Primary
Line
FU-4
Secondary
Secondary
Voltage
Connection
Connection
Jumper
Voltage
208 VAC
H5
X3
H1 to H3 and H2 to H5
110 VAC
380 VAC
H4
X3
H2 to H3
120 VAC
415 VAC
H5
X3
H2 to H3
120 VAC
460 VAC
H4
X2
H2 to H3
115 VAC
230 VAC
H4
X2
H1 to H3 & H2 to H4
115 VAC
The primary to FU-3 is factory connected to H1.
One secondary lead is factory connected to X1.
The X1 and H1 connections remain the same for all line voltages.
Easy-Start ES Instruction Manual
Options
SECTION 4
4-3
Available Options
Cat. No. Suffix
Description
T2
300VA control power
transformer. Other details
T4
500VA control transformer.
Other details same as T.
Y2
Time delay relay, (type TR)
delay on make.
Programmable Time
Settings:
1, 3, 6, 10, 60 seconds
5, 10 minutes
Y3
Auxiliary relay, contacts
and coil unwired.
Control Devices:
Cutler-Hammer Transformer Connections
Cat. No. Suffix
Description
T
150VA control power
transformer with 2 primary
fuses.
Easy-Start ES models have multi-voltage ratings.
Each model is factory wired for the following
incoming line voltage for Cutler-Hammer
transformer:
Easy-Start ES
Voltage Rating
CPT Wired For
208/230/460
460V
380/415
380V
If the incoming line voltage is different than the
one shown in above table, reconnect the CPT
primary and secondary as follows for Cutler-
Hammer transformers:
Easy ES-052
Volts
Connect
X2
X1
460
230
H2 to H3
H1 to H3 & H2 to H4
H1-H4
H1-H4
X1-X2
115
H1
H3
H2
H4
Diagram 1
Lines
Easy ES-053
Volts
Connect
X3
X2
X1
416
380
208
115
95
H1-H5
H1-H4
H2 to H3
H2 to H3
H1 to H3 & H2 to H4
H1 to H3 & H2 to H5
H1-H4
H1-H5
X1-X3
X1-X2
H1
H3
H2 H4
H5
Diagram 2
Lines