2

DPF = decimal point factor. From the table below, select the DPF that matches the

display decimal point location:

Displayed Decimal Point  D P F

 XXXXX 

1

 XXXX.X 

10

 XXX.XX 

100

 XX.XXX 

1000

 X.XXXX 

10000

And PPI = pulses per item, the number of pulses the unit receives from the sensor

per physical unit (revolution, foot, gallon, etc.) on the rate display.

To display process time:

Scaler = 

PPI x DPF 

NOS

,

where NOS = number of seconds in the process time unit (1 = seconds, 60 = min-

utes, 3600 = hours, etc.).

DPF = decimal point factor, and is selected from the table above.

PPI = pulses per item, the number of pulses the unit receives from the sensor per

process cycle (oven length, mold machine cycle, etc.).

An inherent ability of devices that use the Tau method of calculation is that they can

calculate  rate  or  process  time  and  update  the  display  each  time  an  input  pulse  is

received. There is a practical limit to how fast the display should update, however,

especially when the process speed is changing and when there may be minor varia-

tions in pulse input frequency at a “steady” speed. The Eclipse has a programmable

display  update  time  that  sets  the  minimum  time  between  updates.  Each  time  the

display updates, the unit waits until the update timer times out and then updates the

display  when  the  next  pulse  comes  in.  The  Eclipse  counts  the  number  of  pulses

received  and  times  the  total  periods  for  all  pulses  received  for  each  update.  The

calculation averages Tau for all periods in the update effectively “smoothing” out the

display. The installer programs an update time in the range of  0.1 to 99.9 seconds to

obtain a display that is smooth, yet responsive.

Sooner  or  later,  the  process  being  monitored  will  be  brought  to  a  halt.  Pulses  will

stop coming in from the sensor. What happens once the update timer has timed out

and the Eclipse is patiently waiting for the next pulse to come in so that it can update

the display, but the next pulse is not coming? Like the bride who has been stood up

at the altar, something must tell the Eclipse that it is waiting in vain and it is time to

get on with its life. The Eclipse is equipped with a zero timer for this purpose. The

zero  timer  sets  the  unit’s  patience  between  pulses. The  installer  programs  a  zero

DESCRIPTION cont.

Summary of Contents for Durant Eclipse Series

Page 1: ...umber 57700 970 04 Durant Eclipse Series Ratemeter Process Timers Models 5770X 47X Table of Contents 1 Introduction 1 Description 5 Mounting 6 Wiring 11 Programming 16 Diagnostics 19 Specifications Vi...

Page 2: ...t per minute barrels per hour etc or in units of time such as baking time or mold ma chine cycle time In either case the Eclipse employes the fiendishly clever Tau method of calculation which means th...

Page 3: ...e input frequency at a steady speed The Eclipse has a programmable display update time that sets the minimum time between updates Each time the display updates the unit waits until the update timer ti...

Page 4: ...a programmable value that is common to both setpoints and both relays This means that a relay turns OFF when the display is less than or equal to the high setpoint minus the hysteresis value or when t...

Page 5: ...al serial communication board allows a host device to download and read programming parameters and to read status information from the rate meter such as display value relay status etc This manual doe...

Page 6: ...body until adhesive surface makes contact with the front bezel 2 Slide unit into cutout in panel 3 Attach mounting clips and screws 4 Tighten screws until unit is firmly in place DO NOT OVERTIGHTEN sc...

Page 7: ...ree additional circuit boards with headers may be installed These option boards are relay output RS 485 serial communications and analog retransmission The option boards occupy spe cific locations in...

Page 8: ...onnecting device for the equipment Switches and circuit breakers in Europe must comply with IEC 947 Terminal Connector Ratings AC or DC Power Input Relay Output 10A 250VAC Wire size 12 24AWG 3 1mm2 0...

Page 9: ...ernal Fuse 1 External Fuse Size U S European 2 AMP 50 V Time Delay T2A 50 V Time Delay 12 VA AC Power Input for AC powered models 57701 47X No Internal Fuse 1 Power In L1 85 265 VAC L2 47 63 Hz 20 VA...

Page 10: ...Max Mag Pickup Source PNP 10 kHz Max Single Ended 12 VDC Out 75 mA Max See Specifications pages 17 18 for input impedances and threshholds Relay Output Option Board Typical Wiring Durant 1 Terminal De...

Page 11: ...on Option Board Durant 1 485 485 Common To Host Serial Port Analog Output Option Board Durant 4 20mA 1 0 10 V Common 4 20mA 0 10 V Output Ratings 4 20 mA into 750 W Ohms maximum 0 10 V into 2500 W Ohm...

Page 12: ...to its minimum values 0V and 4 mA regardless of the input signal To enter the program mode 1 Connect Program Enable input terminal to Ground Durant Jumper Terminals 1 and 2 1 2 3 4 2 Press and hold t...

Page 13: ...1 The parameter name is displayed by pressing and holding the program key PGM 2 The value of the parameter is displayed by releasing the program key 3 While holding the program key PGM the unit scrol...

Page 14: ...lowing list shows all programming parameter names the default value for each and the selection range for each A programmed unit may be restored to de fault settings by pressing both the program PGM an...

Page 15: ...scaler here The de cimal point location on this screen was selected in the scaler decimal point parameter above Range 0 001 to 9999 Display update time Sets the minimum time in seconds between displa...

Page 16: ...log output 10V and 20 mA Range 0 to 99999 Relay 1 High Alarm Setpoint Enter the rate or time at which relay 1 will turn on if the rate or time goes above this value Range 0 to 99999 Relay 2 High Alarm...

Page 17: ...If subsequent errors occur the NOVRAM itself may have failed and the unit should be returned to the factory for repair An error message indicates that the calibration section of NOVRAM has been corrup...

Page 18: ...program enable input to ground Durant Jumper Terminals 1 and 2 1 2 3 4 3 While holding both the right arrow key and the up arrow key turn unit power ON Durant Power In The program LED and all display...

Page 19: ...splay shows software part number Right Arrow All display segments and the program LED turn off and the analog output goes to maximum value 20 mA and 10V Up Arrow Each display digit will turn on one at...

Page 20: ...ric Strength 2300 VAC to signal inputs and relays 500 VAC to RS 485 and analog outputs HUMAN INTERFACE Display 5 digits Type 56 high seven segment red LED Indicator One red LED program calibration ind...

Page 21: ...ogrammable Parity Even odd or no parity Address Range 00 to 99 decimal Protocol Opto 22 compatible Isolation Dielectric Strength 2300 VAC to signal inputs relays and AC power inputs 500 VAC to analog...

Page 22: ...are or may be to any extent liable including without limitation penalties imposed by the Consumer Product Safety Act P L 92 573 and liability imposed upon any person pursuant to the Magnuson Moss War...

Page 23: ...Durant 901 S 12th Street Watertown WI 53094 800 540 9242 920 261 4070 Fax 920 261 9097 www durant com...

Reviews: