31
CF3000 InstAllAtIon And oPerAtIon MAnuAl
25-14682-A July 2019 www.eaton.com
Equipment compatibility
Equipment compatibility
Sensors
Loop wired sensors must be of the Eaton Fire Systems soft addressed analogue
type . Eaton Fire Systems conventional detectors can be connected via an CZMU352
interface . The connection of other detector types via an CZMU352
interface is not recommended .
Call points
Loop wired call points must be the Eaton Fire Systems soft addressed analogue
type, Eaton Fire Systems conventional callpoints can be connected via an CZMU352
interface . The connection of other callpoint types via an CZMU352 interface
is not recommended,
Sounders
Loop powered addressable sounders must be of the Eaton Fire Systems soft
addressed analogue type .
Conventional sounders can also be connected either to the conventional sounder
circuits at the panel or to the loop via a CSC354 addressable sounder controller
interface providing they meet the following:
•
They are suitable for operation between 18V and 28V
•
They are polarised and suppressed
•
The total alarm load is less than the rating of the panel/Alarm Power Interface
ote:
n
It is possible to use devices outside these requirements if they are supplied
with power from a separate source and switched via a suitable relay .
Relay circuits
Additional relays can be added to the system by using either
CMIO353 or CIO351 relay units .