7 Serial interface (Modbus RTU)
7.3 Operating mode Modbus RTU
154
DC1 Frequency Inverter
10/12 MN04020003Z-EN
www.eaton.com
7.3.4.2 Function code 06
hex
: Writing a holding register
This function writes data to a holding register.
Example
Writing of the control word (ID 1) of a DC1 frequency inverter with the slave
address 1.
Master request: 01 06 0000 0001 480A
hex
Slave response: 01 06 0000 0001 480
hex
The slave response is a copy of the master request if it is a normal response.
hex
Name
01
Station address
06
Function code (writing a holding register)
0000
0: The ID of the register for the writing operation is 1, since the master controller has an offset of +1.
0001
Content (2 byte) for register 0000 0000 0000 001
bin
→
RUN
480A
CRC
hex
Name
01
Station address
06
Function code (here. Writing of a holding register)
0000
1: The ID of the register for the writing operation is 1, since the master controller has an offset of +1.
0001
Content (2 byte) for register 0000 0000 0000 001
bin
→
RUN
B844
CRC
→
Function code 06
hex
can be used for a broadcast.