Technical Data and Specifications
C440/XTOE Electronic Overload Relay, DeviceNet
MN04210002E—March 2011 www.eaton.com
7
Electronic Overload Relays Up to 1500A—Ratings and Specifications, continued
Short Circuit Ratings
Short Circuit Ratings (North America CSA, cUL)
Changes to UL 508A and NEC in recent years have brought a focus to control panel safety with regard to short-circuit current
ratings (SCCR). Eaton’s C440 electronic overload relays combined with
XT
series IEC and Freedom Series NEMA contactors
provide a wide variety of SCCR solutions needed for a variety of applications. The SCCR data in this document reflects the
latest information as of April 2010.
C440/
XT
Standalone Overload Relays (
XT
, C440)
Specification
Description
45 mm
55 mm
Electrical/EMC, continued
Surge immunity
IEC 60947-4-1 (Table 13)
IEC 61000-4-5 a Class 4
Three-phase power inputs:
±4 kV line-to-line (DM)
±4 kV line-to-ground (CM)
Three-phase power inputs:
±4 kV line-to-line (DM)
±4 kV line-to-ground (CM)
With accessory installed in expansion bay:
±2 kV line-to-line (DM) –>1.2/50 us;
2 kV line-to-earth, 1 kV line-to-line
±4 kV line-to-ground (CM)
With accessory installed in expansion bay:
±2 kV line-to-line (DM) –>1.2/50 us;
2 kV line-to-earth, 1 kV line-to-line
±4 kV line-to-ground (CM)
Power freq. magnetic field immunity
IEC 60947-4-1, IEC 61000-4-8
30A/m, 50 Hz
30A/m, 50 Hz
Electromagnetic field
IEC 60947-4-1 Table 13, IEC 61000-4-3
10V/m
10V/m
Distortion IEEE 519
5% THD max., 5th harmonic 3% max.
5% THD max., 5th harmonic 3% max.
Electrostatic discharge (ESD)
IEC 61000-4-2, EN 61131-2
4 kV contact
8 kV air discharge
4 kV contact
8 kV air discharge
Electrical fast transient (EFT)
IEC 61000-4-4, EN 61131-2
±2 kV using direct method
±2 kV using direct method
Surge immunity
IEC 61000-4-5, EN 61131-2
±2 kV line-to-ground (CM)
±2 kV line-to-ground (CM)
Overload
FLA Range
Maximum
Operating
Voltage
Standard-Fault Short Circuit Data
High-Fault Short Circuit Data
600V
(kA)
Maximum
Fuse Size (A)
(RK5)
Maximum
Breaker
Size (A)
Fuses (RK5, J, CC)
Thermal-Magnetic Circuit Breakers
480V
(kA)
600V
(kA)
Maximum
Fuse Size
480V
(kA)
600V
(kA)
Maximum
Breaker Size
0.33–1.65A
600 Vac
1
6
15
—
—
—
—
—
—
1–5A
600 Vac
5
20
20
100
100
30
100
35
20
4–20A
600 Vac
5
80
80
100
100
100
100
35
80
9–45A
600 Vac
5
175
175
100
100
100
100
35
100/175 (480/600)
20–100A
600 Vac
10
400
400
100
100
200
150
35
250/400 (480/600)
C440 DeviceNet.book Page 7 Friday, March 25, 2011 10:41 AM
For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616