CF3000 InstAllAtIon And oPerAtIon MAnuAl
25-14682-A July 2019 www.eaton.com
Technical specification
outputs
1. Extinguisher released -> output high 26v
2. FRE operated
3. FPE disabled
4. FRE disabled
5. Panel in fire, will remain on after panel soft reset for > 15 minutes, or
extinguish immediately with interface reset
6. Disable all sounders
Optional Functions not approved to EN54 P2&4
Italian mode: (option not required by en54 pt2)
This mode can be programmed at access level 3 . This relates to points 12 .2(a) &
12 .2(b) of the Internal Italian Ministerial Decree 9th April 1994 which states that
in the event of a fire detection from 2 or more detectors or from an MCP there
should be a 2 minute delay before output activation otherwise in the event of a fire
detection from any one detector there should be a 5 minute delay before output
activation, provided that the fire event is not acknowledged . These delays apply to
siren activation as well as the shutting down/activation of other external equipment
and additionally the legislation states that these delays should be adjustable
depending on the type of activity being carried out within the building .
For example, if there was a fire detected from a single detector then we should
start a 5-minute (adjustable) delay (T2) . If however a fire is detected from a second
detector or a call-point the delay should automatically revert to 2 minutes (adjustable)
(T1) . In this scenario the value of (T1) is critical . To keep things simple, let’s assume
that we set T1 = 2 minutes & T2 = 5 minutes .
day/night (option not required by en54 pt2 )
This mode can be programmed at access level 3 . An interface needs to programmed
in day/night . When this interface is set to off, the panel is in Day mode . In the event
of fire, the detectors respond in heat mode, not smoke mode .
When the panel is in Night mode (interface is set to on), the delay is set to zero .
swedish mode (option not required by en54 pt2)
This mode is programmed at access level 3 . One of the Swedish requirements is
that access level 2 & 3 is only avalailabe by the access of the keyswitch . The key
switch is wired to the class change input .
Commission per loop (option not required by en54 pt2)
This mode is programmed at access level 3 . This allows the commissioning engineer
to auto learn one loop at the time