background image

Series-trip solenoid

Fault-current sensing is provided by a series-connected 

solenoid coil that carries line current. When a fault occurs, 

tripping is initiated by the solenoid plunger.
The plunger, normally held at rest by the closing springs, is 

drawn into the coil by the magnetic force generated by the 

fault current. Downward travel of the plunger overtoggles 

springs in the contact assembly that open the recloser 

contacts. The same motion charges the closing springs in 

preparation for a reclosing operation.
When the circuit is opened, the solenoid coil is 

de-energized, allowing the closing springs to close the 

contacts and simultaneously return the plunger to its 

original position.

Hydraulic control mechanism

The hydraulic control mechanism provides selectivity in 

timing, enabling flexibility in application and coordination 

with other equipment. All timing is governed by the 

hydraulic mechanism that:
1.  Controls the timing before contact opening.
2.  Establishes the time delay before the contacts reclose.
3.  Counts the number of operations.
4.  Causes the recloser to lock out when the preset 

number of trip operations has been completed.

Fast and delayed timing characteristics

Variations of timing characteristics and sequences can be 

programmed for a maximum of four operations. When 

a recloser is programmed for both fast and delayed 

operations, the fast operations, involving no intentional 

time- delay, occur first in the sequence, according to the 

recloser’s “A” curve time-current characteristic. Delayed 

operations are according to the recloser’s “B” or “C” 

time-current curve (“B”, “C”, or “D” curves for Types E, 

4E, V4E, L and V4L). See 

Time Current Curves R280-91-10 

for Type E reclosers; 

R280-91-8

 for Type 4E; 

R280-91-1

 for 

Type H; 

R280-91-2

 for Types 4H, V4H; 

R280-91-15

 for Types 

V4E, V4L; and 

R280-91-3

 for Type L.

Figure 1 . Type H time-current characteristics, 50 amp coil

3600

3000
2400

1800

1200

600
480
360

300
240
180

120

60
48
36

30
24
18

12

6.0
4.8

3.6

3.0
2.4
1.8

1.2

0.6

5 6

8

10

20

30

40

50

60

80

100

200

300

400

500 600

800

1000

2000

60

50
40

30

20

10

8
6

5
4
3

2

1

.8
.6

.5
.4
.3

.2

0.1
.08

.06

.05
.04
.03

.02

.01

3000

4000

5000

CURRENT IN AMPERES

TCC-252

TIME IN SECONDS

TIME IN CYCLES (60-HERTZ BASIS)

50-AMP COIL -

RECLOSER CLEARING TIME

Curve A:  Maximum clearing time for

   one operation, variations  negative

Curves B & C: Average clearing time

   for one operation, variations ±10%

    Tests conducted at 25C

A

B

C

Figure 2 .  Recloser operating levers, indicators, and 

data plates

Non-reclosing

lever

Manual

operating

handle

Data plates

Sleet hood

Figure 3 .  Operations counter located under sleet hood

2

Types E, 4E, V4E, H, 4H, V4H, L, and V4L single-phase recloser installation and operation instructions

OPERATION INSTRUCTIONS

   MN280051EN   May 2017

Summary of Contents for COOPER POWER 4E

Page 1: ...Types E 4E V4E H 4H V4H L and V4L single phase recloser installation and operation instructions COOPER POWER SERIES Reclosers MN280051EN Effective May 2017 Supersedes April 2014 S280 10 8...

Page 2: ...OSE OR MERCHANTABILITY OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON THE CONTENTS OF THIS DOCUMENT SHALL NO...

Page 3: ...aracteristics 2 Data plates 3 Manual operating levers and indicators 3 Manual operating handle 3 Non reclosing lever 3 Operations counter 3 RATINGS AND SPECIFICATIONS 4 DIMENSIONS AND WEIGHTS 6 INSTAL...

Page 4: ...Life mission Safety information DANGER Hazardous voltage Contact with hazardous voltage will cause death or severe personal injury Follow all locally approved safety procedures when working around hig...

Page 5: ...mize the possibility of mechanical damage particularly to the bushings Standards Eaton s Cooper Power series reclosers are designed and tested in accordance with the following standards ANSI IEEE C37...

Page 6: ...maximum of four operations When a recloser is programmed for both fast and delayed operations the fast operations involving no intentional time delay occur first in the sequence according to the reclo...

Page 7: ...located under the sleet hood See Figure 3 WARNING Hazardous voltage This device is not a substitute for a visible disconnect Follow all locally approved safety practices Failure to follow proper safet...

Page 8: ...280 V4L 14 4 15 5 110 50 45 280 Table 2 Rated interruptions Recloser type Interrupting rating Maximum circuit X R ratio Number unit operations Total unit operations E 15 20 2 40 72 45 55 5 20 90 100...

Page 9: ...2000 70 140 2800 2500 2000 100 200 3000 2500 2000 V4H 5 10 200 200 200 10 20 400 400 400 15 30 600 600 600 25 50 1000 1000 1000 35 70 1400 1400 1400 50 100 2000 2000 2000 70 140 2800 2500 2000 100 20...

Page 10: ...POLE BOLT A G Figure 7 Dimensions of types E 4H and L reclosers Table 5 Recloser dimensions Description Recloser type E mm in 4E V4E mm in 4H V4H mm in L mm in V4L mm in A 380 15 380 15 355 14 380 15...

Page 11: ...yed operations a short time elapses between opening of contacts and placement of the operating handle in the OPEN position 5 Check data plates Make sure the ratings and settings on the recloser data p...

Page 12: ...recloser operation The recloser can be opened or closed manually regardless of the position of the non reclosing lever Figure 8 Connection diagram with switches to facilitate maintenance and complete...

Page 13: ...rs For further information contact your Eaton representative Factory maintenance classes The factory service department offers recloser maintenance training classes These classes taught by experienced...

Page 14: ...This page is intentionally left blank 10 Types E 4E V4E H 4H V4H L and V4L single phase recloser installation and operation instructions OPERATION INSTRUCTIONS MN280051EN May 2017...

Page 15: ...This page is intentionally left blank 11 Types E 4E V4E H 4H V4H L and V4L single phase recloser installation and operation instructions OPERATION INSTRUCTIONS MN280051EN May 2017...

Page 16: ...tes Eaton com cooperpowerseries 2017 Eaton All Rights Reserved Printed in USA Publication No MN280051EN May 2017 KA2048 0348 REV03 Eaton is a registered trademark All trademarks are property of their...

Reviews: