Table 24:
Assigned mains contactors
Device type
Rated operating voltage
Rated input
current
related mains contactor
DC1…
(50 Hz)
(60 Hz)
Part no.
thermal current AC-1
+50 °C
+40 °C
U
LN
U
LN
I
LN
I
N
I
N
[A]
[A]
[A]
DC1-1D2D3…
1 AC 110 V
1 AC 120 V
6.7
DILEM-10 + DILM12-XP1
20
22
DC1-1D4D3…
1 AC 110 V
1 AC 120 V
12.5
DILEM-10 + DILM12-XP1
20
22
DC1-1D5D8…
1 AC 110 V
1 AC 120 V
16.8
DILEM-10 + DILM12-XP1
20
22
DC1-1S24D3…
1 AC 230 V
1 AC 240 V
6.0
DILEM-10 + DILM12-XP1
20
22
DC1-1S27D0…
1 AC 230 V
1 AC 240 V
9.3
DILEM-10 + DILM12-XP1
20
22
DC1-1S2011…
1 AC 230 V
1 AC 240 V
14.0
DILEM-10 + DILM12-XP1
20
22
DC1-122D3…
1 AC 230 V
1 AC 240 V
6.7
DILEM-10 + DILM12-XP1
DILM7
20
21
22
DC1-124D3…
1 AC 230 V
1 AC 240 V
12.5
DILM7
21
22
DC1-127D0FN…
1 AC 230 V
1 AC 240 V
14.8
DILM7
21
22
DC1-127D0FB…
1 AC 230 V
1 AC 240 V
14.8
DILM7
21
22
DC1-12011…
1 AC 230 V
1 AC 240 V
22.2
DILM17
38
40
DC1-12015…
1 AC 230 V
1 AC 240 V
31.7
DILM17
38
40
DC1-322D3…
3 AC 230 V
3 AC 240 V
3.0
DILEM-10
20
22
DC1-324D3…
3 AC 230 V
3 AC 240 V
5.8
DILEM-10
20
22
DC1-327D0FN…
3 AC 230 V
3 AC 240 V
9.2
DILEM-10
20
22
DC1-327D0FB…
3 AC 230 V
3 AC 240 V
9.2
DILEM-10
20
22
DC1-32011…
3 AC 230 V
3 AC 240 V
13.7
DILM7
21
22
DC1-32018…
3 AC 230 V
3 AC 240 V
20.7
DILM7
DILM17
1)
21
38
22
40
DC1-342D2…
3 AC 400 V
3 AC 480 V
2.4
DILEM-10
20
22
DC1-344D1FN…
3 AC 400 V
3 AC 480 V
4.3
DILEM-10
20
22
DC1-344D1FB…
3 AC 400 V
3 AC 480 V
4.3
DILEM-10
20
22
DC1-345D8…
3 AC 400 V
3 AC 480 V
6.1
DILEM-10
20
22
DC1-349D5…
3 AC 400 V
3 AC 480 V
9.8
DILEM-10
20
22
DC1-34014…
3 AC 400 V
3 AC 480 V
14.6
DILM7
21
22
DC1-34018…
3 AC 400 V
3 AC 480 V
18.1
DILM7
21
22
DC1-34024…
3 AC 400 V
3 AC 480 V
24.7
DILM17
38
40
1) For UL® installation observe note
2) maximum operating tempe40 °C
→
For UL
®
compliant installation and operation, the mains side
switching devices must allow for a 1.25 times higher input cur-
rent. The switching devices meets this requirement.
Summary of Contents for DC1-12011 Series
Page 1: ...Manual PowerXL DC1 Frequency Inverter 10 12 MN04020003Z EN...
Page 4: ...II...
Page 12: ...0 About this manual 0 5 Units 8 DC1 Frequency Inverter 10 12 MN04020003Z EN www eaton com...
Page 190: ...9 Appendix 9 9 Sinusoidal filter 186 DC1 Frequency Inverter 10 12 MN04020003Z EN www eaton com...