Commissioning the Control Panel System
Commissioning the Control Panel System
Commissioning mode
Walk test mode allows a single engineer to test the various sensors and call points
on a system without always having to return to the panel either to reset the system
or silence the alarms . When in COMMISSIONING MODE, the system operates as
normal except that when a Sensor or call point goes into alarm, the alarms only
operate for a few seconds and then will silence . After a full test has been carried
out the engineer can check the order in which the sensors/call points were operated
using the DISPLAY LOG mode . This information can also be printed on
the optional printer .
When the panel is in “Walk Test Mode” the control panel inserts a different code
into the log and also onto the print-out . This is to distinguish between when a device
has been tested in “Walk Test Mode” and when a device has been triggered while in
normal operation .
The following differences will occur:
I. When in the LOG mode, “One man walk test”” will appear on the display
followed by the address text and device type
II. On the printout a “One man walk test” message will appear will appear
followed by the address text and device type
III. During a real fire “FIRE !” Will appear on the display followed by the
address text and device type
Configuration
DB level check
The panel includes the facility to test and set the system sounders with the
minimum amount of disturbance . In sounder test mode, the sounders will sound for
30 seconds on then 30 seconds off . This facility can be accessed via
the engineering menu .
Sensor LED flashing
The control panel Sensor flashing function is used to allow a visual inspection and
confirmation that the fire panel is in communication with the installed system
devices . This facility can be accessed via the engineering menu and can be switched
on or off at any time as required .