Easy-Start ES Instruction Manual
Operation
SECTION 3
3-4
DIP Switch Settings
For complete DIP switch calibration AC
current tables of all Models, see the
following tables (Tables 3-2 thru 3-12).
DIP Switch Ampere Settings ES045
Table 3-2
DS1
DS2
POSITIONS
123
123
123
123
123
123
123
123
1
2
3
4
000
001
010
011
100
101
110
111
0
0
0
0
12.7
11.1
10.1
9.0
8.0
7.4
6.9
6.4
0
0
0
1
16.4
14.4
13.1
11.8
10.5
9.7
9.1
8.4
0
0
1
0
19.4
17.2
15.6
14.2
12.7
11.7
10.9
10.2
0
0
1
1
22.5
20.0
18.3
16.6
14.9
13.8
12.9
12.1
0
1
0
0
25.5
21.8
20.0
18.2
16.3
15.1
14.2
13.3
0
1
0
1
27.2
24.4
22.4
20.4
18.4
17.0
16.0
15.0
0
1
1
0
29.5
26.5
24.4
22.3
20.2
18.7
17.6
16.5
0
1
1
1
31.9
28.8
26.5
24.3
22.0
20.5
19.3
18.1
1
0
0
0
33.4
30.2
27.9
25.6
23.2
21.7
20.4
19.2
1
0
0
1
35.6
32.2
29.8
27.5
25.0
23.3
22.0
20.7
1
0
1
0
37.4
34.0
31.5
29.1
26.5
24.7
23.4
22.0
1
0
1
1
39.2
35.7
33.2
30.7
28.0
26.2
24.8
23.4
1
1
0
0
40.4
36.9
34.3
31.8
29.0
27.2
25.8
24.3
1
1
0
1
42.0
38.5
35.9
33.3
30.5
28.6
27.1
25.6
1
1
1
0
43.5
39.9
37.3
34.6
31.8
29.9
28.2
26.8
1
1
1
1
45.0
41.4
38.7
36.0
33.1
31.1
29.6
28.0
StockCheck.com