disconnect any non priority devices 7 LED 22 is ON the LCD indicates REDUCE LOAD REST...

Page 58: ...y part of a grounded battery can result in electrical shock The likelihood of such shock can be reduced if such grounds are removed during installation and maintenance applicable to equipment and remo...

Page 59: ...to firmly press together the two parts of the connector during remounting A Unscrew the left hand side of the front panel two screws then remove the part B Disconnect the battery block by separating...

Page 60: ...e UPS control panel LED 51 UPS ON OK to switch goes OFF the UPS can now be disconnected and replaced Return to normal operation 1 Check that the UPS is correctly connected to the HotSwap MBP module 2...

Page 61: ...without condensation 20 40 C 4 104 F 1000 m w Noise level 47 dBA 86 86710 00EN A02 Page 27 86 86710 00 A02 UM indd 27 14 01 2009 10 56 31 EX 2200 EX 3000 EXB 9 Output power 1890 VA 1 1480 W 2500 VA 2...

Page 62: ...power plug located in the SYS Tray 2 Click on the symbol next to UPS Settings to expand the UPS Settings section 3 Click on Startup Timer and change the The group of outlets restarts after to 0 to ha...

Page 63: ...Shutdown timer allows the user to define how long the powershare outlet should provide power after a power loss To configure the powershare to power off at the same time as the main outlets 6 Set the...

Page 64: ...ely drawn by the load to the maximum output of the UPS Personalization It is possible to modify certain UPS parameters set in the factory Certain UPS functions can also be modified by the Personal Sol...

Page 65: ...es 31 2009 10 56 32 2009 10 56 32...

Page 66: ...www eaton com 86 86710 00 A02 86 86710 00 A02 UM indd 34 14 01 2009 10 56 53 www eaton com 614 03760 01...

Reviews: