background image

10

Instruction Booklet  

IB0162063EN

Effective January 2014

O & M Manual for the EGS Metered, Service

Entrance Automatic Transfer Switch with Relay Control

Eaton Corporation www.eatoncanada.ca

4.9 Protection

For Catalogue #EgSC100aMSE and EgSC200aMSE

This switch is equipped with integral over-current protection. 

Continuous load current not to exceed 80 percent of switch rating.
This Transfer Switch is rated for use on a circuit capable of deliver-

ing not more than 10,000 rms symmetrical amperes, 240 volts maxi-
mum.

Section 5: Functional Testing

Warning

YOU arE rEaDY TO EnErgiZE THE EQUiPMEnT.  VOLTagES WiTHin THE 

EnCLOSUrE arE CaPaBLE OF CaUSing SEVErE PErSOnaL inJUrY Or 

DEaTH.  USE EXTrEME CaUTiOn TO aVOiD COnTaCT WiTH EnErgiZED 

EQUiPMEnT.

5.1 Preliminary Checks

S

tep 1:   Check all loads connected to the ATS to ensure that they are ready 

to be energized.

5.2 Energize the Switch

Step 1:  With the service entrance barrier removed use a voltmeter to mea-

sure the line-to-line and the line-to-neutral voltages on the line 

side of the circuit breaker. Confirm the utility voltage is correct then 

replace the service entrance barrier.

Step 2:  Ensure the generator control selector switch located on the standby 

generator is set to the OFF position. If so equiped, remove the control 

fuse from the generator control panel to ensure the generator does 

not iniate a start during this phase of the preliminary check. Open 

the generator power source circuit breaker located on the generator 

assembly. 

Step 3:  Close the service entrance disconnect circuit breaker in the switch to 

connect the ATS to the utility power source voltage. If the ATS unit 

is not already in the UTILITY position, and the voltage is acceptable, 

the solenoid will engage and the contactor will automatically switch 

to the UTILITY position.

Warning

COnTaCT WiTH EnErgiZED COMPOnEnTS WiLL CaUSE ELECTriCaL 

SHOCK CaPaBLE OF PrODUCing SEVErE PErSOnaL inJUrY Or 

DEaTH.  USE EXTrEME CaUTiOn TO aVOiD COnTaCT WiTH EnErgiZED 

COMPOnEnTS WHEn USing a METEr FOr VOLTagE CHECKS.

Step 4: Replace the control fuse in the generator control panel removed in 

Step 2 of Section 5.2. Position the generator control selector switch, 

located on the standby generator, to the AUTOSTART position.  (It 

may also be labeled REMOTE START or AUTO.). Close the generator 

power source circuit breaker opened in Step 2 of Section 5.2.

5.3 Operational Checks

Step 1: Open the service entrance disconnect circuit breaker originally closed in 

Step 3 of Section 5.2.

 nOTiCE

THiS WiLL SiMULaTE an inTErrUPTiOn OF THE UTiLiTY POWEr SOUrCE.

Step 2: After a time delay (based on the generator settings), the standby gen-

erator engine will start.

Step 3: Using a voltmeter, measure the line-to-line and line-to-neutral voltages 

across the generator line terminals to ensure that the generator 

emergency voltage is correct.  If necessary, make adjustments to the 

voltage regulator on the generator according to the manufacturer’s 

recommendations to correct any voltage deviations.  The ATS will 

only respond to the correct voltage from the generator power source.

Step 4: The ATS Time Delay Normal (Utility) to Emergency (Generator) (TDNE) 

will begin to time after the generator engine begins to run.  After 

time out, the solenoid will engage and the contactor will automati-

cally switch from the UTILITY to the GENERATOR position.

Step 5: Close the service entrance disconnect circuit breaker described in Step 

3 of Section 5.2.

Step 7: The ATS Time Delay Emergency (Generator) to Normal (Utility) (TDEN) 

timer will begin timing, and the solenoid will engage and automati-

cally switch from the GENERATOR to the UTILITY position and the 

generator will shut down after a cool down period.

Summary of Contents for EGS Series

Page 1: ...uipment Description 5 4 Installation and Wiring 8 5 Functional Testing 12 6 Adjustments 13 7 Maintenance and Component Replacement 14 Effective January 2014 Instruction Booklet IB0162063EN O M Manual...

Page 2: ...e proceeding If fur ther information is required by the purchaser regarding a particular installation application or maintenance activity please contact an authorized Eaton sales representative or the...

Page 3: ...ear Conversely if connected to the generator power source and the generator power source fails while the utility power source is still unavailable the ATS remains connected to the generator power sour...

Page 4: ...e when it is within its undervoltage setpoint ranges for the nominal voltage setting Connected Connected is defined as when the input is shorted by an external contact or connection Failed or Fails A...

Page 5: ...site and ready to be installed the packaging material can be removed Refer to Section 4 of this manual for specific installation instructions 2 3 Storage Although well packaged this equipment is not s...

Page 6: ...configuration or an under ground one Twin 2 hub openings on the top of the enclosure will accept a standard Myers type hub The assembly ships with removable hub closure plates installed over these ope...

Page 7: ...e lugs sup plied will accommodate the power cables being used Also verify that the cables comply with all local electrical codes Standard ATS equipment as supplied from the factory will accommodate th...

Page 8: ...range number of Cables per Phase 100 14 1 0 AWG 1 200 4 AWG 300 MCM 1 CaUTiOn iMPrOPEr POWEr CaBLE COnnECTiOnS Can CaUSE EXCESSiVE HEaT anD SUBSEQUEnT EQUiPMEnT FaiLUrE ote N Tighten the cable lugs to...

Page 9: ...ector switch to the OFF position to prevent an unwanted generator start Control wiring such as the generator transfer wires and utility sensing must be run in a separate conduit from the power cables...

Page 10: ...ontactor will automatically switch to the UTILITY position WARNING CONTACT WITH ENERGIZED COMPONENTS WILL CAUSE ELECTRICAL SHOCK CAPABLE OF PRODUCING SEVERE PERSONAL INJURY OR DEATH USE EXTREME CAUTIO...

Page 11: ...DEVICE FAILURE TO FOLLOW THIS PROCEDURE COULD CAUSE SEVERE PERSONAL INJURY AND OR DEATH ALWAYS TURN THE utility POWER OFF AND TURN THE generator IF A GENERATOR CONTROL SELECTOR SWITCH TO THE oFF POSI...

Page 12: ...inspection and or maintenance Disconnect the line power from the equipment being serviced by opening next highest disconnect device Make certain that any accessory control power is switched off b Ins...

Page 13: ...IB0162063EN Effective January 2014 O MManualfortheEGSMetered Service EntranceAutomaticTransferSwitchwithRelayControl Eaton Corporation www eatoncanada ca Figure 15 Wiring Diagram for the EGSC ATS Show...

Page 14: ...B0162063EN Effective January 2014 O MManualfortheEGSMetered Service EntranceAutomaticTransferSwitchwithRelayControl Eaton Corporation www eatoncanada ca 7 3 Maintenance Log Date Action Example 01 01 1...

Page 15: ...DEATH ALWAYS TURN THE UTILITY SOURCE 1 POWER OFF AND TURN THE GENERATOR SOURCE 2 CONTROL SELECTOR SWITCH TO THE OFF POSITION BEFORE ATTEMPTING TO REPLACE ANY COMPONENTS NOTICE Apply utility source 1 p...

Page 16: ...thRelayControl Eaton Corporation www eatoncanada ca Figure 16 Dimensions and Plan View of a Service Entrance EGS in 200A 2 2 Hub Openings 5 90 150mm 5 90 150mm 7 81 198mm 36 19 919mm 29 47 749mm 4 69...

Page 17: ...17 Instruction Booklet IB0162063EN Effective January 2014 O MManualfortheEGSMetered Service EntranceAutomaticTransferSwitchwithRelayControl Eaton Corporation www eatoncanada ca Notes...

Page 18: ...ractual agreement between the parties This literature is not intended to and does not enlarge or add to any such contract The sole source governing the rights and remedies of any purchaser of this equ...

Reviews: