42
CF3000 InstAllAtIon And oPerAtIon MAnuAl
25-14682-A July 2019 www.eaton.com
Technical specification
Optional auxiliary board VDS requirement
(option not required by en54)
This board can be connected to an Extinguishing system as well as a Fire Brigade
Control Panel . This board has been tested and approved in according with DIN14661
and DIN 14675 .
Optional functions as per EN54 P2&4
Inputs/outputs to the fire brigade panel
Outputs
•
Output 1: Fire protecting equipment operated “Extinguishing On”
This output is ON in alarm condition to indicate that the Control and indicating equipment has
operated the fire protecting equipment (option 7.10 of EN54 pt2 )
•
Output 2: Fire Routing Equipment operated “Fire Brigade Link”
This output is ON in alarm condition to indicate that the Control and indicating equipment has
operated the fire routing equipment (option 7.9 of EN54 pt2 ).
•
Output 3: Disablement of Fire Protecting Equipment
This output is ON to indicate that the fire Protecting equipment has been disabled either by the control
and indicating equipment or the Fire Brigade Panel.
•
Output 4: Disablement of the Fire Routing Equipment
This output is ON to indicator that the fire routing equipment has been disabled either by the control
and indicating equipment or the Fire Brigade Panel.
•
Output 5: Reset from Fire Alarm Condition
This output is ON to indicate that the control and indicating Equipment is in alarm condition.
This output will remain on for at least 15mins after reset or when the reset has been activated from
the Fire Alarm Brigade Panel
•
Output 6: Disablement of Sounders
This output is ON to indicate that the sounders have been disabled either by the control and indicating
equipment or the Fire Brigade Panel.