Table 3 . Interrupting ratings
Recloser
type
Trip-coil
continuous
current (amps)
Minimum-
trip current
(amps)
Interrupting current
(rms symmetrical amps)
E
@24.9 kV
5
10
300
10
20
600
15
30
900
25
50
1500
35
70
2100
50
100
2500
70
140
2500
100
200
2500
4E
50
100
3000
70
140
4000
100
200
4000
140
280
4000
200
400
4000
280
560
4000
V4E
15
30
900
25
50
1500
35
70
2100
50
100
3000
70
140
4200
100
200
6000
140
280
6000
170
340
6000
200
400
6000
280
560
6000
H
@2.4 through 14.4 kV
5
10
125
10
20
250
15
30
375
25
50
625
35
70
875
50
100
1250
4H
@4.8
@8.32
@14.4
5
10
200
200
200
10
20
400
400
400
15
30
600
600
600
25
50
1000
1000
1000
35
70
1400
1400
1400
50
100
2000
2000
2000
70
140
2800
2500
2000
100
200
3000
2500
2000
V4H
5
10
200
200
200
10
20
400
400
400
15
30
600
600
600
25
50
1000
1000
1000
35
70
1400
1400
1400
50
100
2000
2000
2000
70
140
2800
2500
2000
100
200
3000
2500
2000
140
280
3000
2500
2000
200
400
3000
2500
2000
Recloser
type
Trip-coil
continuous
current (amps)
Minimum-
trip current
(amps)
Interrupting current
(rms symmetrical amps)
L
@4.8
@8.32
@14.4
25
50
1500
1500
1500
35
70
2100
2100
2100
50
100
3000
3000
3000
70
140
4200
4200
4000
100
200
6000
5000
4000
140
280
6000
5000
4000
200
400
6000
5000
4000
280
560
6000
5000
4000
V4L
@2.4 through 14.4 kV
15
30
900
25
50
1500
35
70
2100
50
100
3000
70
140
4200
100
200
6000
140
280
6000
170
340
6000
200
400
6000
280
560
6000
5
Types E, 4E, V4E, H, 4H, V4H, L, and V4L single-phase recloser installation and operation instructions
OPERATION INSTRUCTIONS
MN280051EN May 2017