2 Engineering
2.5 Motor and Application
DC1 Frequency Inverter
10/12 MN04020003Z-EN
www.eaton.com
43
2.5.6 Connecting EX motors
The following aspects must be taken into account when connectinghazard-
ous location motors:
•
The frequency inverter must be installed outside the EX area.
•
All applicable industry-specific and country-specific regulations for haz-
ardous locations (ATEX 100a) must be complied with.
•
The specifications and instructions provided by the motor’s manufac-
turer with regard to operation with a frequency inverter – e.g., whether
motor reactors (dV/dt limiting) or sinusoidal filters are required – must be
taken into account.
•
Temperature monitors in the motor windings (thermistor, Thermo-Click)
must not be connected directly to the frequency inverter, but instead
must be connected through a relay approved for the hazardous location
(e.g. EMT6).
2.5.7 Sinusoidal filter
Sinusoidal filters are connected in the output of a frequency inverter.
Figure 17:
Circuit Diagram of a sinusoidal filter
The sinusoidal filter removes high-frequency components above the set
resonance frequency from the frequency inverter output voltage (U
2
).
This reduces the conducted and radiated emission.
a
Without sinusoidal filter
b
With sinusoidal filter
f: Rotating field frequency
n: Order of harmonics
Figure 18:
High frequency components of the output voltage
U
2
U ∼
1U2
1V2
1W2
PE
1U1
1V1
1W1
PE
M
3 ~
①
②
f
2
5
10
15
20
25
30
35
40
45