CF3000 InstAllAtIon And oPerAtIon MAnuAl
25-14682-A July 2019 www.eaton.com
Installation
Fixing details
Read all the installation instructions before commencing with the installation .
The installation of this panel must be carried out by a suitably qualified /trained
person . The installation must comply with IEE wiring regulations and with
BS5839 part 1 2002 .
The electronic components within the fire panel are Static Sensitive.
Do not touch the electronics directly.
Mounting the backbox
The panel can be flush mount or surface mounted .
1. Surface Mount; drill four holes and fix the backbox to the wall
2. Flush mounting the backbox requires a hole 364x 472 with a depth of
117mm (standard battery / backbox ) or 217 mm if deep backbox is used
Installing Cabling
Once the backbox is mounted the next stage is to install the power and loop cables
and fit the glands .
364mm
117mm
132mm
472mm
227mm
309mm
400mm
479mm