7
Instruction Booklet
IB0162063EN
Effective January 2014
O & M Manual for the EGS Metered, Service
Entrance Automatic Transfer Switch with Relay Control
Eaton Corporation www.eatoncanada.ca
Figure 6. Location of wireway retaining tabs.
Figure 7. Removing the wireway.
4.4 Utility Power Cable Connection
Warning
POWEr COnDUCTOrS MaY HaVE VOLTagE PrESEnT THaT Can CaUSE
SEVErE PErSOnaL inJUrY Or DEaTH. DE-EnErgiZE aLL POWEr
Or COnTrOL CirCUiT COnDUCTOrS TO BE COnnECTED TO THE aTS
EQUiPMEnT BEFOrE BEginning TO WOrK WiTH THE COnDUCTOrS
anD/Or TErMinaTing THEM TO THE EQUiPMEnT
CaUTiOn
TO HELP PrEVEnT COMPOnEnT DaMagE Or FUTUrE MaLFUnCTiOnS,
USE EXTrEME CarE TO KEEP COnTaMinanTS OUT OF THE aTS
EQUiPMEnT WHEn MaKing THE POWEr CaBLE COnnECTiOnS.
Test all power cables prior to connection to the unit to ensure that
the conductors or cable insulation has not been damaged while
being pulled into position.
Power cables are to be connected to solderless, screw type lugs
located on the meter socket jaw assembly. Verify that the lugs sup-
plied will accommodate the power cables being used. Also verify
that the cables comply with all local electrical codes. Standard ATS
equipment, as supplied from the factory, will accommodate the wire
sizes shown in Table 2.
Table 2. Wire Sizes for ATSs.
Transfer Switch
amp rating
Meter Socket Lug
Size range
number of Cables
per Phase
100
#6 AWG - 250 MCM
1
200
#6 AWG - 250 MCM
1
Carefully strip the insulation from the power cables to avoid nicking
or ringing of the conductor strands. Prepare the stripped conductor
termination end by cleaning it with a wire brush. If aluminum con-
ductors are used, apply an appropriate joint compound to the clean
conductor surface area.
CaUTiOn
iMPrOPEr POWEr CaBLE COnnECTiOnS Can CaUSE EXCESSiVE HEaT
anD SUBSEQUEnT EQUiPMEnT FaiLUrE.
ote:
n
Tighten the cable lugs to the torque identified on the label affixed to
the unit’s door.
Connect cables as follows (see Figure 9, and Table 2):
•
The utility power cables to the utility lugs on the meter socket
jaw assembly;
•
The utility neutral cable to the utility neutral lug on the meter
socket jaw assembly.
Figure 8. Power and Neutral Utility Cable Connection Locations.
Removal
directions
Sealing
Tab
Utility
Line Lugs
Utility
Neutral