Figure 6. Location of wireway retaining tabs. 

Figure 7. Removing the wireway.

4.4 Utility Power Cable Connection

Warning

POWEr COnDUCTOrS MaY HaVE VOLTagE PrESEnT THaT Can CaUSE 

SEVErE PErSOnaL inJUrY Or DEaTH.  DE-EnErgiZE aLL POWEr 

Or COnTrOL CirCUiT COnDUCTOrS TO BE COnnECTED TO THE aTS 

EQUiPMEnT BEFOrE BEginning TO WOrK WiTH THE COnDUCTOrS 

anD/Or TErMinaTing THEM TO THE EQUiPMEnT

CaUTiOn

TO HELP PrEVEnT COMPOnEnT DaMagE Or FUTUrE MaLFUnCTiOnS, 

USE EXTrEME CarE TO KEEP COnTaMinanTS OUT OF THE aTS 

EQUiPMEnT WHEn MaKing THE POWEr CaBLE COnnECTiOnS.

Test all power cables prior to connection to the unit to ensure that 

the conductors or cable insulation has not been damaged while 

being pulled into position.
Power cables are to be connected to solderless, screw type lugs 

located on the meter socket jaw assembly.  Verify that the lugs sup-

plied will accommodate the power cables being used.  Also verify 

that the cables comply with all local electrical codes.  Standard ATS 

equipment, as supplied from the factory, will accommodate the wire 

sizes shown in Table 2.

Table 2.  Wire Sizes for ATSs.

Transfer Switch 

amp rating

Meter Socket Lug 

Size range

number of Cables 

per Phase

100

#6 AWG - 250 MCM

1

200

#6 AWG - 250 MCM 

1

Carefully strip the insulation from the power cables to avoid nicking 

or ringing of the conductor strands.  Prepare the stripped conductor 

termination end by cleaning it with a wire brush.  If aluminum con-

ductors are used, apply an appropriate joint compound to the clean 

conductor surface area.

CaUTiOn

iMPrOPEr POWEr CaBLE COnnECTiOnS Can CaUSE EXCESSiVE HEaT 

anD SUBSEQUEnT EQUiPMEnT FaiLUrE.

ote:

n

Tighten the cable lugs to the torque identified on the label affixed to 

the unit’s door.

Connect cables as follows (see Figure 9, and Table 2):

• 

The utility power cables to the utility lugs on the meter socket 

jaw assembly;

• 

The utility neutral cable to the utility neutral lug on the meter 

socket jaw assembly.

Figure 8. Power and Neutral Utility Cable Connection Locations.

Removal 

directions

Sealing 

Tab

Utility 

Line Lugs

Utility 

Neutral

Summary of Contents for EGS Series

Page 1: ...uipment Description 5 4 Installation and Wiring 8 5 Functional Testing 12 6 Adjustments 13 7 Maintenance and Component Replacement 14 Effective January 2014 Instruction Booklet IB0162063EN O M Manual...

Page 2: ...e proceeding If fur ther information is required by the purchaser regarding a particular installation application or maintenance activity please contact an authorized Eaton sales representative or the...

Page 3: ...ear Conversely if connected to the generator power source and the generator power source fails while the utility power source is still unavailable the ATS remains connected to the generator power sour...

Page 4: ...e when it is within its undervoltage setpoint ranges for the nominal voltage setting Connected Connected is defined as when the input is shorted by an external contact or connection Failed or Fails A...

Page 5: ...site and ready to be installed the packaging material can be removed Refer to Section 4 of this manual for specific installation instructions 2 3 Storage Although well packaged this equipment is not s...

Page 6: ...configuration or an under ground one Twin 2 hub openings on the top of the enclosure will accept a standard Myers type hub The assembly ships with removable hub closure plates installed over these ope...

Page 7: ...e lugs sup plied will accommodate the power cables being used Also verify that the cables comply with all local electrical codes Standard ATS equipment as supplied from the factory will accommodate th...

Page 8: ...range number of Cables per Phase 100 14 1 0 AWG 1 200 4 AWG 300 MCM 1 CaUTiOn iMPrOPEr POWEr CaBLE COnnECTiOnS Can CaUSE EXCESSiVE HEaT anD SUBSEQUEnT EQUiPMEnT FaiLUrE ote N Tighten the cable lugs to...

Page 9: ...ector switch to the OFF position to prevent an unwanted generator start Control wiring such as the generator transfer wires and utility sensing must be run in a separate conduit from the power cables...

Page 10: ...ontactor will automatically switch to the UTILITY position WARNING CONTACT WITH ENERGIZED COMPONENTS WILL CAUSE ELECTRICAL SHOCK CAPABLE OF PRODUCING SEVERE PERSONAL INJURY OR DEATH USE EXTREME CAUTIO...

Page 11: ...DEVICE FAILURE TO FOLLOW THIS PROCEDURE COULD CAUSE SEVERE PERSONAL INJURY AND OR DEATH ALWAYS TURN THE utility POWER OFF AND TURN THE generator IF A GENERATOR CONTROL SELECTOR SWITCH TO THE oFF POSI...

Page 12: ...inspection and or maintenance Disconnect the line power from the equipment being serviced by opening next highest disconnect device Make certain that any accessory control power is switched off b Ins...

Page 13: ...IB0162063EN Effective January 2014 O MManualfortheEGSMetered Service EntranceAutomaticTransferSwitchwithRelayControl Eaton Corporation www eatoncanada ca Figure 15 Wiring Diagram for the EGSC ATS Show...

Page 14: ...B0162063EN Effective January 2014 O MManualfortheEGSMetered Service EntranceAutomaticTransferSwitchwithRelayControl Eaton Corporation www eatoncanada ca 7 3 Maintenance Log Date Action Example 01 01 1...

Page 15: ...DEATH ALWAYS TURN THE UTILITY SOURCE 1 POWER OFF AND TURN THE GENERATOR SOURCE 2 CONTROL SELECTOR SWITCH TO THE OFF POSITION BEFORE ATTEMPTING TO REPLACE ANY COMPONENTS NOTICE Apply utility source 1 p...

Page 16: ...thRelayControl Eaton Corporation www eatoncanada ca Figure 16 Dimensions and Plan View of a Service Entrance EGS in 200A 2 2 Hub Openings 5 90 150mm 5 90 150mm 7 81 198mm 36 19 919mm 29 47 749mm 4 69...

Page 17: ...17 Instruction Booklet IB0162063EN Effective January 2014 O MManualfortheEGSMetered Service EntranceAutomaticTransferSwitchwithRelayControl Eaton Corporation www eatoncanada ca Notes...

Page 18: ...ractual agreement between the parties This literature is not intended to and does not enlarge or add to any such contract The sole source governing the rights and remedies of any purchaser of this equ...

Reviews: