Cooper Crouse-Hinds GmbH

33333

2

Safety instructions

Attention!  These "Annex for

operating instructions"

GHG 510 7003 P0004 is only for

use with the original operating

instructions   GHG 510 7003 P0001.

The GHG 514 plugs and sockets are not

suitable for Zone 0  hazardous areas.

For  installation only by qualified

electrician in accordance with the Natio-

nal Electric Code, Canadian Electric Code,

applicable local codes and the

instructions.

Select properwire size and type for load

and application. Refer to National Electric

Code, Article 400, for wire information.

The temperature class and explosion

group marked on the apparatus shall be

observed.

The operations must be carried out by

electrical suitably trained in hazardous

area with knowledge of increased safty

explosion protection

IEC 60079-14.

Modifications to the plugs and sockets or

changes of their design are not permitted.

They shall be used for their intended

purpose and in perfect and clean

condition.

For replacement and repair only genuine

COOPER CROUSE-HINDS / CEAG spare

parts shall be used.

Repairs that affect the explosion

protection, may only be carried out by

COOPER CROUSE-HINDS / CEAG or a

qualified electrician in compliance with

the respective national regulations.

Prior to taking the plugs and sockets into

operation, they will have to be checked in

accordance with the instruction as per

section 6.

The sockets may only be used with the

associated COOPER CROUSE-HINDS /

CEAG plugs in undamaged condition.

The interlocking switch of the socket is

mechanically secured by means of spring-

loaded locking pins, and  cannot be

connected without plug.

Before the initial operation, any foreign

matter will have to be removed from the

inside of the plugs and sockets.

Observe the national safety rules and

regulations for prevention of accidents as

well as the safety instructions included in

these operating instructions and set in

italics the same as this text!

Annex to operating instructions
Plug and socket system 60A, GHG 514

4

Field of application

The plugs and sockets GHG 514 are suitable
for use in:

Class I, Zone 1
Class I, Division 2  -

Groups A, B, C and D

Class II,Division 1  -

Groups E,F and G (cUL)!

The enclosure materials employed, including
the exterior metal parts, are made of high-
quality materials which ensure a corrosion
protection and resistance to chemical
substances corresponding to the
requirements in a “normal industrial
atmosphere”:

- impact resistant polyamide
- glass-fibre reinforced polyester
- special steel AISI 316 L

In case of use in an extremely aggresive
atmosphere, please refer to manufacturer

1x hub M40 / 1/4" NPT

+ 1x blanking plug M40

Wall socket

3

Conformity with standards

The plugs and sockets meet the
requirements of the following standards:

C22.2 No.0-M91

Canadian Electrical
Code Part II

C22.2 No.182.1-07

Plugs and
Receptacles

C22.2 No 60079-0-07

Electr. App. for Expl.

Gas Atmosp.- Part 0: General Requirements.

C22.2 No 60079-1-07

Electr. App. for Expl.

Gas Atmosp.- Part 1: Flameproof Enclosure
"d".

CSA

No 60079-7-03

Electr. App. for Expl.

Gas Atmosp.- Part 7: Increased Safety "e".

CSA

No 61241-1-1-03

  Electr. App.

protected by enclosures and surface
limitation - Specification for apparatus.

UL 1682-07

Plugs and Receptacles.

UL 1686-07

Pin and Sleeve Configurations.

UL 60079-0

Electr. App. for Expl. Gas

Atmosp.- Part 0: General Requirements.

UL 60079-1

Electr. App. for Expl. Gas

Atmosp.- Part 1: Flameproof Enclosure "d".

UL 60079-7

Electr. App. for Expl. Gas

Atmosp.- Part 7: Increased Safety "e".

UL 1203

Explosion-Proof and Dust

Ignition-Proof Electrical Equipment for use in
Hazardous (Classified) Locations.

Summary of Contents for Crouse-Hinds GHG 514

Page 1: ...lig GHG 514 Explosion protected plugs and sockets 63A 4 pole and 5 pole GHG 514 Fiche et prise de pour atmosphères explosives 63A à 4 pôles et 5 pôles GHG 514 GHG 510 7003 P0001 D E F g Betriebsanleitung Operating instructions Mode d emploi CEAG Products ...

Page 2: ...s 8 3 Conformity with standards 8 4 Field of application 8 5 Application Properties 8 9 6 Installation 9 6 1 Mounting 9 6 2 Opening the device Electrical connection 9 6 3 Cable entry KLE blanking plug 9 10 6 3 1 Sockets 9 10 6 3 2 Plug Coupler 10 6 4 Closing the device 10 6 5 Taking into operation 10 7 Maintenance Servicing 10 8 Repairs Modifications 10 9 Disposal Recycling 10 Declaration of confo...

Page 3: ... 1 2 1 2 min max 1 2 24 0 28 0 6 0 7 0 Dichtung 2 1 2 min max 2 28 0 35 0 5 0 7 0 Prüfdrehmomente Einschraubgewinde Nm 7 5 1 Der max Klemmbereiche für Leitungen mit der Kombination aus Dichtung 1 2 kann je nach verwendetem Leitungstyp und Anwendung variieren 2 Bei derWahl der Dichtungsgummis ist darauf zu achten dass bei zukünftigenWartungsarbeiten an der KLE die Druckschraube nachgezogen werden k...

Page 4: ...n der Zonen 1 2 und Zonen 21 22 gemäß EN IEC 60079 10 1 und EN IEC 60079 10 2 geeignet Die eingesetzten Gehäusematerialien ein schließlich der aussenliegenden Metallteile bestehen aus hochwertigenWerkstoffen die einen anwendungsgerechten Korrosionsschutz und Chemikalienresistenz in normaler Industrieatmosphäre gewährleisten schlagfestes Polyamid glasfaserverstärktes Polyester Edelstahl AISI 316 L ...

Page 5: ...n Die ordnungsgemäß abisolierten Anschlusslei tungen der Kabel sind unter Berücksichtigung einschlägiger Vorschriften anzuschließen Bild 3 4 Seite 6 Der Steckereinsatz Pos 3 ist durch Lösen der Befestigungsschrauben Pos 10 aus der Steckerhülse Pos 11 herauszunehmen Danach kann der Steckereinsatz an den Anschlüssen der Steckerstifte angeschlossen werden siehe Bild 5 Seite 6 Achtung BeiVerlust der B...

Page 6: ...erprüfen Vor jedem Stecken des Steckers in die Steckdose ist dieser auf Beschädigungen zu überprüfen Der Betreiber muss dafür sorgen dass beim Betrieb der Steckvorrichtung überall ein gleiches Erdpotential anliegt Unsachgemäße Installation und Betrieb der Steckvorrichtungen kann zum Verlust der Garantie führen 7 Instandhaltung Wartung Die für dieWartung Instandhaltung von elektrischen Betriebsmitt...

Page 7: ...able cables and test torques of the pressure srew Ø Nm seel 1 2 1 2 min max 1 2 24 0 28 0 6 0 7 0 seel 2 1 2 min max 2 28 0 35 0 5 0 7 0 Test torque for screw in thread cable entry Nm 7 5 1 The maximum clamping area for cables with the seal combination 1 2 can vary according to the type of cable used 2 When selecting the seal rubber ensure that the pressure screw can be tightened when carrying out...

Page 8: ...15V 500V 690V blue red black black GHG 514 4 pole 50 60Hz GHG 514 5 pole 50 60Hz GHG 514 5 pole 50 60Hz 220 250V 380 415V 500V 690V blue red black black w o auxiliary contact with auxiliary contact w o auxiliary contact with auxiliary contact They are conform to the standards specified in the EC Declaration of conformity enclosed separately 4 Field of application The plugs and sockets GHG 514 are ...

Page 9: ...terminal The conductor itself shall not be damaged Taking into account the respective regulations the properly bared conductors of the cables shall be connected Fig 3 4 page 10 The plug insert item 3 is removed from the pin bushing item 11 after the fastening screws item 10 have been unscrewed Thereafter the plug insert can be connected to the connec tions of the plug pins see fig 5 page 10 Attent...

Page 10: ...d The inappropriate installation and operation of the plugs and sockets can entail the loss of war ranty 7 Maintenance Servicing The relevant national regulations which apply to the maintenance servicing of electrical apparatus in explosive atmospheres shall be observed IEC EN 60079 17 Before opening the enclosure make sure that the device is disconnected from the voltage or take appropriate prote...

Page 11: ...2 1 2 min max 1 2 24 0 28 0 6 0 7 0 phoque 2 1 2 min max 2 28 0 35 0 5 0 7 0 Couple d essai pour l entrée de câble Nm 7 5 1 Lorsque les bagues 1 2 sont utilisées la capacité de serrage maximale peut varier légèrement selon le type de câble utilisé 2 Lors de la sélection des bagues d étanchéité au moment de l installation il faut s assurer qu il reste une marge de serrage suffisante au niveau du ch...

Page 12: ...GHG 514 4 pôles 50 60 Hz GHG 514 5 pôles 50 60 Hz GHG 514 5 pôles 50 60Hz 220 250V 380 415V 500V 690V bleu rouge noir noir sans contact avec contact auxiliaire auxiliaire sans contact avec contact auxiliaire auxiliaire 3 Conformité avec les normes Les Appareils ont été conçues fabriquées et contrôlées suivant DIN EN ISO 9001 2008 et EN ISO IEC 80079 34 2011 Les Appareils sont conformes aux normes ...

Page 13: ...nt reposer au niveau du mur qu en les points de fixation prévus La vis choisie doit correspondre au trou de fixation voir plan coté et elle ne doit pas avarier l ouverture par ex emploi d une rondelle Le dispositif doit être fixé en diagonale avec au moins deux vis Le montage de la prise murale doit se faire de sorte que l ouverture d enfichage ne soit pas dirigée vers le haut fig 2 6 2 Ouverture ...

Page 14: ...ôte du dispositif 6 5 Mise en service Avant la mise en service du matériel les vérifications spécifiées dans les règlements nationaux individuels devront être exécutées De plus il faudra vérifier son fonctionnement et installation corrects en conformité avec ce mode d emploi et avec d autres règlements y applicables Chaque fois que la fiche est enfichée dans la prise elle devra d abord être vérifi...

Page 15: ...15 EATON s Crouse Hinds Business Notizen Notes Remarques ...

Page 16: ...de la Union Europea EST Seda kasutusjuhendit oma riigikeeles võite küsida oma riigis asuvast asjaomasest Cooper Crouse Hindsi CEAG esindusest FIN Tarvittaessa tämän käyttöohjeen käännös on saatavissa toisella EU n kielellä Teidän Cooper Crouse Hinds CEAG edustajaltanne GR Cooper Crouse Hinds CEAG H A kezelési útmutatót az adott ország nyelvén a Cooper Crouse Hinds CEAG cég helyi képviseletén igény...

Page 17: ...se aluminium wiring Use copper wire only To avoid electrical shock electrical power must be off before and during installation inspection and maintenance To avoid electrical shock always disconnect primary power source before opening device or enclosure for inspection or service Observe the national safety rules and regulations Explosion protected plug and socket system 60 A 4 pole and 5 pole GHG ...

Page 18: ...atalogue version Wall socket 2 x M40 1 x hub M40 1 4 NPT 1 x blanking plug plug Coupler Ø 26 34 mm Supply terminal Cross section Stripped wire length Wall socket 2 x AWG 11 4 19 mm with cable lugs 1 x AWG 2 Plug 1 x AWG 11 5 12 mm with cable lugs 1 x AWG 4 Test torques Cover screws 2 5 Nm Terminals plug 2 4 Nm Terminals wall socket 3 5 Nm Self cutting screws size 4 2 0 Nm Self cutting screws size ...

Page 19: ... removed from the inside of the plugs and sockets Observe the national safety rules and regulations for prevention of accidents as well as the safety instructions included in these operating instructions and set in italics the same as this text Annex to operating instructions Plug and socket system 60A GHG 514 4 Field of application The plugs and sockets GHG 514 are suitable for use in Class I Zon...

Page 20: ... LRQH GHO PDQXDOH RSHUDWLYR LQ XQ DOWUD OLQJXD GHOOD RPXQLW j XURSHD SRWHWH ULFKLHGHUOD DO YRVWUR UDSSUHVHQWDQWH RRSHU URXVH LQGV 7 âLRV QDXGRMLPR LQVWUXNFLMRV LãYHUVWRV Ƴ njVǐ JLPWąMą NDOEą JDOLWH SDUHLNDODXWL DWVDNLQJRMH RRSHU URXVH LQGV DWVWRY EHMH VDYR ãDO MH 9 âR HNVSOXDWƗFLMDV LQVWUXNFLMX YDOVWV YDORGƗ YDUDW SLHSUDVƯW MXVX YDOVWV DWELOGƯJDMƗ RRSHU URXVH LQGV SƗUVWƗYQLHFƯEƗ 0 LVWJƫX MLWROEX GD...

Reviews: