Data plates

The recloser data plates, located on the sleet hood 

(see Figure 2), provide ratings information including: 

product type and serial number, nominal operating voltage, 

maximum-interrupting current, trip coil rating, operating 

sequence, and number of operations to lockout. Be sure that 

the ratings and settings are correct for the planned installation.

Manual operating levers and indicators

The operating levers and indicators for the recloser are 

located under the sleet hood. See Figure 2.

Manual operating handle

The manual operating handle (yellow handle) permits manual 

opening and closing of an energized recloser. It is not to 

be used as a substitute for a visible disconnect during line 

work. Pulling down the handle trips and locks open the main 

contacts of the recloser. Lifting up the handle closes the 

main contacts. The handle is operated with a hotstick.

The correct placement of the hotstick for closing the 

recloser is shown in Figure 4. The correct placement of the 

hotstick to open the recloser is shown in Figure 5. Place the 

hotstick hook into the eyelet of the manual operating handle 

and pull downward.

Non-reclosing lever

The non-reclosing lever provides the recloser with the 

capability of locking out on the first trip operation for added 

safety during downline, hot-line work. This lever is also 

hotstick operated.

Operations counter

A four-digit mechanical counter, which records all trip 

operations, is located under the sleet hood. See Figure 3.

WARNING 

Hazardous voltage . This device is not a substitute for 

a visible disconnect . Follow all locally approved safety 

practices . Failure to follow proper safety practices can 

result in contact with high voltage, which will cause 

death or severe personal injury . 

G112 .1

WARNING 

Hazardous voltage . Do not rely on the open position 

of the yellow operating handle or the contact position 

indicator; it does not ensure that the line has been 

de-energized . Always establish a visible disconnect . 

Failure to follow proper safety practices can result in 

contact with high voltage, which will cause death or 

severe personal injury . 

G114 .1

DANGER

Hazardous voltage . Contact with hazardous voltage will 

cause death or severe personal injury . Follow all locally 

approved safety procedures when working around high 

and low voltage lines and equipment . 

G103 .3

 IMPORTANT 

The hotstick tip must be placed in the groove under the 

eyelet of the manual operating handle when closing 

the switch .

 IMPORTANT 

The manual operating handle is trip-free . If the recloser is 

closed against a fault, it will continue to trip and reclose 

until the handle is allowed to drop to the open position .

Figure 4 .  Correct placement of the hotstick to close 

the recloser

To close, place hotstick tip 

against manual operating 

handle and push upward.

Figure 5 .  Correct placement of hotstick to open recloser

To open, insert hotstick 

tip into eyelet of manual 

operating handle and pull 

downward.

3

Types E, 4E, V4E, H, 4H, V4H, L, and V4L single-phase recloser installation and operation instructions

OPERATION INSTRUCTIONS

   MN280051EN   May 2017

Summary of Contents for COOPER POWER 4E

Page 1: ...Types E 4E V4E H 4H V4H L and V4L single phase recloser installation and operation instructions COOPER POWER SERIES Reclosers MN280051EN Effective May 2017 Supersedes April 2014 S280 10 8...

Page 2: ...OSE OR MERCHANTABILITY OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON THE CONTENTS OF THIS DOCUMENT SHALL NO...

Page 3: ...aracteristics 2 Data plates 3 Manual operating levers and indicators 3 Manual operating handle 3 Non reclosing lever 3 Operations counter 3 RATINGS AND SPECIFICATIONS 4 DIMENSIONS AND WEIGHTS 6 INSTAL...

Page 4: ...Life mission Safety information DANGER Hazardous voltage Contact with hazardous voltage will cause death or severe personal injury Follow all locally approved safety procedures when working around hig...

Page 5: ...mize the possibility of mechanical damage particularly to the bushings Standards Eaton s Cooper Power series reclosers are designed and tested in accordance with the following standards ANSI IEEE C37...

Page 6: ...maximum of four operations When a recloser is programmed for both fast and delayed operations the fast operations involving no intentional time delay occur first in the sequence according to the reclo...

Page 7: ...located under the sleet hood See Figure 3 WARNING Hazardous voltage This device is not a substitute for a visible disconnect Follow all locally approved safety practices Failure to follow proper safet...

Page 8: ...280 V4L 14 4 15 5 110 50 45 280 Table 2 Rated interruptions Recloser type Interrupting rating Maximum circuit X R ratio Number unit operations Total unit operations E 15 20 2 40 72 45 55 5 20 90 100...

Page 9: ...2000 70 140 2800 2500 2000 100 200 3000 2500 2000 V4H 5 10 200 200 200 10 20 400 400 400 15 30 600 600 600 25 50 1000 1000 1000 35 70 1400 1400 1400 50 100 2000 2000 2000 70 140 2800 2500 2000 100 20...

Page 10: ...POLE BOLT A G Figure 7 Dimensions of types E 4H and L reclosers Table 5 Recloser dimensions Description Recloser type E mm in 4E V4E mm in 4H V4H mm in L mm in V4L mm in A 380 15 380 15 355 14 380 15...

Page 11: ...yed operations a short time elapses between opening of contacts and placement of the operating handle in the OPEN position 5 Check data plates Make sure the ratings and settings on the recloser data p...

Page 12: ...recloser operation The recloser can be opened or closed manually regardless of the position of the non reclosing lever Figure 8 Connection diagram with switches to facilitate maintenance and complete...

Page 13: ...rs For further information contact your Eaton representative Factory maintenance classes The factory service department offers recloser maintenance training classes These classes taught by experienced...

Page 14: ...This page is intentionally left blank 10 Types E 4E V4E H 4H V4H L and V4L single phase recloser installation and operation instructions OPERATION INSTRUCTIONS MN280051EN May 2017...

Page 15: ...This page is intentionally left blank 11 Types E 4E V4E H 4H V4H L and V4L single phase recloser installation and operation instructions OPERATION INSTRUCTIONS MN280051EN May 2017...

Page 16: ...tes Eaton com cooperpowerseries 2017 Eaton All Rights Reserved Printed in USA Publication No MN280051EN May 2017 KA2048 0348 REV03 Eaton is a registered trademark All trademarks are property of their...

Reviews: