Ratings and specifications
Table 1 . Ratings and specifications
Recloser type
Rated system
nominal
voltage (kV)
Rated system
max. voltage (kV)
Rated system
withstand voltage
(BIL) (kV)
60 Hz Insulation level
withstand rating
Continuous
current (amps)
Dry 1-Min. (kV)
Wet 10-Sec (kV)
E
24.9
27
150
60
50
100
4E
24.9
27
150
60
50
280
V4E
24.9
27
150
60
50
280
H
14.4
15.0
95
35
30
50
4H
14.4
15.5
110
50
45
100
V4H
14.4
15.5
110
50
45
200
L
14.4
15.5
110
50
45
280
V4L
14.4
15.5
110
50
45
280
Table 2 . Rated interruptions
Recloser type
% Interrupting rating
Maximum circuit X/R ratio Number unit operations
Total unit operations
E
15-20
2
40
72
45-55
5
20
90-100
12
12
4E
15-20
3
32
64
45-55
6
20
90-100
13
12
V4E
15-20
3
96
248
45-55
7
120
90-100
15
32
H
15-20
2
40
100
45-55
4
40
90-100
8
20
4H
15-20
2
32
68
45-55
5
24
90-100
10
12
V4H
15-20
2
128
272
45-55
5
96
90-100
10
48
L
15-20
3
32
64
45-55
6
20
90-100
12
12
V4L
15-20
3
96
248
45-55
7
120
90-100
15
32
4
Types E, 4E, V4E, H, 4H, V4H, L, and V4L single-phase recloser installation and operation instructions
OPERATION INSTRUCTIONS
MN280051EN May 2017