Operation

Initial operation

With the recloser connected as shown in Figure 8, close 

the source-side disconnect switch. Move the yellow manual 

operating handle under the sleet hood to the CLOSE 

position as indicated on the head cover. The recloser should 

immediately close. Close the load-side disconnect switch 

and open the bypass switch. The recloser is now in service. 

To remove from service, close the bypass switch and open 

the disconnect switches.

Manual operation

Manual operation of an energized E, H, or L group recloser 

requires a hotstick engagement of the yellow operating 

handle located under the sleet hood. When the handle 

is pulled down, the mechanism is tripped to open the 

main contacts. When the handle is pushed up, the main 

contacts close.

Non-reclosing operation

When the non-reclosing lever (Figure 2) has been manually 

pulled down into the non-reclosing position, any current 

over minimum-trip rating will automatically lock open 

the recloser on the first trip operation instead of cycling 

through the normal operating sequence. This immediate 

lockout protection is especially desirable for hot-line work. 

However, the non-reclosing lever does not interfere with 

manual recloser operation. The recloser can be opened 

or closed manually regardless of the position of the 

non-reclosing lever.

Figure 8 .  Connection diagram with switches to facilitate maintenance and complete surge protection

BYPASS SWITCH

RECLOSER

GND

SOURCE

LOAD

SURGE

ARRESTER

SURGE

ARRESTER

DISCONNECT

SWITCH

DISCONNECT

SWITCH

LOAD

SOURCE

MULTIGROUNDED

NEUTRAL 

 WARNING 

This equipment is not intended to protect human 

life . Follow all locally approved procedures and safety 

practices when installing or operating this equipment . 

Failure to comply can result in death, severe personal 

injury and equipment damage .

 

G102 .1

 WARNING 

Hazardous voltage . This device is not a substitute for 

a visible disconnect . Follow all locally approved safety 

practices . Failure to follow proper safety practices can 

result in contact with high voltage, which will cause 

death or severe personal injury .

 

G112 .1

 WARNING 

Hazardous voltage . Do not rely on the open position 

of the yellow operating handle or the contact position 

indicator; it does not ensure that the line has been 

de-energized . Always establish a visible disconnect . 

Failure to follow proper safety practices can result in 

contact with high voltage, which will cause death or 

severe personal injury . 

G114 .1

8

Types E, 4E, V4E, H, 4H, V4H, L, and V4L single-phase recloser installation and operation instructions

OPERATION INSTRUCTIONS

   MN280051EN   May 2017

Summary of Contents for COOPER POWER 4E

Page 1: ...Types E 4E V4E H 4H V4H L and V4L single phase recloser installation and operation instructions COOPER POWER SERIES Reclosers MN280051EN Effective May 2017 Supersedes April 2014 S280 10 8...

Page 2: ...OSE OR MERCHANTABILITY OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON THE CONTENTS OF THIS DOCUMENT SHALL NO...

Page 3: ...aracteristics 2 Data plates 3 Manual operating levers and indicators 3 Manual operating handle 3 Non reclosing lever 3 Operations counter 3 RATINGS AND SPECIFICATIONS 4 DIMENSIONS AND WEIGHTS 6 INSTAL...

Page 4: ...Life mission Safety information DANGER Hazardous voltage Contact with hazardous voltage will cause death or severe personal injury Follow all locally approved safety procedures when working around hig...

Page 5: ...mize the possibility of mechanical damage particularly to the bushings Standards Eaton s Cooper Power series reclosers are designed and tested in accordance with the following standards ANSI IEEE C37...

Page 6: ...maximum of four operations When a recloser is programmed for both fast and delayed operations the fast operations involving no intentional time delay occur first in the sequence according to the reclo...

Page 7: ...located under the sleet hood See Figure 3 WARNING Hazardous voltage This device is not a substitute for a visible disconnect Follow all locally approved safety practices Failure to follow proper safet...

Page 8: ...280 V4L 14 4 15 5 110 50 45 280 Table 2 Rated interruptions Recloser type Interrupting rating Maximum circuit X R ratio Number unit operations Total unit operations E 15 20 2 40 72 45 55 5 20 90 100...

Page 9: ...2000 70 140 2800 2500 2000 100 200 3000 2500 2000 V4H 5 10 200 200 200 10 20 400 400 400 15 30 600 600 600 25 50 1000 1000 1000 35 70 1400 1400 1400 50 100 2000 2000 2000 70 140 2800 2500 2000 100 20...

Page 10: ...POLE BOLT A G Figure 7 Dimensions of types E 4H and L reclosers Table 5 Recloser dimensions Description Recloser type E mm in 4E V4E mm in 4H V4H mm in L mm in V4L mm in A 380 15 380 15 355 14 380 15...

Page 11: ...yed operations a short time elapses between opening of contacts and placement of the operating handle in the OPEN position 5 Check data plates Make sure the ratings and settings on the recloser data p...

Page 12: ...recloser operation The recloser can be opened or closed manually regardless of the position of the non reclosing lever Figure 8 Connection diagram with switches to facilitate maintenance and complete...

Page 13: ...rs For further information contact your Eaton representative Factory maintenance classes The factory service department offers recloser maintenance training classes These classes taught by experienced...

Page 14: ...This page is intentionally left blank 10 Types E 4E V4E H 4H V4H L and V4L single phase recloser installation and operation instructions OPERATION INSTRUCTIONS MN280051EN May 2017...

Page 15: ...This page is intentionally left blank 11 Types E 4E V4E H 4H V4H L and V4L single phase recloser installation and operation instructions OPERATION INSTRUCTIONS MN280051EN May 2017...

Page 16: ...tes Eaton com cooperpowerseries 2017 Eaton All Rights Reserved Printed in USA Publication No MN280051EN May 2017 KA2048 0348 REV03 Eaton is a registered trademark All trademarks are property of their...

Reviews: